Fire & Life Safety · Building Systems · Industrial Automation [email protected] +880 1347 561 256
Honeywell Process Measurement & Control

Direct Fired Furnace Burners

BIC..L

BIC..L is an excess-air burner family for processes needing controlled temperature and consistent heating.

BIC..L is an excess-air burner family for processes needing controlled temperature and consistent heating. The page lists natural gas and gaseous LPG, with other fuels available by request, and direct spark ignition. Its published capacity range is 75–440 kW; the stated furnace-temperature figure should be checked in the technical documentation.

Features & Benefits

Maximum Combustion Air Temperature
≤ 250 deg C
Maximum Furnace Temperature
1250 deg C (higher on request)
Ambient Temperature Range
-20 to +180 deg C (-4 to +356 deg F)
Installation Orientation
Horizontal or angled
Cooling/Purge Air Option
2 to 6 % of rated air flow when burner is off
Excess Air Capability
Up to ≈1500% (λ up to ~16)
Maintenance Interval
Twice per year (more frequent if media is contaminated)
Combustion Principle
Nozzle‑mixing (gas and air mix only at burner head)
Turndown Capability
High (supported by excess‑air operation)
Flame Supervision
Flame rod standard
Outlet Velocity
High (up to 250 m/s)
Capacity Range
85 kW to 440 kW (320 to 1664 x 10³ BTU/h)
Ignition Type
Direct spark ignition
Flame Length
450 to 900 mm depending on model
Control Type
ON/OFF cyclic, staged, or modulating
Fuel Type
Natural Gas
Approvals
EN 746-2 (Compliance for industrial thermoprocessing equipment), Eurasian Customs Union (Meets technical specifications), Machinery Directive 2006/42/EC Declaration of Incorporation confirmed, WEEE Directive Disposal compliance
Material
Cast Steel (GG)
  • Excess-air operation supports controlled temperature and consistent heating.

Applications

  • Excess-air heating requiring precise temperature control

Specifications

Combustion/Furnace/Chamber Temperatures

Maximum Combustion Air Temperature
≤ 250 deg C

Maximum/Minimum Temperature Limits

Maximum Furnace Temperature
1250 deg C (higher on request)

Environmental Conditions

Ambient Temperature Range
-20 to +180 deg C (-4 to +356 deg F)

Installation & Mounting Specifications

Installation Orientation
Horizontal or angled

Air & Combustion Air Specifications

Cooling/Purge Air Option
2 to 6 % of rated air flow when burner is off
Excess Air Capability
Up to ≈1500% (λ up to ~16)

Electrical Specifications

Maintenance Interval
Twice per year (more frequent if media is contaminated)

Combustion, Mixing & Fuel Dynamics

Combustion Principle
Nozzle‑mixing (gas and air mix only at burner head)

Processing & Performance Metrics

Turndown Capability
High (supported by excess‑air operation)
Outlet Velocity
High (up to 250 m/s)
Capacity Range
85 kW to 440 kW (320 to 1664 x 10³ BTU/h)

Ignition, Flame & Supervision Specifications

Flame Supervision
Flame rod standard
Ignition Type
Direct spark ignition

Burner/Flame‑Related Lengths

Flame Length
450 to 900 mm depending on model

Control, Logic & Functional Behavior

Control Type
ON/OFF cyclic, staged, or modulating

Fuel, Gas & Media Specifications

Fuel Type
Natural Gas

Standards & Certifications

Approvals
EN 746-2 (Compliance for industrial thermoprocessing equipment), Eurasian Customs Union (Meets technical specifications), Machinery Directive 2006/42/EC Declaration of Incorporation confirmed, WEEE Directive Disposal compliance

Material Specifications

Material
Cast Steel (GG)
BIC..L — manufacturer page values
ParameterPublished value / configuration
Maximum Combustion Air Temperature≤ 250 deg C
Maximum Furnace Temperature1250 deg C (higher on request)
Ambient Temperature Range-20 to +180 deg C (-4 to +356 deg F)
Installation OrientationHorizontal or angled
Cooling/Purge Air Option2 to 6 % of rated air flow when burner is off
Excess Air CapabilityUp to ≈1500% (λ up to ~16)
Maintenance IntervalTwice per year (more frequent if media is contaminated)
Combustion PrincipleNozzle‑mixing (gas and air mix only at burner head)
Turndown CapabilityHigh (supported by excess‑air operation)
Outlet VelocityHigh (up to 250 m/s)
Capacity Range85 kW to 440 kW (320 to 1664 x 10³ BTU/h)
Flame SupervisionFlame rod standard
Ignition TypeDirect spark ignition
Flame Length450 to 900 mm depending on model
Control TypeON/OFF cyclic, staged, or modulating
Fuel TypeNatural Gas
ApprovalsEN 746-2 (Compliance for industrial thermoprocessing equipment), Eurasian Customs Union (Meets technical specifications), Machinery Directive 2006/42/EC Declaration of Incorporation confirmed, WEEE Directive Disposal compliance
MaterialCast Steel (GG)

Values retain manufacturer model qualifications. Review Honeywell specifications ↗

Manufacturer sources

https://process.honeywell.com/us/en/products/thermal-solutions/burners-and-heat-exchangers/direct-fired-furnace-burners/bic-l

Last source check: 2026-11-02

Excess air burner · Manufacturer ownership retained; republication licence not independently confirmed

ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.

Your next project. A clear starting point.

Tell us about your facility and what you need to achieve.

CallSend enquiry