Safety Shut-Off Valves
HON 303 MK5
HON 303 MK5 is a self-acting safety shut-off valve installed upstream of a regulator with an external downstream sensing line.
HON 303 MK5 is a self-acting safety shut-off valve installed upstream of a regulator with an external downstream sensing line. It closes the station on overpressure without an external supply. A pressure-compensation button supports manual resetting, while the LP and MP versions provide different release-setting ranges for the selected installation.
Models: HON 303 MK5
Features & Benefits
- Maximum inlet pressure
- 7 bar
- Sizes
- DN250 and DN300
- Reset
- Manual
- Low pressure loss and self-powered operation
Applications
- Gas supply and network overpressure protection
Detailed capabilities
HON 303 MK5 — operating design
HON 303 MK5 is a self-acting safety shut-off valve installed upstream of a regulator with an external downstream sensing line. It closes the station on overpressure without an external supply. A pressure-compensation button supports manual resetting, while the LP and MP versions provide different release-setting ranges for the selected installation.
Sensing and manual re-engagement
HON 303 MK5 is installed on the inlet side with an external line sensing the downstream pressure. Overpressure closes the supply automatically without auxiliary power. A pressure-equalization button assists hand reset. LP and MP series settings are separate, and the source lists DN250 and DN300 for this large-valve offering rather than the sizes of other HON shut-offs.
Published configuration and technical facts
The manufacturer lists these values for HON 303 MK5. Version, size and option qualifications remain attached to each fact.
- Maximum Inlet Pressure Rating: Up to 7 bar
- Pipe Size: DN 250, DN 300
- Temperature Range: -20 to 60 deg C
- Setting Range: Series 303LP: 0.037 to 0.48 bar; Series 303MP: 0.42 to 4.5 bar
Technical Specifications
- Maximum Inlet Pressure Rating
- Up to 7 bar
- Pipe Size
- DN 250, DN 300
Standards & Certifications
- Explosion Protection
- All mechanical components of this device are without potential ignition sources and/or hot faces. They are not subject to ATEX 95 (94/9/EC). All electronic accessories, on the other hand, meet ATEX requirements.
- Approvals
- CE Mark with PED
Environmental Conditions
- Temperature Range
- -20 to 60 deg C
- Setting Range
- Series 303LP: 0.037 to 0.48 bar; Series 303MP: 0.42 to 4.5 bar
Applications & Compatibility
- Applications
- Suitable for natural, non-aggressive and manufactured gases - nitrogen, carbon dioxide, propane and other gases upon enquiry
| Parameter | Published value / configuration |
|---|---|
| Maximum Inlet Pressure Rating | Up to 7 bar |
| Pipe Size | DN 250, DN 300 |
| Explosion Protection | All mechanical components of this device are without potential ignition sources and/or hot faces. They are not subject to ATEX 95 (94/9/EC). All electronic accessories, on the other hand, meet ATEX requirements. |
| Approvals | CE Mark with PED |
| Temperature Range | -20 to 60 deg C |
| Setting Range | Series 303LP: 0.037 to 0.48 bar; Series 303MP: 0.42 to 4.5 bar |
| Applications | Suitable for natural, non-aggressive and manufactured gases - nitrogen, carbon dioxide, propane and other gases upon enquiry |
Values retain manufacturer model qualifications. Review Honeywell specifications ↗
Part Number
Published model / variant identifiers. A full ordering code requires the manufacturer configuration.
Published part numbers
2 parts
| Part Number | Description | Enquiry |
|---|---|---|
| HON303LP | SERIES 303LP SAFETY CUT OFF VALVE | Request quotation |
| HON303MP | SERIES 303MP SAFETY CUT OFF VALVE | Request quotation |