Burner Control Units
Automatic burner control units PFU
PFU combines ignition, burner sequencing and flame supervision in a rack-mounted control family.
PFU combines ignition, burner sequencing and flame supervision in a rack-mounted control family. Ionization permits continuous duty; UVS sensing is limited to intermittent duty, while the UVD 1 variant permits continuous UV supervision. An optical interface supports setup and diagnostics, and the display presents operating parameters and flame information.
Features & Benefits
- Operating Temperature Range
- -20 to +60 deg C (-4 to +140 deg F)|No condensation allowed
- Minimum Burner Pause Time
- 0 to 250 seconds
- Start-up Safety Time
- Adjustable: 3, 5, or 10 seconds
- Flame Proving Period
- 0 to 25 s
- Sensor Cable Length
- Max. 100 m
- Software Interface
- BCSoft (via optical interface)
- Fieldbus Interface
- PROFIBUS DP via PFA 700
- Start-up Attempts
- 1 to 4
- Air Valve Control
- Integrated (PFU..L variant)
- Restart Attempts
- Up to 3 (configurable)
- Enclosure Rating
- IP00 (IP20 when installed in module subrack)
- Sensor Voltage
- ~230 V AC
- Altitude Limit
- < 2000 m AMSL
- Mains Voltage
- PFU..N: 110/120 VAC|PFU..T: 220/240 VAC
- Flame Control
- UV, ionization, or temperature (high-temp version)
- Display Type
- 2-digit 7-segment display for program status and flame signal
- Manual Mode
- Available for commissioning and diagnostics
- Dimensions
- 133.4 mm H x 40.6 mm W
- Approvals
- SIL 3 (EN 61508), EN 298:2012, FM Approved PFU..T variant only; NFPA 86 Compliant, AGA Approved, UKCA Certified, Eurasian Customs Union
- Safety time on start-up
- 3, 5 or 10 s
- Safety time during operation
- 1 or 2 s
Applications
- Impulse, modulating or staged gas-burner control
Detailed capabilities
Sensing, control access and model references
The optical interface allows parameter adjustment and diagnosis, with manual mode and air-valve control described. The display exposes program state, parameters and flame signal. The narrative names PFU 778 for direct ignition and PFU 798 for pilot/main arrangements, but the specification and selection references identify PFU 760/780. That source inconsistency is retained; model identity should be established from the exact technical information rather than silently substituting one identifier.
Published application context
- Impulse, modulating or staged gas-burner control
Technical facts in the product overview
- Safety time on start-up: 3, 5 or 10 s
- Safety time during operation: 1 or 2 s
Overview
- Models
- PFU 760, PFU 780
Operating/Process Temperature Ranges
- Operating Temperature Range
- -20 to +60 deg C (-4 to +140 deg F); No condensation allowed
Operating Limits & Resistance
- Minimum Burner Pause Time
- 0 to 250 seconds
Control, Safety & Timing Characteristics
- Start-up Safety Time
- Adjustable: 3, 5, or 10 seconds
Ignition, Flame & Supervision Specifications
- Flame Proving Period
- 0 to 25 s
- Flame Control
- UV, ionization, or temperature (high-temp version)
Dimensions & Length Specifications
- Sensor Cable Length
- Max. 100 m
Control, Software & User Interface Specifications
- Software Interface
- BCSoft (via optical interface)
- Display Type
- 2-digit 7-segment display for program status and flame signal
Communication & Interfaces
- Fieldbus Interface
- PROFIBUS DP via PFA 700
Control, Logic & System Behavior
- Start-up Attempts
- 1 to 4
- Restart Attempts
- Up to 3 (configurable)
Air & Combustion Air Specifications
- Air Valve Control
- Integrated (PFU..L variant)
Environmental Conditions
- Enclosure Rating
- IP00 (IP20 when installed in module subrack)
Electrical Specifications
- Sensor Voltage
- ~230 V AC
- Mains Voltage
- PFU..N: 110/120 VAC; PFU..T: 220/240 VAC
Operating Limits, Durability & Lifecycle
- Altitude Limit
- < 2000 m AMSL
Applications & Compatibility
- Applications
- PFU 760: Directly ignited burners; intermittent or continuous operation; PFU 780: Pilot + main burners, intermittent or continuous operation
Control, Logic & Functional Behavior
- Manual Mode
- Available for commissioning and diagnostics
Dimensions & Weight
- Dimensions
- 133.4 mm H x 40.6 mm W
Standards & Certifications
- Approvals
- SIL 3 (EN 61508), EN 298:2012, FM Approved PFU..T variant only; NFPA 86 Compliant, AGA Approved, UKCA Certified, Eurasian Customs Union
Technical Specifications
- Safety time on start-up
- 3, 5 or 10 s
- Safety time during operation
- 1 or 2 s
| Parameter | Published value / configuration |
|---|---|
| Models | PFU 760, PFU 780 |
| Operating Temperature Range | -20 to +60 deg C (-4 to +140 deg F); No condensation allowed |
| Minimum Burner Pause Time | 0 to 250 seconds |
| Start-up Safety Time | Adjustable: 3, 5, or 10 seconds |
| Flame Proving Period | 0 to 25 s |
| Flame Control | UV, ionization, or temperature (high-temp version) |
| Sensor Cable Length | Max. 100 m |
| Software Interface | BCSoft (via optical interface) |
| Display Type | 2-digit 7-segment display for program status and flame signal |
| Fieldbus Interface | PROFIBUS DP via PFA 700 |
| Start-up Attempts | 1 to 4 |
| Restart Attempts | Up to 3 (configurable) |
| Air Valve Control | Integrated (PFU..L variant) |
| Enclosure Rating | IP00 (IP20 when installed in module subrack) |
| Sensor Voltage | ~230 V AC |
| Mains Voltage | PFU..N: 110/120 VAC; PFU..T: 220/240 VAC |
| Altitude Limit | < 2000 m AMSL |
| Applications | PFU 760: Directly ignited burners; intermittent or continuous operation; PFU 780: Pilot + main burners, intermittent or continuous operation |
| Manual Mode | Available for commissioning and diagnostics |
| Dimensions | 133.4 mm H x 40.6 mm W |
| Approvals | SIL 3 (EN 61508), EN 298:2012, FM Approved PFU..T variant only; NFPA 86 Compliant, AGA Approved, UKCA Certified, Eurasian Customs Union |
| Safety time on start-up | 3, 5 or 10 s |
| Safety time during operation | 1 or 2 s |
Values retain manufacturer model qualifications. Review Honeywell specifications ↗
Part Number
Published part numbers
10 parts
| Part Number | Description | Enquiry |
|---|---|---|
| KS88650271 | PFU760LTK1 | Request quotation |
| KS88650272 | PFU760LTD | Request quotation |
| KS88650273 | PFU760LT | Request quotation |
| KS88650274 | PFU760LT | Request quotation |
| KS88650275 | PFU760LT | Request quotation |
| KS88650276 | PFU760LT | Request quotation |
| KS88650277 | PFU760LT | Request quotation |
| KS88650278 | PFU760LT | Request quotation |
| KS88650279 | PFU780LT | Request quotation |
| KS88650280 | PFU780LTUK2 | Request quotation |
Manufacturer sources
Last source check: 2026-11-02
Burner control unit · Manufacturer ownership retained; republication licence not independently confirmed
ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.