Fire & Life Safety · Building Systems · Industrial Automation [email protected] +880 1347 561 256
Honeywell Process Measurement & Control

Direct Fired Furnace Burners

BIC, BICA, ZIC

BIC, BICA and ZIC connect to ceramic burner tubes and differ in housing material: cast steel, aluminum and sheet steel.

BIC, BICA and ZIC connect to ceramic burner tubes and differ in housing material: cast steel, aluminum and sheet steel. The family covers cold-air, hot-air, flat-flame and high-temperature duties. Fuel options include conventional gases, while biological methane and low-calorific gases require consultation; insulated housings and ignition lances are available.

Features & Benefits

Maximum Furnace Temperature
Up to 1450 deg C (2642 deg F)
Ambient Temperature Range
-20 to +180°C (-4 to +356°F)
Installation Orientation
Horizontal or angled
Air Preheat Capability
Up to 600 deg C (1112 deg F)
Ceramic Tube Material
SiSiC (Silicon Infiltrated Silicon Carbide)
Visible Flame Length
22 to 200 cm depending on model
Combustion Principle
Nozzle‑mixing
Flame Supervision
Flame rod standard; UV sensor optional
Outlet Velocity
Medium to high (up to 155 m/s)
Capacity Range
BIC: 15 to 1000 kW|BICA: 15 to 70 kW|ZIC: 315 to 1000 kW
Ignition Type
Direct spark, integrated torch
Control Type
On/Off, modulating, pilot rate, pneumatic ratio control
Fuel Type
BIC: Natural gas, LPG, coke oven gas, town gas, biogas, low‑CV gas|BICA: Natural gas, LPG|ZIC: Natural gas, LPG, coke oven gas, town gas, biogas, low‑CV gas
Approvals
Eurasian Customs Union (Meets technical specifications), EN 746-2, REACH Regulation (Applies to BICW/ZICW (contains RCF/ASW insulation)), WEEE Directive Disposal Compliance, Machinery Directive 2006/42/EC
Material
BIC: Cast Steel|BICA: AlSi|BICW/ZICW: Steel + insulation|ZIC: Steel
Burner sizes
50 to 200
Capacity
10 to 1000 kW
Burner length
300 to 1200 mm

Applications

  • Cold-air and hot-air furnace heating
  • Flat-flame and high-temperature firing

Detailed capabilities

Housing, fuel and burner-tube selections

BIC uses cast steel, BICA aluminum and ZIC sheet steel, all with ceramic-tube connection. Threaded gas connections and burner lengths are selected around the furnace. Integrated ignition lances and internal insulation are optional configurations. The source lists conventional gases directly but requires consultation for biological methane and low-calorific fuels; those fuels are not unconditional approvals for every standard burner.

Manufacturer reference ↗

Published application context

  • Cold-air and hot-air furnace heating
  • Flat-flame and high-temperature firing

Manufacturer reference ↗

Technical facts in the product overview

  • Burner sizes: 50 to 200
  • Capacity: 10 to 1000 kW
  • Burner length: 300 to 1200 mm

Manufacturer reference ↗

Specifications

Overview

Models
BIC, BICA, BICW, ZIC, ZICW

Maximum/Minimum Temperature Limits

Maximum Furnace Temperature
Up to 1450 deg C (2642 deg F)

Environmental Conditions

Ambient Temperature Range
-20 to +180°C (-4 to +356°F)

Installation & Mounting Specifications

Installation Orientation
Horizontal or angled

Air & Combustion Air Specifications

Air Preheat Capability
Up to 600 deg C (1112 deg F)

Material Specifications

Ceramic Tube Material
SiSiC (Silicon Infiltrated Silicon Carbide)
Material
BIC: Cast Steel; BICA: AlSi; BICW/ZICW: Steel + insulation; ZIC: Steel

Burner/Flame‑Related Lengths

Visible Flame Length
22 to 200 cm depending on model

Combustion, Mixing & Fuel Dynamics

Combustion Principle
Nozzle‑mixing

Ignition, Flame & Supervision Specifications

Flame Supervision
Flame rod standard; UV sensor optional
Ignition Type
Direct spark, integrated torch

Processing & Performance Metrics

Outlet Velocity
Medium to high (up to 155 m/s)
Capacity Range
BIC: 15 to 1000 kW; BICA: 15 to 70 kW; ZIC: 315 to 1000 kW

Control, Logic & Functional Behavior

Control Type
On/Off, modulating, pilot rate, pneumatic ratio control

Fuel, Gas & Media Specifications

Fuel Type
BIC: Natural gas, LPG, coke oven gas, town gas, biogas, low‑CV gas; BICA: Natural gas, LPG; ZIC: Natural gas, LPG, coke oven gas, town gas, biogas, low‑CV gas

Standards & Certifications

Approvals
Eurasian Customs Union (Meets technical specifications), EN 746-2, REACH Regulation (Applies to BICW/ZICW (contains RCF/ASW insulation)), WEEE Directive Disposal Compliance, Machinery Directive 2006/42/EC

Technical Specifications

Burner sizes
50 to 200
Capacity
10 to 1000 kW
Burner length
300 to 1200 mm
BIC, BICA, ZIC — manufacturer page values
ParameterPublished value / configuration
ModelsBIC, BICA, BICW, ZIC, ZICW
Maximum Furnace TemperatureUp to 1450 deg C (2642 deg F)
Ambient Temperature Range-20 to +180°C (-4 to +356°F)
Installation OrientationHorizontal or angled
Air Preheat CapabilityUp to 600 deg C (1112 deg F)
Ceramic Tube MaterialSiSiC (Silicon Infiltrated Silicon Carbide)
MaterialBIC: Cast Steel; BICA: AlSi; BICW/ZICW: Steel + insulation; ZIC: Steel
Visible Flame Length22 to 200 cm depending on model
Combustion PrincipleNozzle‑mixing
Flame SupervisionFlame rod standard; UV sensor optional
Ignition TypeDirect spark, integrated torch
Outlet VelocityMedium to high (up to 155 m/s)
Capacity RangeBIC: 15 to 1000 kW; BICA: 15 to 70 kW; ZIC: 315 to 1000 kW
Control TypeOn/Off, modulating, pilot rate, pneumatic ratio control
Fuel TypeBIC: Natural gas, LPG, coke oven gas, town gas, biogas, low‑CV gas; BICA: Natural gas, LPG; ZIC: Natural gas, LPG, coke oven gas, town gas, biogas, low‑CV gas
ApprovalsEurasian Customs Union (Meets technical specifications), EN 746-2, REACH Regulation (Applies to BICW/ZICW (contains RCF/ASW insulation)), WEEE Directive Disposal Compliance, Machinery Directive 2006/42/EC
Burner sizes50 to 200
Capacity10 to 1000 kW
Burner length300 to 1200 mm

Values retain manufacturer model qualifications. Review Honeywell specifications ↗

Part Number

Published part numbers

10 parts

Part NumberDescriptionEnquiry
HK2966GSKT,8 RPM FLG KLNGR,1/8 THK,750°F 95070Request quotation
HK2967AGSKT,10 FLG KLNGR,1/8 THK,750°F 95070Request quotation
HK401313GSKT,8 ANSI GAS INLT KLNGR,1/8 THK,750°FRequest quotation
HK406865-DGSKT,GAS TB BB 1106 3110 KLNGR,1/8 THK,7Request quotation
HK406917-BGSKT,GAS TB BB 1112 3114 KLNGR,1/8 THK,7Request quotation
HK44307GSKT,BBC OIL TB BKPLT KLNGR,1/8 THK,750°Request quotation
HK52994GSKT,BBX114/X118 GAS TB KLNGR,1/8 THK,75Request quotation
HK53032GSKT,BBX1112 GAS TB KLNGR,1/8 THK,750°FRequest quotation
HK55274GSKT,BBG2106 BRNR MTG KLNGR,1/8 THK,750°Request quotation
HK70022GSKT,6 RPM KLNGR,1/8 THK,750°F 95070Request quotation
Manufacturer sources

https://process.honeywell.com/us/en/products/thermal-solutions/burners-and-heat-exchangers/direct-fired-furnace-burners/bic-bica-zic

Last source check: 2026-11-02

Burner for gas · Manufacturer ownership retained; republication licence not independently confirmed

ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.

Your next project. A clear starting point.

Tell us about your facility and what you need to achieve.

CallSend enquiry