Burner Control Units
BCU 4 (Next Generation)
Next-generation BCU 4 controllers bring burner sequencing, ignition, manual operation and status indication together near the burner.
Next-generation BCU 4 controllers bring burner sequencing, ignition, manual operation and status indication together near the burner. A parameter card and replaceable power module support servicing. Air control, valve proving and high-temperature functions are variant-specific; the source identifies some communications and approvals as still in preparation.
Features & Benefits
- Altitude Limit
- < 2000 m AMSL
- Software Interface
- BCSoft (Windows-based engineering tool)
- Operation Modes
- BCU 480/BCU 460: Intermittent and continuous, BCU 465: Intermittent and continuous + flameless mode
- High-Temperature Operation
- Yes (>750 deg C)
- Flame Control
- BCU 480/BCU 460: UV sensor (UVS/UVC), ionization, or temperature-based (HT mode), BCU 465: Intermittent and continuous + flameless mode
- Fieldbus Communication
- PROFIBUS, PROFINET, EtherNet/IP, Modbus TCP via BCM 400 module
- Enclosure Rating
- IP20 (BCM module)
- Display Type
- 4-digit 7-segment LED display
- Compatible Burner Types
- Single-stage, Two-stage, Modulating, Pilot/main, Flameless Operation Burners
- Approvals
- SIL 3 Capability per EN 61508, PL e per ISO 13849, EU Directives: LVD 2014/35/EU, EMC 2014/30/EU, GAR 2016/426, EN 13611, EN 1854 Compliance, FM Approved (FM 7610), ANSI/CSA, UKCA (460/465), Eurasian Customs Union compliance
- Ambient Temperature Range
- -20 to +70 deg C (-4 to +158 deg F)|No condensation allowed
- The parameter card simplifies transferring settings during replacement.
- A separate power module allows wear components to be replaced.
Applications
- Industrial gas-burner control near the burner
Detailed capabilities
Configuration-specific functions and approval status
The four-digit display, parameter card and replaceable power section support setup and service. Capacity control targets frequent cycling. Semiconductor air-valve output belongs to the stated F3 variant, valve proving to C1 and high-temperature operation to the named Dx arrangements. The page calls CSA/AGA approvals and protective-bus communication 'in preparation'; those are not current approvals or available functions merely because EU/FM/EAC and SIL/PL statements also appear.
Features and benefits
- The parameter card simplifies transferring settings during replacement.
- A separate power module allows wear components to be replaced.
Published application context
- Industrial gas-burner control near the burner
Operating Limits, Durability & Lifecycle
- Altitude Limit
- < 2000 m AMSL
Control, Software & User Interface Specifications
- Software Interface
- BCSoft (Windows-based engineering tool)
- Display Type
- 4-digit 7-segment LED display
Control, Logic & Functional Behavior
- Operation Modes
- BCU 480/BCU 460: Intermittent and continuous, BCU 465: Intermittent and continuous + flameless mode
Overview
- Models
- BCU 460, BCU 465, BCU 480
Maximum/Minimum Temperature Limits
- High-Temperature Operation
- Yes (>750 deg C)
Ignition, Flame & Supervision Specifications
- Flame Control
- BCU 480/BCU 460: UV sensor (UVS/UVC), ionization, or temperature-based (HT mode), BCU 465: Intermittent and continuous + flameless mode
Communication & Interfaces
- Fieldbus Communication
- PROFIBUS, PROFINET, EtherNet/IP, Modbus TCP via BCM 400 module
Environmental Conditions
- Enclosure Rating
- IP20 (BCM module)
- Ambient Temperature Range
- -20 to +70 deg C (-4 to +158 deg F); No condensation allowed
Applications & Compatibility
- Compatible Burner Types
- Single-stage, Two-stage, Modulating, Pilot/main, Flameless Operation Burners
- Applications
- BCU 480: Multi‑burner, pilot + main burner, industrial furnaces; BCU 460: General industrial burners; BCU 465: High‑velocity burners, Low‑NOx flameless combustion
Standards & Certifications
- Approvals
- SIL 3 Capability per EN 61508, PL e per ISO 13849, EU Directives: LVD 2014/35/EU, EMC 2014/30/EU, GAR 2016/426, EN 13611, EN 1854 Compliance, FM Approved (FM 7610), ANSI/CSA, UKCA (460/465), Eurasian Customs Union compliance
| Parameter | Published value / configuration |
|---|---|
| Altitude Limit | < 2000 m AMSL |
| Software Interface | BCSoft (Windows-based engineering tool) |
| Display Type | 4-digit 7-segment LED display |
| Operation Modes | BCU 480/BCU 460: Intermittent and continuous, BCU 465: Intermittent and continuous + flameless mode |
| Models | BCU 460, BCU 465, BCU 480 |
| High-Temperature Operation | Yes (>750 deg C) |
| Flame Control | BCU 480/BCU 460: UV sensor (UVS/UVC), ionization, or temperature-based (HT mode), BCU 465: Intermittent and continuous + flameless mode |
| Fieldbus Communication | PROFIBUS, PROFINET, EtherNet/IP, Modbus TCP via BCM 400 module |
| Enclosure Rating | IP20 (BCM module) |
| Ambient Temperature Range | -20 to +70 deg C (-4 to +158 deg F); No condensation allowed |
| Compatible Burner Types | Single-stage, Two-stage, Modulating, Pilot/main, Flameless Operation Burners |
| Applications | BCU 480: Multi‑burner, pilot + main burner, industrial furnaces; BCU 460: General industrial burners; BCU 465: High‑velocity burners, Low‑NOx flameless combustion |
| Approvals | SIL 3 Capability per EN 61508, PL e per ISO 13849, EU Directives: LVD 2014/35/EU, EMC 2014/30/EU, GAR 2016/426, EN 13611, EN 1854 Compliance, FM Approved (FM 7610), ANSI/CSA, UKCA (460/465), Eurasian Customs Union compliance |
Values retain manufacturer model qualifications. Review Honeywell specifications ↗
Part Number
Published part numbers
10 parts
| Part Number | Description | Enquiry |
|---|---|---|
| KS22804014 | Insulation 3-A -casing flue ga | Request quotation |
| KS74960689 | Ventilanschlusskabel TC /B | Request quotation |
| KS74966057 | Leistungsmodul BCU 4series Q F0 E1 O0 - | Request quotation |
| KS74966073 | Leistungsmodul BCU 4series Q F3 E0 O0 - | Request quotation |
| KS74966081 | Leistungsmodul LM400 Q F3 E1 O0 - | Request quotation |
| KS74966105 | Leistungsmodul BCU 4series W F3 E0 O0 - | Request quotation |
| KS74966113 | Leistungsmodul BCU 4series W F3 E1 O0 - | Request quotation |
| KS88610001 | BCU460 3/2WGBS2B1/1 | Request quotation |
| KS88610002 | BCU465 5/1LW3GBS3AB1/1 | Request quotation |
| KS88610003 | CTLR,BRNR,BCU 460 3/1LW3GBB1/1 | Request quotation |