Line & Duct Burners
Linnox
Linnox ULE combines excess-air premixing with an internal recirculating flame to limit combustion temperature and emissions.
Linnox ULE combines excess-air premixing with an internal recirculating flame to limit combustion temperature and emissions. Modular geometry distributes heat in direct or indirect air-heating duties. Ratio-regulator control and 10:1 turndown support operation, while Linnox Tee arrangements add rows for higher input; emission values retain their published oxygen reference.
Features & Benefits
- Control Motor Specifications
- Rotation ≤2 rpm (≈30 s/90 deg typical); ≥25 in-lb (2.8 Nm) torque; 90 deg stroke; continuous or high/low modulating; reversible.
- Air Pressure Requirement
- 20 in wc (50 mbar) at burner inlet at maximum input
- Standard Burner Length
- Longer lengths as engineered orders|Up to 9 ft (2700 mm) standard
- Ratio Control Device
- Eclipse‑supplied ratio regulator required
- Combustion Method
- High‑excess‑air pre‑mix combustion with internal flame recirculation
- Airflow Direction
- Process air must flow parallel to burner flame (no cross‑flow)
- Mounting Options
- Mounting plate for installation into process air duct (insulated or non‑insulated)
- Control Actuator
- Control actuator modulates air butterfly valve
- Flame Detection
- UV Scanner only (no flame rod option)
- Turndown Ratio
- 10:1 or 8:1 turndown configurations
- Number of Rows
- Up to 4 burner rows in a single duct
- Input Capacity
- 90 to 2700 kBtu/h per module (26 to 791 kW per 300 mm)
- Ignition Type
- Direct Spark Ignition
- Burner Design
- Pre‑mix line burner for direct air heating
- Burner Style
- Available in straight sections, double T geometries, and cross sections.
- Fuel Type
- Natural Gas (alternative fuels require Eclipse consultation)
- Emissions
- Designed for ultra‑low NOx and CO across the turndown range
- Material
- Stainless steel housing; for sizes above AB600L, standard steel plate (consult Eclipse for >500°F upstream temperatures).
- Premixing and recirculation lower flame temperature and NOx.
Applications
- Direct and indirect air heating
Detailed capabilities
Why Linnox uses excess air and recirculation
Linnox ULE first premixes fuel with excess air to limit flame temperature, then uses the burner geometry to recirculate the flame internally. This combination addresses stable low-emission operation rather than relying on high flame temperature. A ratio regulator controls the gas/air relationship. The page reports both nominal-input and oxygen-corrected emissions figures; those reference conditions should accompany the numbers wherever reproduced.
Module rows and system sizing
The burner serves direct or indirect air heating where temperature distribution and emissions matter. Input per unit length can be configured around the required layout, with Linnox Tee adding multiple module rows for inputs up to the stated 45 million Btu/hr. Honeywell describes custom-engineered systems, so the full input, layout and control arrangement are established for the installation rather than selected from one common burner package.
Features and benefits
- Premixing and recirculation lower flame temperature and NOx.
Published application context
- Direct and indirect air heating
Overview
- Models
- Straight ULE and Tee ULE
Motor Specifications
- Control Motor Specifications
- Rotation ≤2 rpm (≈30 s/90 deg typical); ≥25 in-lb (2.8 Nm) torque; 90 deg stroke; continuous or high/low modulating; reversible.
Air & Combustion Air Specifications
- Air Pressure Requirement
- 20 in wc (50 mbar) at burner inlet at maximum input
- Airflow Direction
- Process air must flow parallel to burner flame (no cross‑flow)
Dimensions & Length Specifications
- Standard Burner Length
- Longer lengths as engineered orders; Up to 9 ft (2700 mm) standard
Control, Logic & Functional Behavior
- Ratio Control Device
- Eclipse‑supplied ratio regulator required
Combustion Design & Characteristics
- Combustion Method
- High‑excess‑air pre‑mix combustion with internal flame recirculation
Installation & Mounting Specifications
- Mounting Options
- Mounting plate for installation into process air duct (insulated or non‑insulated)
Actuation, Valve & Motion Control Specifications
- Control Actuator
- Control actuator modulates air butterfly valve
Ignition, Flame & Supervision Specifications
- Flame Detection
- UV Scanner only (no flame rod option)
- Ignition Type
- Direct Spark Ignition
Performance, Flow & Capacity
- Turndown Ratio
- 10:1 or 8:1 turndown configurations
Product Configuration & Options
- Number of Rows
- Up to 4 burner rows in a single duct
Performance Specifications
- Input Capacity
- 90 to 2700 kBtu/h per module (26 to 791 kW per 300 mm)
Product Design & Configuration
- Burner Design
- Pre‑mix line burner for direct air heating
- Burner Style
- Available in straight sections, double T geometries, and cross sections.
Applications & Compatibility
- Applications
- Applications requiring maximum linear heat distribution with ultra‑low emissions
Fuel, Gas & Media Specifications
- Fuel Type
- Natural Gas (alternative fuels require Eclipse consultation)
Processing & Performance Metrics
- Emissions
- Designed for ultra‑low NOx and CO across the turndown range
Material Specifications
- Material
- Stainless steel housing; for sizes above AB600L, standard steel plate (consult Eclipse for >500°F upstream temperatures).
| Parameter | Published value / configuration |
|---|---|
| Models | Straight ULE and Tee ULE |
| Control Motor Specifications | Rotation ≤2 rpm (≈30 s/90 deg typical); ≥25 in-lb (2.8 Nm) torque; 90 deg stroke; continuous or high/low modulating; reversible. |
| Air Pressure Requirement | 20 in wc (50 mbar) at burner inlet at maximum input |
| Airflow Direction | Process air must flow parallel to burner flame (no cross‑flow) |
| Standard Burner Length | Longer lengths as engineered orders; Up to 9 ft (2700 mm) standard |
| Ratio Control Device | Eclipse‑supplied ratio regulator required |
| Combustion Method | High‑excess‑air pre‑mix combustion with internal flame recirculation |
| Mounting Options | Mounting plate for installation into process air duct (insulated or non‑insulated) |
| Control Actuator | Control actuator modulates air butterfly valve |
| Flame Detection | UV Scanner only (no flame rod option) |
| Ignition Type | Direct Spark Ignition |
| Turndown Ratio | 10:1 or 8:1 turndown configurations |
| Number of Rows | Up to 4 burner rows in a single duct |
| Input Capacity | 90 to 2700 kBtu/h per module (26 to 791 kW per 300 mm) |
| Burner Design | Pre‑mix line burner for direct air heating |
| Burner Style | Available in straight sections, double T geometries, and cross sections. |
| Applications | Applications requiring maximum linear heat distribution with ultra‑low emissions |
| Fuel Type | Natural Gas (alternative fuels require Eclipse consultation) |
| Emissions | Designed for ultra‑low NOx and CO across the turndown range |
| Material | Stainless steel housing; for sizes above AB600L, standard steel plate (consult Eclipse for >500°F upstream temperatures). |
Values retain manufacturer model qualifications. Review Honeywell specifications ↗
Part Number
Published part numbers
10 parts
| Part Number | Description | Enquiry |
|---|---|---|
| 00.4017101.01 | STRP,ELMNT,BRNR,LX | Request quotation |
| 00.4017101.02 | STRP,ELMNT,BRNR,LX,24KW 120KW | Request quotation |
| 00.4017102.01 | PLT,SHLD,FLM,LX,FOLDED 145MM,2BFINISH | Request quotation |
| 00.4017105.07 | GSKT,ELMNT,BRNR,LX,26KW THRU 158KW | Request quotation |
| 00.4017119.00 | PLT,END,SHLD,FLM,LX,26KW 158KW NO HOLES | Request quotation |
| 00.4017119.04 | PLT,INLT,SHLD,FLM,LX, | Request quotation |
| 00.4017121.07 | INGITOR ROD ASSEMBLY LINNOX NEW DESIGN | Request quotation |
| 00.4017121.10 | ROD,IGN,CCS LS | Request quotation |
| 00.4017121.11 | Linnox flame sensor ionization | Request quotation |
| 00.4017121.13 | PLUG,SPRK,IGN,CCS LS,MINNOX BRNR,LENG 60 | Request quotation |
Manufacturer sources
Last source check: 2026-11-02
Linnox Product Image · Manufacturer ownership retained; republication licence not independently confirmed
Linnox Product Image 2 · Manufacturer ownership retained; republication licence not independently confirmed
Linnox Product Image 3 · Manufacturer ownership retained; republication licence not independently confirmed
Linnox Product Image 1 · Manufacturer ownership retained; republication licence not independently confirmed
Linnox Product Image 4 · Manufacturer ownership retained; republication licence not independently confirmed
Linnox Product Image 5 · Site owner attests manufacturer permission; licence not independently audited
Linnox Product Image 6 · Site owner attests manufacturer permission; licence not independently audited
ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.
Your next project. A clear starting point.
Tell us about your facility and what you need to achieve.