Fire & Life Safety · Building Systems · Industrial Automation [email protected] +880 1347 561 256
Honeywell Process Measurement & Control

Burner Control Units

Kromschroeder BCU 400 burner control unit

BCU 400 integrates burner sequencing, ignition and operating indication in a metal enclosure.

BCU 400 integrates burner sequencing, ignition and operating indication in a metal enclosure. The family distinguishes directly ignited burners from pilot/main arrangements and offers model-specific air control. Ionization, UVS and UVD 1 sensing have different duty qualifications. An optical software interface sets the operating behavior.

Features & Benefits

Start-up Safety Time
3, 5 or 10 seconds
Safety Time During Operation
1 or 2 seconds
Mains Voltage
230 VAC or 115 VAC, for grounded or ungrounded mains
Safety time on start-up
3, 5 or 10 s

Applications

  • Directly ignited and pilot/main gas burners, according to BCU variant

Detailed capabilities

Choosing the BCU 400 subfamily

BCU 440 addresses ionization-supervised direct burners up to the published capacity. BCU 460 supports direct ignition without that stated limit and optional air-valve control, while BCU 465 extends air control and BCU 480 handles pilot/main burners. B1 denotes PROFIBUS DP. Single-electrode operation is possible, with UVS and UVD 1 having different duty qualifications; the optical software sets operating modes rather than making those sensor restrictions interchangeable.

Manufacturer reference ↗

Published application context

  • Directly ignited and pilot/main gas burners, according to BCU variant

Manufacturer reference ↗

Technical facts in the product overview

  • Safety time on start-up: 3, 5 or 10 s

Manufacturer reference ↗

Specifications

Control, Safety & Timing Characteristics

Start-up Safety Time
3, 5 or 10 seconds

Safety, Protection & Reliability

Safety Time During Operation
1 or 2 seconds

Electrical Specifications

Mains Voltage
230 VAC or 115 VAC, for grounded or ungrounded mains

Technical Specifications

Safety time on start-up
3, 5 or 10 s
Kromschroeder BCU 400 burner control unit — manufacturer page values
ParameterPublished value / configuration
Start-up Safety Time3, 5 or 10 seconds
Safety Time During Operation1 or 2 seconds
Mains Voltage230 VAC or 115 VAC, for grounded or ungrounded mains
Safety time on start-up3, 5 or 10 s

Values retain manufacturer model qualifications. Review Honeywell specifications ↗

Part Number

Published part numbers

7 parts

Part NumberDescriptionEnquiry
74960625PCO 200 including BCSoft CD-ROMRequest quotation
KS86601097Adapter Kit for BIC 140 ConnectionRequest quotation
KS88680262BCU460W3P2C0D0000K1E0-/LM400WF0O0E1-Request quotation
KS88680407BCU465W2P6C0D2010K1E1-/LM400WF3O0E1-Request quotation
KS88680867BCU460W1P2C0D0000K2E0-/LM400WF0O0E1-Request quotation
KS88681877BCU 460Q3P2C0D1000K1E0-/LM400QF0O0E1-Request quotation
KS88685918BCU460Q8P2C2D1000K1E1-/LM400QFRequest quotation
Manufacturer sources

https://process.honeywell.com/us/en/products/thermal-solutions/burner-management-systems/burner-control-units/kromschroeder-bcu-400-burner-control-unit

Last source check: 2026-11-02

Kromschroeder BCU 400 · Manufacturer ownership retained; republication licence not independently confirmed

ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.

Your next project. A clear starting point.

Tell us about your facility and what you need to achieve.