Safety Shut-Off Valves
HON 711 - DN 200 thru 300
HON 711 in DN200 through DN300 uses an axial passage to limit pressure loss in large gas lines.
HON 711 in DN200 through DN300 uses an axial passage to limit pressure loss in large gas lines. The shut-off valve offers several release arrangements and is supplied with manual release as standard. Compatible actuator selection determines the pressure trip range, while optional electromagnetic release and closed-position sensing support remote systems.
Models: HON 711 - DN 200 thru 300
Features & Benefits
- Sizes
- DN200, DN250 and DN300
- Maximum admissible pressure
- 100 bar
- Response time
- 0.1–0.5 s
- Axial passage reduces pressure loss
Applications
- Gas transmission stations, power plants and industrial facilities
Detailed capabilities
HON 711 - DN 200 thru 300 — operating design
HON 711 in DN200 through DN300 uses an axial passage to limit pressure loss in large gas lines. The shut-off valve offers several release arrangements and is supplied with manual release as standard. Compatible actuator selection determines the pressure trip range, while optional electromagnetic release and closed-position sensing support remote systems.
Large axial body and release options
This HON 711 group covers DN200, DN250 and DN300. Axial flow limits pressure loss, while the listed actuator systems establish overpressure or underpressure response. Manual release is standard among four release arrangements, with electromagnetic release and closed-position sensing optional. The source gives 0.1–0.5 second closing response and identifies SIL certification for the applicable device.
Published configuration and technical facts
The manufacturer lists these values for HON 711 - DN 200 thru 300. Version, size and option qualifications remain attached to each fact.
- Maximum Operating Pressure: Up to 100 bar (130 bar on request for ANSI 900 RTJ) kilopascal
- Outlet Pressure Range: For over-pressure Wdso 80 mbar to 90 bar; For under-pressure Wdsu 10 mbar to 90 bar
- Temperature Range: -20 to +60 deg C (Class 2)
- Explosion Protection: Not subject to ATEX 95 (no ignition sources), electronic accessories must satisfy ATEX
- Approvals: CE (PED), DVGW, GOST, GOSTTECHNADSOR, SIL IEC61508
- Control Devices: K10a, K11a/1, K11a/2, K16, K17, K18, K19
- Connection Type: ANSI 300, 600 RF, RTJ, 900 RTJ (PS = 130 bar on request); DIN Flange PN 25, PN 40
- Nominal Widths: DN 25 to 300
- Response Time: 0.1 to 0.3 sec millisecond
- Materials: A 352 LCC/G20Mn5 QT Medium/Low Alloyed Steel
Environmental Conditions
- Maximum Operating Pressure
- Up to 100 bar (130 bar on request for ANSI 900 RTJ) kilopascal
- Outlet Pressure Range
- For over-pressure Wdso 80 mbar to 90 bar; For under-pressure Wdsu 10 mbar to 90 bar
- Temperature Range
- -20 to +60 deg C (Class 2)
Mechanical & Physical Properties
- Supplemental Fixture
- Manual Release, Current Supply, Current Failure, Remote Indication, Outdoor Type, Special Design
Standards & Certifications
- Explosion Protection
- Not subject to ATEX 95 (no ignition sources), electronic accessories must satisfy ATEX
- Approvals
- CE (PED), DVGW, GOST, GOSTTECHNADSOR, SIL IEC61508
Communication & Protocols
- Control Devices
- K10a, K11a/1, K11a/2, K16, K17, K18, K19
Technical Specifications
- Connection Type
- ANSI 300, 600 RF, RTJ, 900 RTJ (PS = 130 bar on request); DIN Flange PN 25, PN 40
Electrical Specifications
- Nominal Widths
- DN 25 to 300
I/O Capabilities
- Response Time
- 0.1 to 0.3 sec millisecond
Applications & Compatibility
- Applications
- Safety shut-off valve for gas pressure regulating stations, Natural gas (DVGW G 260) and other gases on request
Material Specifications
- Materials
- A 352 LCC/G20Mn5 QT Medium/Low Alloyed Steel
| Parameter | Published value / configuration |
|---|---|
| Maximum Operating Pressure | Up to 100 bar (130 bar on request for ANSI 900 RTJ) kilopascal |
| Outlet Pressure Range | For over-pressure Wdso 80 mbar to 90 bar; For under-pressure Wdsu 10 mbar to 90 bar |
| Temperature Range | -20 to +60 deg C (Class 2) |
| Supplemental Fixture | Manual Release, Current Supply, Current Failure, Remote Indication, Outdoor Type, Special Design |
| Explosion Protection | Not subject to ATEX 95 (no ignition sources), electronic accessories must satisfy ATEX |
| Approvals | CE (PED), DVGW, GOST, GOSTTECHNADSOR, SIL IEC61508 |
| Control Devices | K10a, K11a/1, K11a/2, K16, K17, K18, K19 |
| Connection Type | ANSI 300, 600 RF, RTJ, 900 RTJ (PS = 130 bar on request); DIN Flange PN 25, PN 40 |
| Nominal Widths | DN 25 to 300 |
| Response Time | 0.1 to 0.3 sec millisecond |
| Applications | Safety shut-off valve for gas pressure regulating stations, Natural gas (DVGW G 260) and other gases on request |
| Materials | A 352 LCC/G20Mn5 QT Medium/Low Alloyed Steel |
Values retain manufacturer model qualifications. Review Honeywell specifications ↗
Resources
Resources linked from the manufacturer’s page. Confirm the document revision and applicable model before installation or ordering.
Honeywell resource listing ↗Part Number
Published model / variant identifiers. A full ordering code requires the manufacturer configuration.
Published part numbers
1 parts
| Part Number | Description | Enquiry |
|---|---|---|
| HON711 | Safety Shut-Off Valve HON 711 | Request quotation |
Manufacturer sources
Last source check: 2026-11-02
HON 711 – DN 200 thru 300 Image · Manufacturer ownership retained; republication licence not independently confirmed
ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.
Your next project. A clear starting point.