Burner Control Units
Protective system control FCU
FCU centralizes protective functions for multi-burner industrial furnaces.
FCU centralizes protective functions for multi-burner industrial furnaces. Its valve-proving function checks leakage, while temperature monitoring or limiting supports high-temperature equipment. A replaceable power module carries the safety outputs. The published approval coverage includes variant qualifications, with CSA specifically associated with FCU..H0.
Features & Benefits
- Actuator Type
- IC20, IC40, RBW three‑point step, frequency converter fan control (via terminals 53-56)
- Valve Type
- V1, V2, V3, relief valve configuration options as per tightness test scenario (parameters 52-53)
- Timing Adjustments
- tGV (fan run‑up), tPV (pre‑purge), tPN (post‑purge), tRF (enable delay), tMP (min pause), tE (switch‑on delay), tL1/tL2 (valve opening), tM (measurement time)
- Temperature Monitoring
- STM (≥750 deg C high temp mode), STL/FSTL (max furnace temp 200-1600 deg C), double thermocouple Types K, N, S only (H1 versions)
- Safety Level
- SIL 3 (EN 61508), PL e (ISO 13849) Certified
- Program Sequences
- Startup, Safety Interlock Checks, Pre‑Purge, Airflow Monitoring, Tightness Test, Ignition Enable, Operation, Post‑Purge
- Product Type
- Protective system control for monitoring and controlling central safety functions in multi‑burner furnace systems
- Power Supply
- 120 VAC (Q), 230 VAC (W); 24 VDC control voltage ±10%
- Parameter Storage
- Replaceable parameter chip card; settings transferable across units with identical type code
- Outputs
- AC/24VDC - Gas valves V1(13), V2(14), V3(15), LDS start limits (16), Purge (17), High Temp (18), Fault 24V (41), Operation 24V (42), Capacity control (53-56), Fan (58), Safety interlock (57)
- Installation Type
- DIN‑rail mount 35 x 7.5 mm, control cabinet ≥IP54, no condensation allowed
- Input Capacity
- 24 VDC - Start (1), Controlled air flow (2), Remote reset (3), Burner operation (4), Fan ready (44), VPS/POC (45), Emergency stop (46), Air min (47), Air flow (48), Gas min (49), Gas max (50), Programmable inputs (51,65,66,67,68)
- Environmental Rating
- Cabinet IP54; OCU faceplate IP65|Operating -20 to +60 deg C
- Communication Options
- PROFINET/Modbus TCP via BCM 500 module; cyclic and acyclic data (status, faults, remaining times, STM/STL temps)
- Approvals
- FM Approved, EU‑GAR 2016/426, EMC 2014/30/EU, LVD 2014/35/EU, ANSI/CSA Z21.20; Eurasian CU approval
- Replacing the output power module supports a longer service life.
Applications
- Central safety functions in multi-burner industrial furnaces
Actuation, Valve & Motion Control Specifications
- Actuator Type
- IC20, IC40, RBW three‑point step, frequency converter fan control (via terminals 53-56)
- Valve Type
- V1, V2, V3, relief valve configuration options as per tightness test scenario (parameters 52-53)
Control, Safety & Functional Behavior
- Timing Adjustments
- tGV (fan run‑up), tPV (pre‑purge), tPN (post‑purge), tRF (enable delay), tMP (min pause), tE (switch‑on delay), tL1/tL2 (valve opening), tM (measurement time)
Temperature Control/Measurement
- Temperature Monitoring
- STM (≥750 deg C high temp mode), STL/FSTL (max furnace temp 200-1600 deg C), double thermocouple Types K, N, S only (H1 versions)
Standards & Certifications
- Safety Level
- SIL 3 (EN 61508), PL e (ISO 13849) Certified
- Approvals
- FM Approved, EU‑GAR 2016/426, EMC 2014/30/EU, LVD 2014/35/EU, ANSI/CSA Z21.20; Eurasian CU approval
Control, Software & User Interface Specifications
- Program Sequences
- Startup, Safety Interlock Checks, Pre‑Purge, Airflow Monitoring, Tightness Test, Ignition Enable, Operation, Post‑Purge
Overview
- Product Type
- Protective system control for monitoring and controlling central safety functions in multi‑burner furnace systems
- Models
- FCU 500 (central control), FCU 505 (zone control)
Electrical Specifications
- Power Supply
- 120 VAC (Q), 230 VAC (W); 24 VDC control voltage ±10%
Software, Configuration & Cyber
- Parameter Storage
- Replaceable parameter chip card; settings transferable across units with identical type code
Inputs, Outputs & Signal Interfaces
- Outputs
- AC/24VDC - Gas valves V1(13), V2(14), V3(15), LDS start limits (16), Purge (17), High Temp (18), Fault 24V (41), Operation 24V (42), Capacity control (53-56), Fan (58), Safety interlock (57)
Installation & Mounting Specifications
- Installation Type
- DIN‑rail mount 35 x 7.5 mm, control cabinet ≥IP54, no condensation allowed
Performance Specifications
- Input Capacity
- 24 VDC - Start (1), Controlled air flow (2), Remote reset (3), Burner operation (4), Fan ready (44), VPS/POC (45), Emergency stop (46), Air min (47), Air flow (48), Gas min (49), Gas max (50), Programmable inputs (51,65,66,67,68)
Environmental Conditions
- Environmental Rating
- Cabinet IP54; OCU faceplate IP65; Operating -20 to +60 deg C
Communication & Interfaces
- Communication Options
- PROFINET/Modbus TCP via BCM 500 module; cyclic and acyclic data (status, faults, remaining times, STM/STL temps)
Applications & Compatibility
- Applications
- Gas min./max., air min., pre‑purge, tightness test, temperature monitoring, burner start enable, zone capacity control
| Parameter | Published value / configuration |
|---|---|
| Actuator Type | IC20, IC40, RBW three‑point step, frequency converter fan control (via terminals 53-56) |
| Valve Type | V1, V2, V3, relief valve configuration options as per tightness test scenario (parameters 52-53) |
| Timing Adjustments | tGV (fan run‑up), tPV (pre‑purge), tPN (post‑purge), tRF (enable delay), tMP (min pause), tE (switch‑on delay), tL1/tL2 (valve opening), tM (measurement time) |
| Temperature Monitoring | STM (≥750 deg C high temp mode), STL/FSTL (max furnace temp 200-1600 deg C), double thermocouple Types K, N, S only (H1 versions) |
| Safety Level | SIL 3 (EN 61508), PL e (ISO 13849) Certified |
| Approvals | FM Approved, EU‑GAR 2016/426, EMC 2014/30/EU, LVD 2014/35/EU, ANSI/CSA Z21.20; Eurasian CU approval |
| Program Sequences | Startup, Safety Interlock Checks, Pre‑Purge, Airflow Monitoring, Tightness Test, Ignition Enable, Operation, Post‑Purge |
| Product Type | Protective system control for monitoring and controlling central safety functions in multi‑burner furnace systems |
| Models | FCU 500 (central control), FCU 505 (zone control) |
| Power Supply | 120 VAC (Q), 230 VAC (W); 24 VDC control voltage ±10% |
| Parameter Storage | Replaceable parameter chip card; settings transferable across units with identical type code |
| Outputs | AC/24VDC - Gas valves V1(13), V2(14), V3(15), LDS start limits (16), Purge (17), High Temp (18), Fault 24V (41), Operation 24V (42), Capacity control (53-56), Fan (58), Safety interlock (57) |
| Installation Type | DIN‑rail mount 35 x 7.5 mm, control cabinet ≥IP54, no condensation allowed |
| Input Capacity | 24 VDC - Start (1), Controlled air flow (2), Remote reset (3), Burner operation (4), Fan ready (44), VPS/POC (45), Emergency stop (46), Air min (47), Air flow (48), Gas min (49), Gas max (50), Programmable inputs (51,65,66,67,68) |
| Environmental Rating | Cabinet IP54; OCU faceplate IP65; Operating -20 to +60 deg C |
| Communication Options | PROFINET/Modbus TCP via BCM 500 module; cyclic and acyclic data (status, faults, remaining times, STM/STL temps) |
| Applications | Gas min./max., air min., pre‑purge, tightness test, temperature monitoring, burner start enable, zone capacity control |
Values retain manufacturer model qualifications. Review Honeywell specifications ↗
Part Number
Published part numbers
10 parts
| Part Number | Description | Enquiry |
|---|---|---|
| KS74960666 | L-Modul FCU 500P/QF2 | Request quotation |
| KS88621000 | FCU500WC0F1H0K0-E | Request quotation |
| KS88621001 | FCU500WC0F0H0K2-E | Request quotation |
| KS88621002 | FCU500WC0F0H0K1-E | Request quotation |
| KS88621003 | FCU500WC0F0H0K1-E | Request quotation |
| KS88621004 | FCU500WC0F0H0K1-E | Request quotation |
| KS88621005 | FCU500WC0F1H0K2-E | Request quotation |
| KS88621006 | FCU500WC0F0H0K1-E | Request quotation |
| KS88621007 | FCU500WC1F0H0K2-E | Request quotation |
| KS88621008 | FCU500WC0F0H0K0-E | Request quotation |