Fire & Life Safety · Building Systems · Industrial Automation [email protected] +880 1347 561 256
Honeywell Process Measurement & Control

Burner Control Units

Automatic burner control units PFU

PFU combines ignition, burner sequencing and flame supervision in a rack-mounted control family.

PFU combines ignition, burner sequencing and flame supervision in a rack-mounted control family. Ionization permits continuous duty; UVS sensing is limited to intermittent duty, while the UVD 1 variant permits continuous UV supervision. An optical interface supports setup and diagnostics, and the display presents operating parameters and flame information.

Features & Benefits

Operating Temperature Range
-20 to +60 deg C (-4 to +140 deg F)|No condensation allowed
Minimum Burner Pause Time
0 to 250 seconds
Start-up Safety Time
Adjustable: 3, 5, or 10 seconds
Flame Proving Period
0 to 25 s
Sensor Cable Length
Max. 100 m
Software Interface
BCSoft (via optical interface)
Fieldbus Interface
PROFIBUS DP via PFA 700
Start-up Attempts
1 to 4
Air Valve Control
Integrated (PFU..L variant)
Restart Attempts
Up to 3 (configurable)
Enclosure Rating
IP00 (IP20 when installed in module subrack)
Sensor Voltage
~230 V AC
Altitude Limit
< 2000 m AMSL
Mains Voltage
PFU..N: 110/120 VAC|PFU..T: 220/240 VAC
Flame Control
UV, ionization, or temperature (high-temp version)
Display Type
2-digit 7-segment display for program status and flame signal
Manual Mode
Available for commissioning and diagnostics
Dimensions
133.4 mm H x 40.6 mm W
Approvals
SIL 3 (EN 61508), EN 298:2012, FM Approved PFU..T variant only; NFPA 86 Compliant, AGA Approved, UKCA Certified, Eurasian Customs Union
Safety time on start-up
3, 5 or 10 s
Safety time during operation
1 or 2 s

Applications

  • Impulse, modulating or staged gas-burner control

Detailed capabilities

Sensing, control access and model references

The optical interface allows parameter adjustment and diagnosis, with manual mode and air-valve control described. The display exposes program state, parameters and flame signal. The narrative names PFU 778 for direct ignition and PFU 798 for pilot/main arrangements, but the specification and selection references identify PFU 760/780. That source inconsistency is retained; model identity should be established from the exact technical information rather than silently substituting one identifier.

Manufacturer reference ↗

Published application context

  • Impulse, modulating or staged gas-burner control

Manufacturer reference ↗

Technical facts in the product overview

  • Safety time on start-up: 3, 5 or 10 s
  • Safety time during operation: 1 or 2 s

Manufacturer reference ↗

Specifications

Overview

Models
PFU 760, PFU 780

Operating/Process Temperature Ranges

Operating Temperature Range
-20 to +60 deg C (-4 to +140 deg F); No condensation allowed

Operating Limits & Resistance

Minimum Burner Pause Time
0 to 250 seconds

Control, Safety & Timing Characteristics

Start-up Safety Time
Adjustable: 3, 5, or 10 seconds

Ignition, Flame & Supervision Specifications

Flame Proving Period
0 to 25 s
Flame Control
UV, ionization, or temperature (high-temp version)

Dimensions & Length Specifications

Sensor Cable Length
Max. 100 m

Control, Software & User Interface Specifications

Software Interface
BCSoft (via optical interface)
Display Type
2-digit 7-segment display for program status and flame signal

Communication & Interfaces

Fieldbus Interface
PROFIBUS DP via PFA 700

Control, Logic & System Behavior

Start-up Attempts
1 to 4
Restart Attempts
Up to 3 (configurable)

Air & Combustion Air Specifications

Air Valve Control
Integrated (PFU..L variant)

Environmental Conditions

Enclosure Rating
IP00 (IP20 when installed in module subrack)

Electrical Specifications

Sensor Voltage
~230 V AC
Mains Voltage
PFU..N: 110/120 VAC; PFU..T: 220/240 VAC

Operating Limits, Durability & Lifecycle

Altitude Limit
< 2000 m AMSL

Applications & Compatibility

Applications
PFU 760: Directly ignited burners; intermittent or continuous operation; PFU 780: Pilot + main burners, intermittent or continuous operation

Control, Logic & Functional Behavior

Manual Mode
Available for commissioning and diagnostics

Dimensions & Weight

Dimensions
133.4 mm H x 40.6 mm W

Standards & Certifications

Approvals
SIL 3 (EN 61508), EN 298:2012, FM Approved PFU..T variant only; NFPA 86 Compliant, AGA Approved, UKCA Certified, Eurasian Customs Union

Technical Specifications

Safety time on start-up
3, 5 or 10 s
Safety time during operation
1 or 2 s
Automatic burner control units PFU — manufacturer page values
ParameterPublished value / configuration
ModelsPFU 760, PFU 780
Operating Temperature Range-20 to +60 deg C (-4 to +140 deg F); No condensation allowed
Minimum Burner Pause Time0 to 250 seconds
Start-up Safety TimeAdjustable: 3, 5, or 10 seconds
Flame Proving Period0 to 25 s
Flame ControlUV, ionization, or temperature (high-temp version)
Sensor Cable LengthMax. 100 m
Software InterfaceBCSoft (via optical interface)
Display Type2-digit 7-segment display for program status and flame signal
Fieldbus InterfacePROFIBUS DP via PFA 700
Start-up Attempts1 to 4
Restart AttemptsUp to 3 (configurable)
Air Valve ControlIntegrated (PFU..L variant)
Enclosure RatingIP00 (IP20 when installed in module subrack)
Sensor Voltage~230 V AC
Mains VoltagePFU..N: 110/120 VAC; PFU..T: 220/240 VAC
Altitude Limit< 2000 m AMSL
ApplicationsPFU 760: Directly ignited burners; intermittent or continuous operation; PFU 780: Pilot + main burners, intermittent or continuous operation
Manual ModeAvailable for commissioning and diagnostics
Dimensions133.4 mm H x 40.6 mm W
ApprovalsSIL 3 (EN 61508), EN 298:2012, FM Approved PFU..T variant only; NFPA 86 Compliant, AGA Approved, UKCA Certified, Eurasian Customs Union
Safety time on start-up3, 5 or 10 s
Safety time during operation1 or 2 s

Values retain manufacturer model qualifications. Review Honeywell specifications ↗

Part Number

Published part numbers

10 parts

Part NumberDescriptionEnquiry
KS88650271PFU760LTK1Request quotation
KS88650272PFU760LTDRequest quotation
KS88650273PFU760LTRequest quotation
KS88650274PFU760LTRequest quotation
KS88650275PFU760LTRequest quotation
KS88650276PFU760LTRequest quotation
KS88650277PFU760LTRequest quotation
KS88650278PFU760LTRequest quotation
KS88650279PFU780LTRequest quotation
KS88650280PFU780LTUK2Request quotation
Manufacturer sources

https://process.honeywell.com/us/en/products/thermal-solutions/burner-management-systems/burner-control-units/automatic-burner-control-units-pfu

Last source check: 2026-11-02

Burner control unit · Manufacturer ownership retained; republication licence not independently confirmed

ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.

Your next project. A clear starting point.

Tell us about your facility and what you need to achieve.