Line & Duct Burners
RatioStar
RatioStar uses stainless-steel modules in rows of up to 24, with propagation modules carrying ignition between rows.
RatioStar uses stainless-steel modules in rows of up to 24, with propagation modules carrying ignition between rows. On-ratio control and configurable burner matrices address process-air distribution, reduced oxygen and elevated inlet temperatures. Eclipse can engineer a complete duct and gas-train system around the required heating duty.
Features & Benefits
- Velocity Across Burner
- Advised ≈10-15 m/s; Range ≈5-25 m/s
- Nozzle Gas Pressure
- Natural Gas 59 mbar; Propane 25 mbar
- Typical Excess Air
- ≈30% (λ ≈ 1.3 at maximum input)
- Temperature Limits
- Upstream: 1110 deg F (600 deg C), Downstream: 1830 deg F (1000 deg C)
- Air Inlet Pressure
- ± 10 to 15 mbar
- Flame Supervision
- UV Scanner only
- Air Pressure Drop
- 2 to 2.5 mbar across stabilization plate
- Turndown Ratio
- 1:5 on air
- Input Capacity
- Max - 425,000 Btu/h (125 kW) per module|Min - 42,500 Btu/h (12.5 kW) per module
- Control Method
- Mechanically or electronically linked air/gas valves
- Ignition Type
- Pilot
- Flame Length
- ≈1500 mm from Stabilization Plate
- Model Name
- RatioStar RAS, Version 1
- Dimensions
- ≈150 x 150 mm
- Fuel Type
- Natural Gas; Propane (other gases on request)
- Emissions
- CO and NOx performance shown in datasheet graphs (application‑dependent)
- Approvals
- Gas Manifold: AISI 316L (1.4404); Stabilization Plate: Avesta 253 MA (1.4893); Flame Shield: Avesta 253 MA (1.4893); Gas Nozzles: AISI 321 (1.4541)
- Configurable rows distribute heat around the process-air profile.
Applications
- Process-air heating
- Low-oxygen process-air reheating
- High-inlet-temperature air heating
Detailed capabilities
Rows, propagation and hot process air
RatioStar rows contain up to 24 stainless modules, with propagation modules linking rows for cross-ignition. The matrix can therefore follow the duct and required heat pattern. On-ratio control addresses efficiency, including low-oxygen streams needing added heat and elevated inlet temperatures beyond standard air-heater duties. A complete duct/gas-train system can be engineered around the process rather than inferred from a module alone.
Features and benefits
- Configurable rows distribute heat around the process-air profile.
Published application context
- Process-air heating
- Low-oxygen process-air reheating
- High-inlet-temperature air heating
Processing & Performance Metrics
- Velocity Across Burner
- Advised ≈10-15 m/s; Range ≈5-25 m/s
- Emissions
- CO and NOx performance shown in datasheet graphs (application‑dependent)
Pressure Specifications
- Nozzle Gas Pressure
- Natural Gas 59 mbar; Propane 25 mbar
Combustion Air, Blower & Emissions Specifications
- Typical Excess Air
- ≈30% (λ ≈ 1.3 at maximum input)
Temperature Control/Measurement
- Temperature Limits
- Upstream: 1110 deg F (600 deg C), Downstream: 1830 deg F (1000 deg C)
Air & Combustion Air Specifications
- Air Inlet Pressure
- ± 10 to 15 mbar
- Air Pressure Drop
- 2 to 2.5 mbar across stabilization plate
Ignition, Flame & Supervision Specifications
- Flame Supervision
- UV Scanner only
- Ignition Type
- Pilot
Performance, Flow & Capacity
- Turndown Ratio
- 1:5 on air
Performance Specifications
- Input Capacity
- Max - 425,000 Btu/h (125 kW) per module; Min - 42,500 Btu/h (12.5 kW) per module
Control, Logic & Functional Behavior
- Control Method
- Mechanically or electronically linked air/gas valves
Burner/Flame‑Related Lengths
- Flame Length
- ≈1500 mm from Stabilization Plate
Overview
- Model Name
- RatioStar RAS, Version 1
Dimensions & Weight
- Dimensions
- ≈150 x 150 mm
Fuel, Gas & Media Specifications
- Fuel Type
- Natural Gas; Propane (other gases on request)
Standards & Certifications
- Approvals
- Gas Manifold: AISI 316L (1.4404); Stabilization Plate: Avesta 253 MA (1.4893); Flame Shield: Avesta 253 MA (1.4893); Gas Nozzles: AISI 321 (1.4541)
| Parameter | Published value / configuration |
|---|---|
| Velocity Across Burner | Advised ≈10-15 m/s; Range ≈5-25 m/s |
| Emissions | CO and NOx performance shown in datasheet graphs (application‑dependent) |
| Nozzle Gas Pressure | Natural Gas 59 mbar; Propane 25 mbar |
| Typical Excess Air | ≈30% (λ ≈ 1.3 at maximum input) |
| Temperature Limits | Upstream: 1110 deg F (600 deg C), Downstream: 1830 deg F (1000 deg C) |
| Air Inlet Pressure | ± 10 to 15 mbar |
| Air Pressure Drop | 2 to 2.5 mbar across stabilization plate |
| Flame Supervision | UV Scanner only |
| Ignition Type | Pilot |
| Turndown Ratio | 1:5 on air |
| Input Capacity | Max - 425,000 Btu/h (125 kW) per module; Min - 42,500 Btu/h (12.5 kW) per module |
| Control Method | Mechanically or electronically linked air/gas valves |
| Flame Length | ≈1500 mm from Stabilization Plate |
| Model Name | RatioStar RAS, Version 1 |
| Dimensions | ≈150 x 150 mm |
| Fuel Type | Natural Gas; Propane (other gases on request) |
| Approvals | Gas Manifold: AISI 316L (1.4404); Stabilization Plate: Avesta 253 MA (1.4893); Flame Shield: Avesta 253 MA (1.4893); Gas Nozzles: AISI 321 (1.4541) |
Values retain manufacturer model qualifications. Review Honeywell specifications ↗
Part Number
Published part numbers
10 parts
| Part Number | Description | Enquiry |
|---|---|---|
| 00.4121003.11 | PLT,STABILISATION,FFB,RAS | Request quotation |
| 00.4121003.12 | PLT,PROPAGATION,FFB | Request quotation |
| 00.4121003.15 | PLT,PROPAGATION,FFB,151 MM | Request quotation |
| 00.4121006.00 | MTG STRP,FLUE FIRE BRNR | Request quotation |
| 00.4121028.04 | NZL,GAS,RAS,HP,SPR ONLY | Request quotation |
| 00.4121028.13 | NOZZLE GAS RAS LOW PRESSURE | Request quotation |
| 00.4121028.14 | NZL,GAS,PROPAGATION,RAS,FFB | Request quotation |
| 00.4121029.11 | PLT,END,RAS | Request quotation |
| 00.4121029.13 | PLT,END,RAS,PILT | Request quotation |
| 00.4121029.17 | PLT,END,UV,PILT,500 MM,151MM | Request quotation |