Fire & Life Safety · Building Systems · Industrial Automation [email protected] +880 1347 561 256
Honeywell Process Measurement & Control

Line & Duct Burners

Linnox

Linnox ULE combines excess-air premixing with an internal recirculating flame to limit combustion temperature and emissions.

Linnox ULE combines excess-air premixing with an internal recirculating flame to limit combustion temperature and emissions. Modular geometry distributes heat in direct or indirect air-heating duties. Ratio-regulator control and 10:1 turndown support operation, while Linnox Tee arrangements add rows for higher input; emission values retain their published oxygen reference.

Features & Benefits

Control Motor Specifications
Rotation ≤2 rpm (≈30 s/90 deg typical); ≥25 in-lb (2.8 Nm) torque; 90 deg stroke; continuous or high/low modulating; reversible.
Air Pressure Requirement
20 in wc (50 mbar) at burner inlet at maximum input
Standard Burner Length
Longer lengths as engineered orders|Up to 9 ft (2700 mm) standard
Ratio Control Device
Eclipse‑supplied ratio regulator required
Combustion Method
High‑excess‑air pre‑mix combustion with internal flame recirculation
Airflow Direction
Process air must flow parallel to burner flame (no cross‑flow)
Mounting Options
Mounting plate for installation into process air duct (insulated or non‑insulated)
Control Actuator
Control actuator modulates air butterfly valve
Flame Detection
UV Scanner only (no flame rod option)
Turndown Ratio
10:1 or 8:1 turndown configurations
Number of Rows
Up to 4 burner rows in a single duct
Input Capacity
90 to 2700 kBtu/h per module (26 to 791 kW per 300 mm)
Ignition Type
Direct Spark Ignition
Burner Design
Pre‑mix line burner for direct air heating
Burner Style
Available in straight sections, double T geometries, and cross sections.
Fuel Type
Natural Gas (alternative fuels require Eclipse consultation)
Emissions
Designed for ultra‑low NOx and CO across the turndown range
Material
Stainless steel housing; for sizes above AB600L, standard steel plate (consult Eclipse for >500°F upstream temperatures).
  • Premixing and recirculation lower flame temperature and NOx.

Applications

  • Direct and indirect air heating

Detailed capabilities

Why Linnox uses excess air and recirculation

Linnox ULE first premixes fuel with excess air to limit flame temperature, then uses the burner geometry to recirculate the flame internally. This combination addresses stable low-emission operation rather than relying on high flame temperature. A ratio regulator controls the gas/air relationship. The page reports both nominal-input and oxygen-corrected emissions figures; those reference conditions should accompany the numbers wherever reproduced.

Manufacturer reference ↗

Module rows and system sizing

The burner serves direct or indirect air heating where temperature distribution and emissions matter. Input per unit length can be configured around the required layout, with Linnox Tee adding multiple module rows for inputs up to the stated 45 million Btu/hr. Honeywell describes custom-engineered systems, so the full input, layout and control arrangement are established for the installation rather than selected from one common burner package.

Manufacturer reference ↗

Features and benefits

  • Premixing and recirculation lower flame temperature and NOx.

Manufacturer reference ↗

Published application context

  • Direct and indirect air heating

Manufacturer reference ↗

Specifications

Overview

Models
Straight ULE and Tee ULE

Motor Specifications

Control Motor Specifications
Rotation ≤2 rpm (≈30 s/90 deg typical); ≥25 in-lb (2.8 Nm) torque; 90 deg stroke; continuous or high/low modulating; reversible.

Air & Combustion Air Specifications

Air Pressure Requirement
20 in wc (50 mbar) at burner inlet at maximum input
Airflow Direction
Process air must flow parallel to burner flame (no cross‑flow)

Dimensions & Length Specifications

Standard Burner Length
Longer lengths as engineered orders; Up to 9 ft (2700 mm) standard

Control, Logic & Functional Behavior

Ratio Control Device
Eclipse‑supplied ratio regulator required

Combustion Design & Characteristics

Combustion Method
High‑excess‑air pre‑mix combustion with internal flame recirculation

Installation & Mounting Specifications

Mounting Options
Mounting plate for installation into process air duct (insulated or non‑insulated)

Actuation, Valve & Motion Control Specifications

Control Actuator
Control actuator modulates air butterfly valve

Ignition, Flame & Supervision Specifications

Flame Detection
UV Scanner only (no flame rod option)
Ignition Type
Direct Spark Ignition

Performance, Flow & Capacity

Turndown Ratio
10:1 or 8:1 turndown configurations

Product Configuration & Options

Number of Rows
Up to 4 burner rows in a single duct

Performance Specifications

Input Capacity
90 to 2700 kBtu/h per module (26 to 791 kW per 300 mm)

Product Design & Configuration

Burner Design
Pre‑mix line burner for direct air heating
Burner Style
Available in straight sections, double T geometries, and cross sections.

Applications & Compatibility

Applications
Applications requiring maximum linear heat distribution with ultra‑low emissions

Fuel, Gas & Media Specifications

Fuel Type
Natural Gas (alternative fuels require Eclipse consultation)

Processing & Performance Metrics

Emissions
Designed for ultra‑low NOx and CO across the turndown range

Material Specifications

Material
Stainless steel housing; for sizes above AB600L, standard steel plate (consult Eclipse for >500°F upstream temperatures).
Linnox — manufacturer page values
ParameterPublished value / configuration
ModelsStraight ULE and Tee ULE
Control Motor SpecificationsRotation ≤2 rpm (≈30 s/90 deg typical); ≥25 in-lb (2.8 Nm) torque; 90 deg stroke; continuous or high/low modulating; reversible.
Air Pressure Requirement20 in wc (50 mbar) at burner inlet at maximum input
Airflow DirectionProcess air must flow parallel to burner flame (no cross‑flow)
Standard Burner LengthLonger lengths as engineered orders; Up to 9 ft (2700 mm) standard
Ratio Control DeviceEclipse‑supplied ratio regulator required
Combustion MethodHigh‑excess‑air pre‑mix combustion with internal flame recirculation
Mounting OptionsMounting plate for installation into process air duct (insulated or non‑insulated)
Control ActuatorControl actuator modulates air butterfly valve
Flame DetectionUV Scanner only (no flame rod option)
Ignition TypeDirect Spark Ignition
Turndown Ratio10:1 or 8:1 turndown configurations
Number of RowsUp to 4 burner rows in a single duct
Input Capacity90 to 2700 kBtu/h per module (26 to 791 kW per 300 mm)
Burner DesignPre‑mix line burner for direct air heating
Burner StyleAvailable in straight sections, double T geometries, and cross sections.
ApplicationsApplications requiring maximum linear heat distribution with ultra‑low emissions
Fuel TypeNatural Gas (alternative fuels require Eclipse consultation)
EmissionsDesigned for ultra‑low NOx and CO across the turndown range
MaterialStainless steel housing; for sizes above AB600L, standard steel plate (consult Eclipse for >500°F upstream temperatures).

Values retain manufacturer model qualifications. Review Honeywell specifications ↗

Part Number

Published part numbers

10 parts

Part NumberDescriptionEnquiry
00.4017101.01STRP,ELMNT,BRNR,LXRequest quotation
00.4017101.02STRP,ELMNT,BRNR,LX,24KW 120KWRequest quotation
00.4017102.01PLT,SHLD,FLM,LX,FOLDED 145MM,2BFINISHRequest quotation
00.4017105.07GSKT,ELMNT,BRNR,LX,26KW THRU 158KWRequest quotation
00.4017119.00PLT,END,SHLD,FLM,LX,26KW 158KW NO HOLESRequest quotation
00.4017119.04PLT,INLT,SHLD,FLM,LX,Request quotation
00.4017121.07INGITOR ROD ASSEMBLY LINNOX NEW DESIGNRequest quotation
00.4017121.10ROD,IGN,CCS LSRequest quotation
00.4017121.11Linnox flame sensor ionizationRequest quotation
00.4017121.13PLUG,SPRK,IGN,CCS LS,MINNOX BRNR,LENG 60Request quotation
Manufacturer sources

https://process.honeywell.com/us/en/products/thermal-solutions/burners-and-heat-exchangers/line-and-duct-burners/linnox

Last source check: 2026-11-02

Linnox Product Image · Manufacturer ownership retained; republication licence not independently confirmed

Linnox Product Image 2 · Manufacturer ownership retained; republication licence not independently confirmed

Linnox Product Image 3 · Manufacturer ownership retained; republication licence not independently confirmed

Linnox Product Image 1 · Manufacturer ownership retained; republication licence not independently confirmed

Linnox Product Image 4 · Manufacturer ownership retained; republication licence not independently confirmed

Linnox Product Image 5 · Site owner attests manufacturer permission; licence not independently audited

Linnox Product Image 6 · Site owner attests manufacturer permission; licence not independently audited

ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.

Your next project. A clear starting point.

Tell us about your facility and what you need to achieve.

CallSend enquiry