Burner Control Units

Kromschroeder IFD 258 burner control unit

IFD 258 controls gas-burner ignition and flame supervision with an adjustable detection threshold.

IFD 258 controls gas-burner ignition and flame supervision with an adjustable detection threshold. The response to flame loss can be switched between restart and immediate lockout. A display reports operating sequence and flame strength; the manufacturer distinguishes continuous ionization supervision from the available UV sensing arrangement.

Features & Benefits

Approvals
EN 298, Machinery Directive 2006/42/EC, Gas Appliances Directive, Low Voltage Directive, EMC Directive; AGA, FM, CSA, GOST‑R approvals
Start-up Sequence Controls
Waiting time tW, flame simulation check, safety time tSA, ignition time tZ; lockout if flame not detected within tSA
Start-up Safety Time
Selectable: 3, 5, or 10 seconds (model dependent)
Sensor Cable Length
Ionization: max 75 m; UV sensor: max 100 m; ignition cable: up to 5 m (IFD 258)/1 m (IFD 258..I)
Safety Time During Operation
Default 1 seconds, optional 2 seconds, must not exceed 3 seconds as per EN 746-2
Restart/Lockout Behavior
Switch‑selectable: immediate fault lockout or one‑off restart on flame failure
Program Display
2‑digit 7‑segment display for program status, flame signal, and fault codes (00, 01, 02, 04, 09, 10, 52, 53)
Permitted UV Sensors
Elster Kromschröder UVS 1, 5, 6, 10 (-40 to +80 deg C)
Outputs
Ignition: max 2 A; Valve output: max 1 A; Signaling contacts: max 2 A at 253 VAC
Operating Cycles
Control unit: 250,000 cycles; Reset and mains buttons: 1000 cycles each
Mains Voltage
100 V, 120 V, 200 V, 230 VAC (-15%/+10%), 50/60 Hz
Ignition Type
External ignition transformer (IFD 258) or integrated ignition (IFD 258..I) with 22 kVpp ignition voltage and 25 mA current
Ignition Time
Approximately 2, 3, or 6 seconds depending on model configuration
Flame Monitoring
Ionization sensor or UV sensor (UVS); UV mode only for intermittent operation; signal range 0-25 µA; detection ≥ 2 µA
Environmental Conditions
-20 to +60 deg C (-4 to +140 deg F)|Overvoltage category III, no condensation
Device Type
Automatic burner control unit for directly ignited industrial gas burners in continuous operation
Capacity Range
Unlimited capacity burners (atmospheric or forced-draught)
Body Material
Impact‑resistant plastic housing
Safety time on start-up
10 s

Applications

  • Gas-burner ignition and flame supervision

Specifications

Standards & Certifications

Approvals
EN 298, Machinery Directive 2006/42/EC, Gas Appliances Directive, Low Voltage Directive, EMC Directive; AGA, FM, CSA, GOST‑R approvals

Control, Logic & Functional Behavior

Start-up Sequence Controls
Waiting time tW, flame simulation check, safety time tSA, ignition time tZ; lockout if flame not detected within tSA

Control, Safety & Timing Characteristics

Start-up Safety Time
Selectable: 3, 5, or 10 seconds (model dependent)

Dimensions & Length Specifications

Sensor Cable Length
Ionization: max 75 m; UV sensor: max 100 m; ignition cable: up to 5 m (IFD 258)/1 m (IFD 258..I)

Safety, Protection & Reliability

Safety Time During Operation
Default 1 seconds, optional 2 seconds, must not exceed 3 seconds as per EN 746-2

Control, Logic & System Behavior

Restart/Lockout Behavior
Switch‑selectable: immediate fault lockout or one‑off restart on flame failure

Control, Software & User Interface Specifications

Program Display
2‑digit 7‑segment display for program status, flame signal, and fault codes (00, 01, 02, 04, 09, 10, 52, 53)

Ignition, Flame & Supervision Specifications

Permitted UV Sensors
Elster Kromschröder UVS 1, 5, 6, 10 (-40 to +80 deg C)
Ignition Type
External ignition transformer (IFD 258) or integrated ignition (IFD 258..I) with 22 kVpp ignition voltage and 25 mA current
Ignition Time
Approximately 2, 3, or 6 seconds depending on model configuration
Flame Monitoring
Ionization sensor or UV sensor (UVS); UV mode only for intermittent operation; signal range 0-25 µA; detection ≥ 2 µA

Inputs, Outputs & Signal Interfaces

Outputs
Ignition: max 2 A; Valve output: max 1 A; Signaling contacts: max 2 A at 253 VAC

Operating Limits, Durability & Lifecycle

Operating Cycles
Control unit: 250,000 cycles; Reset and mains buttons: 1000 cycles each

Electrical Specifications

Mains Voltage
100 V, 120 V, 200 V, 230 VAC (-15%/+10%), 50/60 Hz

Environmental Conditions

Environmental Conditions
-20 to +60 deg C (-4 to +140 deg F); Overvoltage category III, no condensation

Product Overview & Classification

Device Type
Automatic burner control unit for directly ignited industrial gas burners in continuous operation

Processing & Performance Metrics

Capacity Range
Unlimited capacity burners (atmospheric or forced-draught)

Material Specifications

Body Material
Impact‑resistant plastic housing

Technical Specifications

Safety time on start-up
10 s
Kromschroeder IFD 258 burner control unit — manufacturer page values
ParameterPublished value / configuration
ApprovalsEN 298, Machinery Directive 2006/42/EC, Gas Appliances Directive, Low Voltage Directive, EMC Directive; AGA, FM, CSA, GOST‑R approvals
Start-up Sequence ControlsWaiting time tW, flame simulation check, safety time tSA, ignition time tZ; lockout if flame not detected within tSA
Start-up Safety TimeSelectable: 3, 5, or 10 seconds (model dependent)
Sensor Cable LengthIonization: max 75 m; UV sensor: max 100 m; ignition cable: up to 5 m (IFD 258)/1 m (IFD 258..I)
Safety Time During OperationDefault 1 seconds, optional 2 seconds, must not exceed 3 seconds as per EN 746-2
Restart/Lockout BehaviorSwitch‑selectable: immediate fault lockout or one‑off restart on flame failure
Program Display2‑digit 7‑segment display for program status, flame signal, and fault codes (00, 01, 02, 04, 09, 10, 52, 53)
Permitted UV SensorsElster Kromschröder UVS 1, 5, 6, 10 (-40 to +80 deg C)
Ignition TypeExternal ignition transformer (IFD 258) or integrated ignition (IFD 258..I) with 22 kVpp ignition voltage and 25 mA current
Ignition TimeApproximately 2, 3, or 6 seconds depending on model configuration
Flame MonitoringIonization sensor or UV sensor (UVS); UV mode only for intermittent operation; signal range 0-25 µA; detection ≥ 2 µA
OutputsIgnition: max 2 A; Valve output: max 1 A; Signaling contacts: max 2 A at 253 VAC
Operating CyclesControl unit: 250,000 cycles; Reset and mains buttons: 1000 cycles each
Mains Voltage100 V, 120 V, 200 V, 230 VAC (-15%/+10%), 50/60 Hz
Environmental Conditions-20 to +60 deg C (-4 to +140 deg F); Overvoltage category III, no condensation
Device TypeAutomatic burner control unit for directly ignited industrial gas burners in continuous operation
Capacity RangeUnlimited capacity burners (atmospheric or forced-draught)
Body MaterialImpact‑resistant plastic housing
Safety time on start-up10 s

Values retain manufacturer model qualifications. Review Honeywell specifications ↗

Manufacturer sources

https://process.honeywell.com/us/en/products/thermal-solutions/burner-management-systems/burner-control-units/kromschroeder-ifd-258-burner-control-unit

Last source check: 2026-11-02

IFD 244 · Manufacturer ownership retained; republication licence not independently confirmed

ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.