Direct Fired Furnace Burners
ExtensoHeat
ExtensoHeat is a nozzle-mix lance burner for continuous kilns producing bricks, roof tiles and rough ceramics.
ExtensoHeat is a nozzle-mix lance burner for continuous kilns producing bricks, roof tiles and rough ceramics. The lance reaches through thick walls toward the load, including roof installations above 750°C. Adjustable fuel and air valves support control, with published on/off, modulation and pulse-firing options and several gaseous fuels.
Features & Benefits
- Minimum Operating Temperature
- 1,382 deg F (750 deg C)
- Maximum Furnace Temperature
- 1,832 deg F (1000 deg C)|up to 2,282 deg F (1250 deg C) with high-temp alloy air tube
- Minimum Operating O2 Level
- 12% (vol.)
- Maximum Flame Velocity
- 328 ft/s (100 m/s)
- Fuel Inlet Pressure
- 200 to 1,000 in wc (0.5 to 2.5 bar)
- Air Inlet Pressure
- 4 to 6 in wc (10 to 15 mbar)
- Piping Interfaces
- NPT or BSP
- Maximum Inputs
- 500,000 Btu/hr (146 kW)
- Air Inlet Flow
- 1,765 to 2,118 cfh (50 to 60 Nm³/hr)
- Minimum Input
- 85,000 Btu/hr (25 kW)
- Ignition Type
- Self-ignition by process temperature
- Flame Length
- 27.6 to 39.4 in (700 to 1000 mm) (High Fire)|700 to 1000 mm
- Burner Type
- Lance Burner
- Fuel Type
- Natural Gas, Propane, Butane
- Approvals
- GOST-R Approval, CE, NFPA, EAC, EN Standards
- High-velocity injection promotes even kiln temperature.
- Control options accommodate on/off, modulating or pulse firing.
Applications
- Continuous brick, roof-tile and rough-ceramic kilns
Detailed capabilities
Kiln control and combustion arrangement
ExtensoHeat carries a nozzle-mix flame through a lance toward the load, including thick-wall and roof-mounted kiln arrangements. Adjustable fuel and air valves set operation, with on/off, pulse or modulating control available. The page describes high excess-gas operation, a support-mounted observation port and high-velocity circulation. Capacity and flame-length figures are specific to the published burner arrangement and its fuel heating-value basis.
Features and benefits
- High-velocity injection promotes even kiln temperature.
- Control options accommodate on/off, modulating or pulse firing.
Published application context
- Continuous brick, roof-tile and rough-ceramic kilns
Overview
- Models
- ExtensoHeat EH050
- Burner Type
- Lance Burner
Operating/Process Temperature Ranges
- Minimum Operating Temperature
- 1,382 deg F (750 deg C)
Maximum/Minimum Temperature Limits
- Maximum Furnace Temperature
- 1,832 deg F (1000 deg C); up to 2,282 deg F (1250 deg C) with high-temp alloy air tube
Operating Limits & Resistance
- Minimum Operating O2 Level
- 12% (vol.)
Ignition, Flame & Supervision Specifications
- Maximum Flame Velocity
- 328 ft/s (100 m/s)
- Ignition Type
- Self-ignition by process temperature
Pressure Specifications
- Fuel Inlet Pressure
- 200 to 1,000 in wc (0.5 to 2.5 bar)
Air & Combustion Air Specifications
- Air Inlet Pressure
- 4 to 6 in wc (10 to 15 mbar)
- Air Inlet Flow
- 1,765 to 2,118 cfh (50 to 60 Nm³/hr)
Mechanical Design, Layout & Construction Options
- Piping Interfaces
- NPT or BSP
Inputs, Outputs & Interface Signals
- Maximum Inputs
- 500,000 Btu/hr (146 kW)
- Minimum Input
- 85,000 Btu/hr (25 kW)
Burner/Flame‑Related Lengths
- Flame Length
- 27.6 to 39.4 in (700 to 1000 mm) (High Fire); 700 to 1000 mm
Fuel, Gas & Media Specifications
- Fuel Type
- Natural Gas, Propane, Butane
Standards & Certifications
- Approvals
- GOST-R Approval, CE, NFPA, EAC, EN Standards
| Parameter | Published value / configuration |
|---|---|
| Models | ExtensoHeat EH050 |
| Burner Type | Lance Burner |
| Minimum Operating Temperature | 1,382 deg F (750 deg C) |
| Maximum Furnace Temperature | 1,832 deg F (1000 deg C); up to 2,282 deg F (1250 deg C) with high-temp alloy air tube |
| Minimum Operating O2 Level | 12% (vol.) |
| Maximum Flame Velocity | 328 ft/s (100 m/s) |
| Ignition Type | Self-ignition by process temperature |
| Fuel Inlet Pressure | 200 to 1,000 in wc (0.5 to 2.5 bar) |
| Air Inlet Pressure | 4 to 6 in wc (10 to 15 mbar) |
| Air Inlet Flow | 1,765 to 2,118 cfh (50 to 60 Nm³/hr) |
| Piping Interfaces | NPT or BSP |
| Maximum Inputs | 500,000 Btu/hr (146 kW) |
| Minimum Input | 85,000 Btu/hr (25 kW) |
| Flame Length | 27.6 to 39.4 in (700 to 1000 mm) (High Fire); 700 to 1000 mm |
| Fuel Type | Natural Gas, Propane, Butane |
| Approvals | GOST-R Approval, CE, NFPA, EAC, EN Standards |
Values retain manufacturer model qualifications. Review Honeywell specifications ↗
Manufacturer sources
Last source check: 2026-11-02
ExtensoHeat Product Image · Manufacturer ownership retained; republication licence not independently confirmed
ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.