Fire & Life Safety · Building Systems · Industrial Automation [email protected] +880 1347 561 256
Honeywell Process Measurement & Control

Line & Duct Burners

FlueFire

FlueFire provides supplemental firing between a turbine and waste-heat boiler, using oxygen already present in the exhaust stream.

FlueFire provides supplemental firing between a turbine and waste-heat boiler, using oxygen already present in the exhaust stream. It also supports the published fresh-air and incineration duties. Swirling flow stabilizes the flame near the burner, with the stated inlet and outlet temperature limits defining the process envelope.

Features & Benefits

Process Air Distribution
±15% velocity uniformity across the burner required
Nozzle Gas Pressure
NG: 169 in wc (421 mbar); Propane: 74 in wc (184 mbar); Butane: 56 in wc (140 mbar)
Module Construction
Each 150 mm module has a perforated stabilization plate producing local swirl; two gas nozzles + one raw gas port
Temperature Rating
Downstream: up to 1800 deg F (982 deg C) with 21% O₂ (typical)|Upstream: up to 1300 deg F (700 deg C)
Oxygen Requirement
Operational envelope ~11–21% O₂ in process stream; below this, provide external combustion air
Frame Construction
Heavy steel mounting frame with internal insulation (≈8 in ceramic fiber) and heat‑resistant cladding; sliding end for thermal expansion
Process Velocity
FA: 2100 to 2800 ft/min (10 to 14 m/s)|TEG: 3800 to 5000 ft/min (19 to 25 m/s)
Minimum Capacity
55-95 x 1000 Btu/h (15-25 kW) per 150 mm module (depends on O₂%)
Flame Monitoring
UV Scanner only
CO/NOx Emissions
Emissions depend on process temperature and O₂ level (consult Eclipse)
Row/Propagation
Modules mounted on common manifold to form rows; optional flame propagation plates for cross‑ignition between rows
Capacity Range
Up to 1300 x 1000 Btu/h (344 kW) per 150 mm module at 21% O₂
Pressure Drop
0.3 to 0.5 in wc (75 to 125 Pa)
Ignition Type
Pilot with ignition plug and flame extension tube; UV proves pilot and main flame; pilot interrupted after light‑off
Burner Design
Modular supplementary firing burner
Functions
Supplementary firing of turbine exhaust gases (TEG) using residual O₂; also applicable to fresh air (FA) heating with high outlet temperatures
Fuel Type
Natural Gas, Propane, Butane; low‑calorific gases per specification
  • Using turbine-exhaust oxygen supports system efficiency.

Applications

  • Cogeneration and combined-cycle supplemental firing
  • Fresh-air operation
  • Incineration

Detailed capabilities

Supplementary firing using turbine-exhaust oxygen

FlueFire sits between the turbine and waste-heat boiler, mixing fuel with oxygen still present in the exhaust. A swirl pattern stabilizes combustion close to the burner. The stated inlet and outlet temperatures define different locations in the heating path and should not be merged into one material rating. Fresh-air operation and incineration are additional described arrangements, not assumptions about every turbine-exhaust installation.

Manufacturer reference ↗

Features and benefits

  • Using turbine-exhaust oxygen supports system efficiency.

Manufacturer reference ↗

Published application context

  • Cogeneration and combined-cycle supplemental firing
  • Fresh-air operation
  • Incineration

Manufacturer reference ↗

Specifications

Air & Combustion Air Specifications

Process Air Distribution
±15% velocity uniformity across the burner required

Pressure Specifications

Nozzle Gas Pressure
NG: 169 in wc (421 mbar); Propane: 74 in wc (184 mbar); Butane: 56 in wc (140 mbar)
Pressure Drop
0.3 to 0.5 in wc (75 to 125 Pa)

Processing & Performance Metrics

Module Construction
Each 150 mm module has a perforated stabilization plate producing local swirl; two gas nozzles + one raw gas port
Frame Construction
Heavy steel mounting frame with internal insulation (≈8 in ceramic fiber) and heat‑resistant cladding; sliding end for thermal expansion
Process Velocity
FA: 2100 to 2800 ft/min (10 to 14 m/s); TEG: 3800 to 5000 ft/min (19 to 25 m/s)
Minimum Capacity
55-95 x 1000 Btu/h (15-25 kW) per 150 mm module (depends on O₂%)
CO/NOx Emissions
Emissions depend on process temperature and O₂ level (consult Eclipse)
Capacity Range
Up to 1300 x 1000 Btu/h (344 kW) per 150 mm module at 21% O₂

Temperature Control/Measurement

Temperature Rating
Downstream: up to 1800 deg F (982 deg C) with 21% O₂ (typical); Upstream: up to 1300 deg F (700 deg C)

Combustion, Mixing & Fuel Dynamics

Oxygen Requirement
Operational envelope ~11–21% O₂ in process stream; below this, provide external combustion air

Ignition, Flame & Supervision Specifications

Flame Monitoring
UV Scanner only
Ignition Type
Pilot with ignition plug and flame extension tube; UV proves pilot and main flame; pilot interrupted after light‑off

Control, Safety & Timing Characteristics

Row/Propagation
Modules mounted on common manifold to form rows; optional flame propagation plates for cross‑ignition between rows

Product Design & Configuration

Burner Design
Modular supplementary firing burner

Applications & Compatibility

Applications
Fresh air heating; High‑temperature process heating; Turbine exhaust/waste heat boiler firing

Control, Logic & Functional Behavior

Functions
Supplementary firing of turbine exhaust gases (TEG) using residual O₂; also applicable to fresh air (FA) heating with high outlet temperatures

Fuel, Gas & Media Specifications

Fuel Type
Natural Gas, Propane, Butane; low‑calorific gases per specification
FlueFire — manufacturer page values
ParameterPublished value / configuration
Process Air Distribution±15% velocity uniformity across the burner required
Nozzle Gas PressureNG: 169 in wc (421 mbar); Propane: 74 in wc (184 mbar); Butane: 56 in wc (140 mbar)
Pressure Drop0.3 to 0.5 in wc (75 to 125 Pa)
Module ConstructionEach 150 mm module has a perforated stabilization plate producing local swirl; two gas nozzles + one raw gas port
Frame ConstructionHeavy steel mounting frame with internal insulation (≈8 in ceramic fiber) and heat‑resistant cladding; sliding end for thermal expansion
Process VelocityFA: 2100 to 2800 ft/min (10 to 14 m/s); TEG: 3800 to 5000 ft/min (19 to 25 m/s)
Minimum Capacity55-95 x 1000 Btu/h (15-25 kW) per 150 mm module (depends on O₂%)
CO/NOx EmissionsEmissions depend on process temperature and O₂ level (consult Eclipse)
Capacity RangeUp to 1300 x 1000 Btu/h (344 kW) per 150 mm module at 21% O₂
Temperature RatingDownstream: up to 1800 deg F (982 deg C) with 21% O₂ (typical); Upstream: up to 1300 deg F (700 deg C)
Oxygen RequirementOperational envelope ~11–21% O₂ in process stream; below this, provide external combustion air
Flame MonitoringUV Scanner only
Ignition TypePilot with ignition plug and flame extension tube; UV proves pilot and main flame; pilot interrupted after light‑off
Row/PropagationModules mounted on common manifold to form rows; optional flame propagation plates for cross‑ignition between rows
Burner DesignModular supplementary firing burner
ApplicationsFresh air heating; High‑temperature process heating; Turbine exhaust/waste heat boiler firing
FunctionsSupplementary firing of turbine exhaust gases (TEG) using residual O₂; also applicable to fresh air (FA) heating with high outlet temperatures
Fuel TypeNatural Gas, Propane, Butane; low‑calorific gases per specification

Values retain manufacturer model qualifications. Review Honeywell specifications ↗

Part Number

Published part numbers

10 parts

Part NumberDescriptionEnquiry
00.4121028.01NZL,GAS,FFB,LOS,FLUE FIRE BRNRRequest quotation
00.4121028.25NZL,GAS,INCINISTAR,STD,D3,7 11XRequest quotation
00.4121029.01PLT,GUIDING END,FLUE FIRE BRNRRequest quotation
00.4121051.02BRNR,SECT,INCINISTAR IS 5,MIDDLERequest quotation
00.4121051.03BRNR,SECT,INCINISTAR IS 5,ENDRequest quotation
00.4121051.05BRNR,SECT,INCINISTAR IS 5,INLT NEAR IGNRequest quotation
00.4121147.00ROD,IGN,ASY, IS 5 BRNR 00.4121053.07,L1Request quotation
00.4121147.02ROD,IGN,ASY ECLIPSE BV 00.4121147.02,L1Request quotation
00.4121147.03ROD,IGN,ASY,ECLIPSE BV 00.4121147.03, BRRequest quotation
00.4121147.04ROD,IGN,ASY 05 IS ECLIPSE BV NO. 00.4121Request quotation
Manufacturer sources

https://process.honeywell.com/us/en/products/thermal-solutions/burners-and-heat-exchangers/line-and-duct-burners/fluefire

Last source check: 2026-11-02

FlueFire Product Image · Manufacturer ownership retained; republication licence not independently confirmed

FlueFire Product Image 1 · Manufacturer ownership retained; republication licence not independently confirmed

FlueFire Product Image 4 · Manufacturer ownership retained; republication licence not independently confirmed

FlueFire Product Image 3 · Manufacturer ownership retained; republication licence not independently confirmed

FlueFire Product Image 2 · Manufacturer ownership retained; republication licence not independently confirmed

ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.

Your next project. A clear starting point.

Tell us about your facility and what you need to achieve.

CallSend enquiry