Fire & Life Safety · Building Systems · Industrial Automation [email protected] +880 1347 561 256
Honeywell Process Measurement & Control

Conductivity

DL4000 Conductivity Cells

DL4000 contacting cells work with the DirectLine conductivity module to measure industrial liquids.

DL4000 contacting cells work with the DirectLine conductivity module to measure industrial liquids. Three cell-constant choices use graphite or platinum electrodes within a PES body, and integral temperature compensation supports the measurement. A fixed cable connects to the remote interface, with submersion, in-line or flow-chamber arrangements available for different installation layouts.

Models: DL4000

Features & Benefits

Cell constants
0.1, 1.0 and 10.0
Body material
PES

Applications

  • Light-industrial electrolytic conductivity measurement

Detailed capabilities

What Is It?

DL4000 cells connect to the DL423 DirectLine conductivity module. The stated 0.1 and 1.0 constants use graphite, while 10.0 uses platinum. PES construction supports light-industrial electrolytic conductivity duties, with submersed, inline or flow-chamber mounting choices. This material-to-constant mapping is specific and should not be replaced with the titanium mapping of 4973/CCD.

Manufacturer reference ↗

How Does It Work?

An integral temperature compensator accompanies the conductivity electrodes. A fixed 20-foot cable connects through a remote connector assembly to the DirectLine module, creating a modular measurement path. The source describes alternative mounts rather than one supplied chamber for every cell, so process fittings and cable/module configuration remain part of the selected installation.

Manufacturer reference ↗

What Problems Does It Solve?

DirectLine packaging reduces the need for a dedicated separate analyzer installation and simplifies startup, operation and maintenance. Users retain a conductivity sensor matched to its module rather than assembling an unrelated signal path. The cost/accuracy benefits are the manufacturer's stated outcomes for that complete arrangement, not evidence of a universal conductivity range for every cell constant.

Manufacturer reference ↗

Specifications

Mechanical & Physical Properties

Compatible Analyzers
DirectLine DL423, UDA2182, APT4000CC, APT4000TC, APT2000CC, APT2000TC

Environmental Conditions

Measurement Range
Suitable for conductivities between 20 and 10,000 μS/cm (EASY), elevated temp/pressure, high purity water (MODERATE), and “dirty” applications (HARSH)

Applications & Compatibility

Applications
Industrial Process Conductivity Measurement (Simple and Complex Processes)
Mounting
In-Line, Flow Chamber, Immersion

Industries / Applications & Compatibility

Industries
Power, Chemical Process, Wastewater, Pure Water and More
DL4000 Conductivity Cells — manufacturer page values
ParameterPublished value / configuration
Compatible AnalyzersDirectLine DL423, UDA2182, APT4000CC, APT4000TC, APT2000CC, APT2000TC
Measurement RangeSuitable for conductivities between 20 and 10,000 μS/cm (EASY), elevated temp/pressure, high purity water (MODERATE), and “dirty” applications (HARSH)
ApplicationsIndustrial Process Conductivity Measurement (Simple and Complex Processes)
MountingIn-Line, Flow Chamber, Immersion
IndustriesPower, Chemical Process, Wastewater, Pure Water and More

Values retain manufacturer model qualifications. Review Honeywell specifications ↗

Resources

Filter documents by type

Resources linked from the manufacturer’s page. Confirm the document revision and applicable model before installation or ordering.

Honeywell resource listing ↗

Part Number

Published model / variant identifiers. A full ordering code requires the manufacturer configuration.

Published part numbers

6 parts

Part NumberDescriptionEnquiry
51452150-5024973 STYLE, 10 CONSTANTRequest quotation
51452152-5014905 STYLE, MONEL, 0.1 CONSTANRequest quotation
51452152-5034905 STYLE, NICKEL, 10 CONSTANRequest quotation
51452152-5044905 STYLE, PLATINUM, 10 CONSTRequest quotation
51452152-5054905 STYLE NICKEL, 50 CONSTANTRequest quotation
51452152-5064905 STYLE, PLATINUM, 50 CONSTRequest quotation
Manufacturer sources

https://process.honeywell.com/us/en/products/process-instruments/analytical-instruments-and-sensors/conductivity/dl4000-conductivity-cells

Last source check: 2026-11-02

DL4000 Conductivity Cells Image · Manufacturer ownership retained; republication licence not independently confirmed

ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.

Your next project. A clear starting point.

Tell us about your facility and what you need to achieve.

CallSend enquiry