Line & Duct Burners
FlueFire
FlueFire provides supplemental firing between a turbine and waste-heat boiler, using oxygen already present in the exhaust stream.
FlueFire provides supplemental firing between a turbine and waste-heat boiler, using oxygen already present in the exhaust stream. It also supports the published fresh-air and incineration duties. Swirling flow stabilizes the flame near the burner, with the stated inlet and outlet temperature limits defining the process envelope.
Features & Benefits
- Process Air Distribution
- ±15% velocity uniformity across the burner required
- Nozzle Gas Pressure
- NG: 169 in wc (421 mbar); Propane: 74 in wc (184 mbar); Butane: 56 in wc (140 mbar)
- Module Construction
- Each 150 mm module has a perforated stabilization plate producing local swirl; two gas nozzles + one raw gas port
- Temperature Rating
- Downstream: up to 1800 deg F (982 deg C) with 21% O₂ (typical)|Upstream: up to 1300 deg F (700 deg C)
- Oxygen Requirement
- Operational envelope ~11–21% O₂ in process stream; below this, provide external combustion air
- Frame Construction
- Heavy steel mounting frame with internal insulation (≈8 in ceramic fiber) and heat‑resistant cladding; sliding end for thermal expansion
- Process Velocity
- FA: 2100 to 2800 ft/min (10 to 14 m/s)|TEG: 3800 to 5000 ft/min (19 to 25 m/s)
- Minimum Capacity
- 55-95 x 1000 Btu/h (15-25 kW) per 150 mm module (depends on O₂%)
- Flame Monitoring
- UV Scanner only
- CO/NOx Emissions
- Emissions depend on process temperature and O₂ level (consult Eclipse)
- Row/Propagation
- Modules mounted on common manifold to form rows; optional flame propagation plates for cross‑ignition between rows
- Capacity Range
- Up to 1300 x 1000 Btu/h (344 kW) per 150 mm module at 21% O₂
- Pressure Drop
- 0.3 to 0.5 in wc (75 to 125 Pa)
- Ignition Type
- Pilot with ignition plug and flame extension tube; UV proves pilot and main flame; pilot interrupted after light‑off
- Burner Design
- Modular supplementary firing burner
- Functions
- Supplementary firing of turbine exhaust gases (TEG) using residual O₂; also applicable to fresh air (FA) heating with high outlet temperatures
- Fuel Type
- Natural Gas, Propane, Butane; low‑calorific gases per specification
- Using turbine-exhaust oxygen supports system efficiency.
Applications
- Cogeneration and combined-cycle supplemental firing
- Fresh-air operation
- Incineration
Detailed capabilities
Supplementary firing using turbine-exhaust oxygen
FlueFire sits between the turbine and waste-heat boiler, mixing fuel with oxygen still present in the exhaust. A swirl pattern stabilizes combustion close to the burner. The stated inlet and outlet temperatures define different locations in the heating path and should not be merged into one material rating. Fresh-air operation and incineration are additional described arrangements, not assumptions about every turbine-exhaust installation.
Features and benefits
- Using turbine-exhaust oxygen supports system efficiency.
Published application context
- Cogeneration and combined-cycle supplemental firing
- Fresh-air operation
- Incineration
Air & Combustion Air Specifications
- Process Air Distribution
- ±15% velocity uniformity across the burner required
Pressure Specifications
- Nozzle Gas Pressure
- NG: 169 in wc (421 mbar); Propane: 74 in wc (184 mbar); Butane: 56 in wc (140 mbar)
- Pressure Drop
- 0.3 to 0.5 in wc (75 to 125 Pa)
Processing & Performance Metrics
- Module Construction
- Each 150 mm module has a perforated stabilization plate producing local swirl; two gas nozzles + one raw gas port
- Frame Construction
- Heavy steel mounting frame with internal insulation (≈8 in ceramic fiber) and heat‑resistant cladding; sliding end for thermal expansion
- Process Velocity
- FA: 2100 to 2800 ft/min (10 to 14 m/s); TEG: 3800 to 5000 ft/min (19 to 25 m/s)
- Minimum Capacity
- 55-95 x 1000 Btu/h (15-25 kW) per 150 mm module (depends on O₂%)
- CO/NOx Emissions
- Emissions depend on process temperature and O₂ level (consult Eclipse)
- Capacity Range
- Up to 1300 x 1000 Btu/h (344 kW) per 150 mm module at 21% O₂
Temperature Control/Measurement
- Temperature Rating
- Downstream: up to 1800 deg F (982 deg C) with 21% O₂ (typical); Upstream: up to 1300 deg F (700 deg C)
Combustion, Mixing & Fuel Dynamics
- Oxygen Requirement
- Operational envelope ~11–21% O₂ in process stream; below this, provide external combustion air
Ignition, Flame & Supervision Specifications
- Flame Monitoring
- UV Scanner only
- Ignition Type
- Pilot with ignition plug and flame extension tube; UV proves pilot and main flame; pilot interrupted after light‑off
Control, Safety & Timing Characteristics
- Row/Propagation
- Modules mounted on common manifold to form rows; optional flame propagation plates for cross‑ignition between rows
Product Design & Configuration
- Burner Design
- Modular supplementary firing burner
Applications & Compatibility
- Applications
- Fresh air heating; High‑temperature process heating; Turbine exhaust/waste heat boiler firing
Control, Logic & Functional Behavior
- Functions
- Supplementary firing of turbine exhaust gases (TEG) using residual O₂; also applicable to fresh air (FA) heating with high outlet temperatures
Fuel, Gas & Media Specifications
- Fuel Type
- Natural Gas, Propane, Butane; low‑calorific gases per specification
| Parameter | Published value / configuration |
|---|---|
| Process Air Distribution | ±15% velocity uniformity across the burner required |
| Nozzle Gas Pressure | NG: 169 in wc (421 mbar); Propane: 74 in wc (184 mbar); Butane: 56 in wc (140 mbar) |
| Pressure Drop | 0.3 to 0.5 in wc (75 to 125 Pa) |
| Module Construction | Each 150 mm module has a perforated stabilization plate producing local swirl; two gas nozzles + one raw gas port |
| Frame Construction | Heavy steel mounting frame with internal insulation (≈8 in ceramic fiber) and heat‑resistant cladding; sliding end for thermal expansion |
| Process Velocity | FA: 2100 to 2800 ft/min (10 to 14 m/s); TEG: 3800 to 5000 ft/min (19 to 25 m/s) |
| Minimum Capacity | 55-95 x 1000 Btu/h (15-25 kW) per 150 mm module (depends on O₂%) |
| CO/NOx Emissions | Emissions depend on process temperature and O₂ level (consult Eclipse) |
| Capacity Range | Up to 1300 x 1000 Btu/h (344 kW) per 150 mm module at 21% O₂ |
| Temperature Rating | Downstream: up to 1800 deg F (982 deg C) with 21% O₂ (typical); Upstream: up to 1300 deg F (700 deg C) |
| Oxygen Requirement | Operational envelope ~11–21% O₂ in process stream; below this, provide external combustion air |
| Flame Monitoring | UV Scanner only |
| Ignition Type | Pilot with ignition plug and flame extension tube; UV proves pilot and main flame; pilot interrupted after light‑off |
| Row/Propagation | Modules mounted on common manifold to form rows; optional flame propagation plates for cross‑ignition between rows |
| Burner Design | Modular supplementary firing burner |
| Applications | Fresh air heating; High‑temperature process heating; Turbine exhaust/waste heat boiler firing |
| Functions | Supplementary firing of turbine exhaust gases (TEG) using residual O₂; also applicable to fresh air (FA) heating with high outlet temperatures |
| Fuel Type | Natural Gas, Propane, Butane; low‑calorific gases per specification |
Values retain manufacturer model qualifications. Review Honeywell specifications ↗
Part Number
Published part numbers
10 parts
| Part Number | Description | Enquiry |
|---|---|---|
| 00.4121028.01 | NZL,GAS,FFB,LOS,FLUE FIRE BRNR | Request quotation |
| 00.4121028.25 | NZL,GAS,INCINISTAR,STD,D3,7 11X | Request quotation |
| 00.4121029.01 | PLT,GUIDING END,FLUE FIRE BRNR | Request quotation |
| 00.4121051.02 | BRNR,SECT,INCINISTAR IS 5,MIDDLE | Request quotation |
| 00.4121051.03 | BRNR,SECT,INCINISTAR IS 5,END | Request quotation |
| 00.4121051.05 | BRNR,SECT,INCINISTAR IS 5,INLT NEAR IGN | Request quotation |
| 00.4121147.00 | ROD,IGN,ASY, IS 5 BRNR 00.4121053.07,L1 | Request quotation |
| 00.4121147.02 | ROD,IGN,ASY ECLIPSE BV 00.4121147.02,L1 | Request quotation |
| 00.4121147.03 | ROD,IGN,ASY,ECLIPSE BV 00.4121147.03, BR | Request quotation |
| 00.4121147.04 | ROD,IGN,ASY 05 IS ECLIPSE BV NO. 00.4121 | Request quotation |
Manufacturer sources
Last source check: 2026-11-02
FlueFire Product Image · Manufacturer ownership retained; republication licence not independently confirmed
FlueFire Product Image 1 · Manufacturer ownership retained; republication licence not independently confirmed
FlueFire Product Image 4 · Manufacturer ownership retained; republication licence not independently confirmed
FlueFire Product Image 3 · Manufacturer ownership retained; republication licence not independently confirmed
FlueFire Product Image 2 · Manufacturer ownership retained; republication licence not independently confirmed
ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.
Your next project. A clear starting point.
Tell us about your facility and what you need to achieve.