Protective system control FCU

FCU centralizes protective functions for multi-burner industrial furnaces.

FCU centralizes protective functions for multi-burner industrial furnaces. Its valve-proving function checks leakage, while temperature monitoring or limiting supports high-temperature equipment. A replaceable power module carries the safety outputs. The published approval coverage includes variant qualifications, with CSA specifically associated with FCU..H0.

Features & Benefits

Actuator Type
IC20, IC40, RBW three‑point step, frequency converter fan control (via terminals 53-56)
Valve Type
V1, V2, V3, relief valve configuration options as per tightness test scenario (parameters 52-53)
Timing Adjustments
tGV (fan run‑up), tPV (pre‑purge), tPN (post‑purge), tRF (enable delay), tMP (min pause), tE (switch‑on delay), tL1/tL2 (valve opening), tM (measurement time)
Temperature Monitoring
STM (≥750 deg C high temp mode), STL/FSTL (max furnace temp 200-1600 deg C), double thermocouple Types K, N, S only (H1 versions)
Safety Level
SIL 3 (EN 61508), PL e (ISO 13849) Certified
Program Sequences
Startup, Safety Interlock Checks, Pre‑Purge, Airflow Monitoring, Tightness Test, Ignition Enable, Operation, Post‑Purge
Product Type
Protective system control for monitoring and controlling central safety functions in multi‑burner furnace systems
Power Supply
120 VAC (Q), 230 VAC (W); 24 VDC control voltage ±10%
Parameter Storage
Replaceable parameter chip card; settings transferable across units with identical type code
Outputs
AC/24VDC - Gas valves V1(13), V2(14), V3(15), LDS start limits (16), Purge (17), High Temp (18), Fault 24V (41), Operation 24V (42), Capacity control (53-56), Fan (58), Safety interlock (57)
Installation Type
DIN‑rail mount 35 x 7.5 mm, control cabinet ≥IP54, no condensation allowed
Input Capacity
24 VDC - Start (1), Controlled air flow (2), Remote reset (3), Burner operation (4), Fan ready (44), VPS/POC (45), Emergency stop (46), Air min (47), Air flow (48), Gas min (49), Gas max (50), Programmable inputs (51,65,66,67,68)
Environmental Rating
Cabinet IP54; OCU faceplate IP65|Operating -20 to +60 deg C
Communication Options
PROFINET/Modbus TCP via BCM 500 module; cyclic and acyclic data (status, faults, remaining times, STM/STL temps)
Approvals
FM Approved, EU‑GAR 2016/426, EMC 2014/30/EU, LVD 2014/35/EU, ANSI/CSA Z21.20; Eurasian CU approval
  • Replacing the output power module supports a longer service life.

Applications

  • Central safety functions in multi-burner industrial furnaces

Specifications

Actuation, Valve & Motion Control Specifications

Actuator Type
IC20, IC40, RBW three‑point step, frequency converter fan control (via terminals 53-56)
Valve Type
V1, V2, V3, relief valve configuration options as per tightness test scenario (parameters 52-53)

Control, Safety & Functional Behavior

Timing Adjustments
tGV (fan run‑up), tPV (pre‑purge), tPN (post‑purge), tRF (enable delay), tMP (min pause), tE (switch‑on delay), tL1/tL2 (valve opening), tM (measurement time)

Temperature Control/Measurement

Temperature Monitoring
STM (≥750 deg C high temp mode), STL/FSTL (max furnace temp 200-1600 deg C), double thermocouple Types K, N, S only (H1 versions)

Standards & Certifications

Safety Level
SIL 3 (EN 61508), PL e (ISO 13849) Certified
Approvals
FM Approved, EU‑GAR 2016/426, EMC 2014/30/EU, LVD 2014/35/EU, ANSI/CSA Z21.20; Eurasian CU approval

Control, Software & User Interface Specifications

Program Sequences
Startup, Safety Interlock Checks, Pre‑Purge, Airflow Monitoring, Tightness Test, Ignition Enable, Operation, Post‑Purge

Overview

Product Type
Protective system control for monitoring and controlling central safety functions in multi‑burner furnace systems
Models
FCU 500 (central control), FCU 505 (zone control)

Electrical Specifications

Power Supply
120 VAC (Q), 230 VAC (W); 24 VDC control voltage ±10%

Software, Configuration & Cyber

Parameter Storage
Replaceable parameter chip card; settings transferable across units with identical type code

Inputs, Outputs & Signal Interfaces

Outputs
AC/24VDC - Gas valves V1(13), V2(14), V3(15), LDS start limits (16), Purge (17), High Temp (18), Fault 24V (41), Operation 24V (42), Capacity control (53-56), Fan (58), Safety interlock (57)

Installation & Mounting Specifications

Installation Type
DIN‑rail mount 35 x 7.5 mm, control cabinet ≥IP54, no condensation allowed

Performance Specifications

Input Capacity
24 VDC - Start (1), Controlled air flow (2), Remote reset (3), Burner operation (4), Fan ready (44), VPS/POC (45), Emergency stop (46), Air min (47), Air flow (48), Gas min (49), Gas max (50), Programmable inputs (51,65,66,67,68)

Environmental Conditions

Environmental Rating
Cabinet IP54; OCU faceplate IP65; Operating -20 to +60 deg C

Communication & Interfaces

Communication Options
PROFINET/Modbus TCP via BCM 500 module; cyclic and acyclic data (status, faults, remaining times, STM/STL temps)

Applications & Compatibility

Applications
Gas min./max., air min., pre‑purge, tightness test, temperature monitoring, burner start enable, zone capacity control
Protective system control FCU — manufacturer page values
ParameterPublished value / configuration
Actuator TypeIC20, IC40, RBW three‑point step, frequency converter fan control (via terminals 53-56)
Valve TypeV1, V2, V3, relief valve configuration options as per tightness test scenario (parameters 52-53)
Timing AdjustmentstGV (fan run‑up), tPV (pre‑purge), tPN (post‑purge), tRF (enable delay), tMP (min pause), tE (switch‑on delay), tL1/tL2 (valve opening), tM (measurement time)
Temperature MonitoringSTM (≥750 deg C high temp mode), STL/FSTL (max furnace temp 200-1600 deg C), double thermocouple Types K, N, S only (H1 versions)
Safety LevelSIL 3 (EN 61508), PL e (ISO 13849) Certified
ApprovalsFM Approved, EU‑GAR 2016/426, EMC 2014/30/EU, LVD 2014/35/EU, ANSI/CSA Z21.20; Eurasian CU approval
Program SequencesStartup, Safety Interlock Checks, Pre‑Purge, Airflow Monitoring, Tightness Test, Ignition Enable, Operation, Post‑Purge
Product TypeProtective system control for monitoring and controlling central safety functions in multi‑burner furnace systems
ModelsFCU 500 (central control), FCU 505 (zone control)
Power Supply120 VAC (Q), 230 VAC (W); 24 VDC control voltage ±10%
Parameter StorageReplaceable parameter chip card; settings transferable across units with identical type code
OutputsAC/24VDC - Gas valves V1(13), V2(14), V3(15), LDS start limits (16), Purge (17), High Temp (18), Fault 24V (41), Operation 24V (42), Capacity control (53-56), Fan (58), Safety interlock (57)
Installation TypeDIN‑rail mount 35 x 7.5 mm, control cabinet ≥IP54, no condensation allowed
Input Capacity24 VDC - Start (1), Controlled air flow (2), Remote reset (3), Burner operation (4), Fan ready (44), VPS/POC (45), Emergency stop (46), Air min (47), Air flow (48), Gas min (49), Gas max (50), Programmable inputs (51,65,66,67,68)
Environmental RatingCabinet IP54; OCU faceplate IP65; Operating -20 to +60 deg C
Communication OptionsPROFINET/Modbus TCP via BCM 500 module; cyclic and acyclic data (status, faults, remaining times, STM/STL temps)
ApplicationsGas min./max., air min., pre‑purge, tightness test, temperature monitoring, burner start enable, zone capacity control

Values retain manufacturer model qualifications. Review Honeywell specifications ↗

Part Number

Published part numbers

10 parts

Part NumberDescriptionEnquiry
KS74960666L-Modul FCU 500P/QF2Request quotation
KS88621000FCU500WC0F1H0K0-ERequest quotation
KS88621001FCU500WC0F0H0K2-ERequest quotation
KS88621002FCU500WC0F0H0K1-ERequest quotation
KS88621003FCU500WC0F0H0K1-ERequest quotation
KS88621004FCU500WC0F0H0K1-ERequest quotation
KS88621005FCU500WC0F1H0K2-ERequest quotation
KS88621006FCU500WC0F0H0K1-ERequest quotation
KS88621007FCU500WC1F0H0K2-ERequest quotation
KS88621008FCU500WC0F0H0K0-ERequest quotation
Manufacturer sources

https://process.honeywell.com/us/en/products/thermal-solutions/burner-management-systems/burner-control-units/protective-system-control-fcu

Last source check: 2026-11-02

Protective System Control · Manufacturer ownership retained; republication licence not independently confirmed

ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.