SOLA Boiler Control Unit

SOLA consolidates boiler heat control, ignition, flame supervision, fan functions and circulation-pump control.

SOLA consolidates boiler heat control, ignition, flame supervision, fan functions and circulation-pump control. R7910A addresses hydronic boilers and R7911 addresses steam boilers. Integrated limits, PID load control and modulation reduce separate controls and wiring, while setback and outdoor-reset functions support the boiler's energy-management strategy.

Features & Benefits

Storage/Shipping Temperature
-40 to 150 deg F (-40 to 66 deg C)
Operating Temperature Range
-4 to 150 deg F (-20 to 66 deg C)
Modulation Output
PWM, 4 to 20 mA, 0 to 10 V
Flame Signal Test
0 to 15 V range, 0.8 V indicates flame
Display Interface
S7999B, S7999C, S7910A
Enclosure Rating
NEMA 1/IP40
Flame Detection
Flame rod or UV
Humidity Range
Up to 95% RH, non-condensing at 104 deg F for 14 days
Fault History
15-item lockout and alert history
Communication
RS485 ModBus, ECOM
Pump Outputs
3 outputs, 5 programmable features
Power Supply
24 VAC (20 to 30 VAC, 60 Hz ±5%)
Sensor Type
NTC 10KΩ or 12KΩ at 77 deg F (25 deg C)
Fan Control
PWM-driven DC fan
Approvals
UL 353: Certified as a Limit Rated Device (with 10K dual element NTC sensors), UL 372: Certified as Primary Safety Control, cUL: Component Recognized (File No. MP268), CSD-1 Acceptable, Section CF-300: Primary Safety Control, Section CW-400: Temperature Operation Control, Section CW-400: Temperature High Limit Control, FCC Part 15, Class B: Emissions compliance
  • Combining boiler functions reduces separate wiring and maintenance.
  • Reset, setback and modulation functions support reduced boiler energy use.

Applications

  • Hydronic boilers with R7910A
  • Steam boilers with R7911

Specifications

Overview

Models
R7910A SOLA HC (Hydronic Control), R7911 SOLA SC (Steam Control)

Storage/Transport Temperatures

Storage/Shipping Temperature
-40 to 150 deg F (-40 to 66 deg C)

Operating/Process Temperature Ranges

Operating Temperature Range
-4 to 150 deg F (-20 to 66 deg C)

Control, Logic & Functional Behavior

Modulation Output
PWM, 4 to 20 mA, 0 to 10 V

Ignition, Flame & Supervision Specifications

Flame Signal Test
0 to 15 V range, 0.8 V indicates flame
Flame Detection
Flame rod or UV

Inputs, Outputs & Interface Signals

Display Interface
S7999B, S7999C, S7910A

Environmental Conditions

Enclosure Rating
NEMA 1/IP40
Humidity Range
Up to 95% RH, non-condensing at 104 deg F for 14 days

Alarms, Diagnostics & Monitoring

Fault History
15-item lockout and alert history

Communication & Interfaces

Communication
RS485 ModBus, ECOM

Mechanical & Hardware Characteristics

Pump Outputs
3 outputs, 5 programmable features

Electrical Specifications

Power Supply
24 VAC (20 to 30 VAC, 60 Hz ±5%)

Measurement, Accuracy & Sensing

Sensor Type
NTC 10KΩ or 12KΩ at 77 deg F (25 deg C)

Combustion Air, Blower & Emissions Specifications

Fan Control
PWM-driven DC fan

Standards & Certifications

Approvals
UL 353: Certified as a Limit Rated Device (with 10K dual element NTC sensors), UL 372: Certified as Primary Safety Control, cUL: Component Recognized (File No. MP268), CSD-1 Acceptable, Section CF-300: Primary Safety Control, Section CW-400: Temperature Operation Control, Section CW-400: Temperature High Limit Control, FCC Part 15, Class B: Emissions compliance
SOLA Boiler Control Unit — manufacturer page values
ParameterPublished value / configuration
ModelsR7910A SOLA HC (Hydronic Control), R7911 SOLA SC (Steam Control)
Storage/Shipping Temperature-40 to 150 deg F (-40 to 66 deg C)
Operating Temperature Range-4 to 150 deg F (-20 to 66 deg C)
Modulation OutputPWM, 4 to 20 mA, 0 to 10 V
Flame Signal Test0 to 15 V range, 0.8 V indicates flame
Flame DetectionFlame rod or UV
Display InterfaceS7999B, S7999C, S7910A
Enclosure RatingNEMA 1/IP40
Humidity RangeUp to 95% RH, non-condensing at 104 deg F for 14 days
Fault History15-item lockout and alert history
CommunicationRS485 ModBus, ECOM
Pump Outputs3 outputs, 5 programmable features
Power Supply24 VAC (20 to 30 VAC, 60 Hz ±5%)
Sensor TypeNTC 10KΩ or 12KΩ at 77 deg F (25 deg C)
Fan ControlPWM-driven DC fan
ApprovalsUL 353: Certified as a Limit Rated Device (with 10K dual element NTC sensors), UL 372: Certified as Primary Safety Control, cUL: Component Recognized (File No. MP268), CSD-1 Acceptable, Section CF-300: Primary Safety Control, Section CW-400: Temperature Operation Control, Section CW-400: Temperature High Limit Control, FCC Part 15, Class B: Emissions compliance

Values retain manufacturer model qualifications. Review Honeywell specifications ↗

Part Number

Published part numbers

10 parts

Part NumberDescriptionEnquiry
32003971-002/USENSOR WITH 6 INCH LEADWIRESRequest quotation
32003971-003/UOTC AND HEADER SENSOR KITRequest quotation
32006512-006/BNAMEPLATE LABELRequest quotation
50001464-006/USENSOR WITH 6 INCH LEADWIRES AND FEMALERequest quotation
50001464-007/USENSOR WITH 42 INCH LEADWIRES WITH END SRequest quotation
50024861-334INDUCTORRequest quotation
50032893-001/UBAG ASSEMBLYRequest quotation
50057608-003IC MCU ARM 64KB 324TFBGARequest quotation
50061545-002LCD DISPLAY - 7INCH 800X480 24BIT COLORRequest quotation
50063482-001/XBAG ASSEMBLYRequest quotation
Manufacturer sources

https://process.honeywell.com/us/en/products/thermal-solutions/burner-management-systems/burner-control-units/sola-boiler-control-unit

Last source check: 2026-11-02

SOLA R7910A · Manufacturer ownership retained; republication licence not independently confirmed

ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.

Your next project. A clear starting point.

Tell us about your facility and what you need to achieve.

CallSend enquiry