Shutoff Valves
V5097 Integrated gas valve train
V5097 integrates gas-valve functions in small or large bodies using separately selected pipe adapters.
V5097 integrates gas-valve functions in small or large bodies using separately selected pipe adapters. Actuator combinations provide on/off, high/low/off or modulating behavior, with double-seal proof-of-closure on specified versions. A stem-mounted shut indicator and test taps support operation; temperature and approval qualifications depend on the chosen actuator pairing.
Features & Benefits
- Gas Type
- Natural Gas and Liquefied Petroleum (LP) Gas
- Ambient Temperature Range
- -40 to +150 deg F (-40 to +66 deg C), depending on actuator selection
- Electrical Connections
- Line‑voltage fluid‑power actuators available in 100 to 240 Vac, 50/60 Hz ranges (Actuator)
- Valve Body Material
- Die‑Cast Aluminum
- Pressure Ratings
- Standard‑pressure and high‑pressure ratings depending on valve/actuator combination
- Mounting Options
- Valve and actuator mount directly together, multi‑position mounting allowed
- Valve Operation
- Normally closed; valve opens when actuator is energized and closes on power loss
- Valve Variants
- V5097A: On‑off service|V5097B: Characterized guide for Hi‑Lo or modulating control|V5097C: On‑off with valve seal overtravel interlock capability|V5097D/E: High‑pressure versions (E supports interlock)
- Valve Series
- V5097 Industrial Gas Valves (A, B, C, D, E variants)
- Valve Design
- Single‑seated, straight‑through industrial gas valve
- Product Type
- Integrated industrial gas valve train consisting of a V5097 industrial gas valve combined with a fluid‑power actuator
- Closing Time
- ≤1 second, meeting safety and approval requirements
- Valve Sizes
- 3/4 to 3 in (small‑body and large‑body designs depending on size)
- Approvals
- UL Listed, FM Approved, CSA Certified; additional international approvals model‑dependent
- Operating Temperature Range
- -40°F to +150°F; When used with V9055 – -40°F to +125°F (-40°C to +66°C; When used with V9055 – -40°C to +52°C)
- Approvals, Underwriters Laboratories Inc.
- When used with V4055A, B, D, E, V4062: Listed, File No. MH1639 Guide No. YIOZ
- Approvals, CSA
- When used with V4055, V4062, and V5097: Certified, General listed File No. 158158, Class 3371 for USA and Canada
- Approvals, Swiss RE
- When used with the V4055A, G: Approved, Report Nos. 20698, 20835, 21172, and 24061
- Approvals, CE
- CE #E3070 (Gastec)
- Includes
- Three 1/4 in. -18 NPT upstream and two 1/4 in. -18 NPT downstream taps
- Used With
- V4055; V4062
- Adapter choices fit several pipe sizes using two body groups.
Applications
- Commercial and industrial burner gas shutoff
Detailed capabilities
Two bodies and separately selected pipe adapters
V5097 uses small and large bodies with several NPT/BSP adapter sizes rather than a unique body casting for every pipe size. Upstream and downstream test taps permit checking, with an additional downstream tap on the CE version. A yellow stem indicator shows the closed position. Selecting the correct adapter remains part of configuring the integrated train.
Actuator pairing determines the operating mode
A/C valves support on/off service, while B uses a characterized guide with the specified actuators for slow-opening, high/low/off or modulating functions. C with the stated D/E actuator arrangement provides double sealing and proof-of-closure. The normal temperature limit changes when V9055 is used, so that reduced limit must remain attached to that actuator pairing. Approval statements likewise apply to named combinations.
Features and benefits
- Adapter choices fit several pipe sizes using two body groups.
Published application context
- Commercial and industrial burner gas shutoff
Technical facts in the product overview
- Operating Temperature Range: -40°F to +150°F; When used with V9055 – -40°F to +125°F (-40°C to +66°C; When used with V9055 – -40°C to +52°C)
- Approvals, Underwriters Laboratories Inc.: When used with V4055A, B, D, E, V4062: Listed, File No. MH1639 Guide No. YIOZ
- Approvals, CSA: When used with V4055, V4062, and V5097: Certified, General listed File No. 158158, Class 3371 for USA and Canada
- Approvals, Swiss RE: When used with the V4055A, G: Approved, Report Nos. 20698, 20835, 21172, and 24061
- Approvals, CE: CE #E3070 (Gastec)
- Includes: Three 1/4 in. -18 NPT upstream and two 1/4 in. -18 NPT downstream taps
- Used With: V4055; V4062
Fuel, Gas & Media Specifications
- Gas Type
- Natural Gas and Liquefied Petroleum (LP) Gas
Environmental Conditions
- Ambient Temperature Range
- -40 to +150 deg F (-40 to +66 deg C), depending on actuator selection
Connections & Interfaces
- Electrical Connections
- Line‑voltage fluid‑power actuators available in 100 to 240 Vac, 50/60 Hz ranges (Actuator)
Applications & Compatibility
- Typical Applications
- Large industrial and commercial burners requiring tight shut‑off and accurate fuel control
Material Specifications
- Valve Body Material
- Die‑Cast Aluminum
Pressure Specifications
- Pressure Ratings
- Standard‑pressure and high‑pressure ratings depending on valve/actuator combination
Installation & Mounting Specifications
- Mounting Options
- Valve and actuator mount directly together, multi‑position mounting allowed
Actuation, Valve & Motion Control Specifications
- Valve Operation
- Normally closed; valve opens when actuator is energized and closes on power loss
- Valve Variants
- V5097A: On‑off service; V5097B: Characterized guide for Hi‑Lo or modulating control; V5097C: On‑off with valve seal overtravel interlock capability; V5097D/E: High‑pressure versions (E supports interlock)
- Valve Series
- V5097 Industrial Gas Valves (A, B, C, D, E variants)
- Valve Design
- Single‑seated, straight‑through industrial gas valve
- Closing Time
- ≤1 second, meeting safety and approval requirements
Overview
- Product Type
- Integrated industrial gas valve train consisting of a V5097 industrial gas valve combined with a fluid‑power actuator
Dimensions & Size Specifications
- Valve Sizes
- 3/4 to 3 in (small‑body and large‑body designs depending on size)
Standards & Certifications
- Approvals
- UL Listed, FM Approved, CSA Certified; additional international approvals model‑dependent
Technical Specifications
- Operating Temperature Range
- -40°F to +150°F; When used with V9055 – -40°F to +125°F (-40°C to +66°C; When used with V9055 – -40°C to +52°C)
- Approvals, Underwriters Laboratories Inc.
- When used with V4055A, B, D, E, V4062: Listed, File No. MH1639 Guide No. YIOZ
- Approvals, CSA
- When used with V4055, V4062, and V5097: Certified, General listed File No. 158158, Class 3371 for USA and Canada
- Approvals, Swiss RE
- When used with the V4055A, G: Approved, Report Nos. 20698, 20835, 21172, and 24061
- Approvals, CE
- CE #E3070 (Gastec)
- Includes
- Three 1/4 in. -18 NPT upstream and two 1/4 in. -18 NPT downstream taps
- Used With
- V4055; V4062
| Parameter | Published value / configuration |
|---|---|
| Gas Type | Natural Gas and Liquefied Petroleum (LP) Gas |
| Ambient Temperature Range | -40 to +150 deg F (-40 to +66 deg C), depending on actuator selection |
| Electrical Connections | Line‑voltage fluid‑power actuators available in 100 to 240 Vac, 50/60 Hz ranges (Actuator) |
| Typical Applications | Large industrial and commercial burners requiring tight shut‑off and accurate fuel control |
| Valve Body Material | Die‑Cast Aluminum |
| Pressure Ratings | Standard‑pressure and high‑pressure ratings depending on valve/actuator combination |
| Mounting Options | Valve and actuator mount directly together, multi‑position mounting allowed |
| Valve Operation | Normally closed; valve opens when actuator is energized and closes on power loss |
| Valve Variants | V5097A: On‑off service; V5097B: Characterized guide for Hi‑Lo or modulating control; V5097C: On‑off with valve seal overtravel interlock capability; V5097D/E: High‑pressure versions (E supports interlock) |
| Valve Series | V5097 Industrial Gas Valves (A, B, C, D, E variants) |
| Valve Design | Single‑seated, straight‑through industrial gas valve |
| Closing Time | ≤1 second, meeting safety and approval requirements |
| Product Type | Integrated industrial gas valve train consisting of a V5097 industrial gas valve combined with a fluid‑power actuator |
| Valve Sizes | 3/4 to 3 in (small‑body and large‑body designs depending on size) |
| Approvals | UL Listed, FM Approved, CSA Certified; additional international approvals model‑dependent |
| Operating Temperature Range | -40°F to +150°F; When used with V9055 – -40°F to +125°F (-40°C to +66°C; When used with V9055 – -40°C to +52°C) |
| Approvals, Underwriters Laboratories Inc. | When used with V4055A, B, D, E, V4062: Listed, File No. MH1639 Guide No. YIOZ |
| Approvals, CSA | When used with V4055, V4062, and V5097: Certified, General listed File No. 158158, Class 3371 for USA and Canada |
| Approvals, Swiss RE | When used with the V4055A, G: Approved, Report Nos. 20698, 20835, 21172, and 24061 |
| Approvals, CE | CE #E3070 (Gastec) |
| Includes | Three 1/4 in. -18 NPT upstream and two 1/4 in. -18 NPT downstream taps |
| Used With | V4055; V4062 |
Values retain manufacturer model qualifications. Review Honeywell specifications ↗
Part Number
Published part numbers
10 parts
| Part Number | Description | Enquiry |
|---|---|---|
| 133417CA/U | BONNETASSEMBLYFOR3"V5055/V5097. | Request quotation |
| 32000109-001/U | 3/4"NPT.USEW/V5097,SMALLBODY.BOD | Request quotation |
| 32000109-002/U | Pipe adapter | Request quotation |
| 32000109-003/U | PIPE ADAPTOR FOR V5197 | Request quotation |
| 32000109-005/U | PIPE ADAPTOR FOR V5197 | Request quotation |
| 32001605-001/U | 2"NPT.USEDW/V5097,LARGEBODY.BODY | Request quotation |
| 32001605-002/U | 2-1/2" NPT USED W/V5097 LARGEBODY | Request quotation |
| 32001605-003/U | 3"NPT.USEDW/V5097LARGEBODY.BODY | Request quotation |
| 4074EYE/U | BAG ASSEMBLY FOR V5097 (LARGE BODY) IN | Request quotation |
| 4074EYK/U | BAG ASSEMBLY FOR V5097 (SMALL BODY) IN | Request quotation |
Manufacturer sources
Last source check: 2026-11-02
V5097 · Manufacturer ownership retained; republication licence not independently confirmed
ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.
Your next project. A clear starting point.
Tell us about your facility and what you need to achieve.