Fire & Life Safety · Building Systems · Industrial Automation [email protected] +880 1347 561 256
Honeywell Process Measurement & Control

Burner Control Units

Burner control unit BCU 570

BCU 570 mounts on a cabinet DIN rail to control, ignite and supervise individual or forced-draught burners.

BCU 570 mounts on a cabinet DIN rail to control, ignite and supervise individual or forced-draught burners. It also handles pressure supervision, valve proving and purge functions. Actuator control establishes the ignition position, while UV or ionization sensing supports the published intermittent and continuous operating modes.

Features & Benefits

Ambient Temperature Range
-20 to +60 deg C
Valve Output Rating
Max 1 A each, total max 2.5 A
Tightness Control
Integrated valve proving system (C1 variant), programmable test period
Software Interface
BCSoft (Windows), opto-adapter PCO 200
Signal Input
Start-Up, Controlled Air Flow, Remote Reset, Safety Interlock, Pressure Switches
Maximum Operating Cycles
Actuator: 250,000|Buttons: 10,000|Fault signal contact: 10,000
Manual Mode
Available; configurable operating time
Mains Voltage
120 VAC (Q), 230 VAC (W), ±15%, 50/60 Hz
Ignition Type
Direct or pilot burner ignition (intermittent or continuous operation)
Flame Signal Current
Ionization: 1-25 µA|UV: 1-35 µA
Flame Control
Flame rod, UVS (intermittent), UVC (continuous)
Fieldbus Interface
Optional BCM 500 module for PROFINET or Modbus TCP
Fan Output Rating
Max 3 A, start-up current max 6 A < 1 s
Enclosure Rating
IP20 (device), IP54 (installation cabinet), IP65 (OCU external)
Display Type
LED segment display with fault/status codes
Dimensions
110 x 100 x 102 mm
Control Output
Fan, ignition, gas valves V1-V4, actuator, controller enable
Approvals
EN 746‑2, EN 676, SIL up to 3, PL e Safety Standard, EU (LVD, EMC, GAR), ANSI/CSA, FM, UL, AGA, EAC

Applications

  • Individual and forced-draught burner control

Specifications

Environmental Conditions

Ambient Temperature Range
-20 to +60 deg C
Enclosure Rating
IP20 (device), IP54 (installation cabinet), IP65 (OCU external)

Actuation, Valve & Motion Control Specifications

Valve Output Rating
Max 1 A each, total max 2.5 A
Tightness Control
Integrated valve proving system (C1 variant), programmable test period

Control, Software & User Interface Specifications

Software Interface
BCSoft (Windows), opto-adapter PCO 200
Display Type
LED segment display with fault/status codes

Inputs, Outputs & Signal Interfaces

Signal Input
Start-Up, Controlled Air Flow, Remote Reset, Safety Interlock, Pressure Switches

Operating Limits & Resistance

Maximum Operating Cycles
Actuator: 250,000; Buttons: 10,000; Fault signal contact: 10,000

Control, Logic & Functional Behavior

Manual Mode
Available; configurable operating time
Control Output
Fan, ignition, gas valves V1-V4, actuator, controller enable

Electrical Specifications

Mains Voltage
120 VAC (Q), 230 VAC (W), ±15%, 50/60 Hz
Flame Signal Current
Ionization: 1-25 µA; UV: 1-35 µA

Ignition, Flame & Supervision Specifications

Ignition Type
Direct or pilot burner ignition (intermittent or continuous operation)
Flame Control
Flame rod, UVS (intermittent), UVC (continuous)

Communication & Interfaces

Fieldbus Interface
Optional BCM 500 module for PROFINET or Modbus TCP

Combustion Air, Blower & Emissions Specifications

Fan Output Rating
Max 3 A, start-up current max 6 A < 1 s

Dimensions & Weight

Dimensions
110 x 100 x 102 mm

Standards & Certifications

Approvals
EN 746‑2, EN 676, SIL up to 3, PL e Safety Standard, EU (LVD, EMC, GAR), ANSI/CSA, FM, UL, AGA, EAC

Applications & Compatibility

Applications
Controls, ignites, and monitors industrial burners (directly ignited or pilot‑ignited)
Burner control unit BCU 570 — manufacturer page values
ParameterPublished value / configuration
Ambient Temperature Range-20 to +60 deg C
Enclosure RatingIP20 (device), IP54 (installation cabinet), IP65 (OCU external)
Valve Output RatingMax 1 A each, total max 2.5 A
Tightness ControlIntegrated valve proving system (C1 variant), programmable test period
Software InterfaceBCSoft (Windows), opto-adapter PCO 200
Display TypeLED segment display with fault/status codes
Signal InputStart-Up, Controlled Air Flow, Remote Reset, Safety Interlock, Pressure Switches
Maximum Operating CyclesActuator: 250,000; Buttons: 10,000; Fault signal contact: 10,000
Manual ModeAvailable; configurable operating time
Control OutputFan, ignition, gas valves V1-V4, actuator, controller enable
Mains Voltage120 VAC (Q), 230 VAC (W), ±15%, 50/60 Hz
Flame Signal CurrentIonization: 1-25 µA; UV: 1-35 µA
Ignition TypeDirect or pilot burner ignition (intermittent or continuous operation)
Flame ControlFlame rod, UVS (intermittent), UVC (continuous)
Fieldbus InterfaceOptional BCM 500 module for PROFINET or Modbus TCP
Fan Output RatingMax 3 A, start-up current max 6 A < 1 s
Dimensions110 x 100 x 102 mm
ApprovalsEN 746‑2, EN 676, SIL up to 3, PL e Safety Standard, EU (LVD, EMC, GAR), ANSI/CSA, FM, UL, AGA, EAC
ApplicationsControls, ignites, and monitors industrial burners (directly ignited or pilot‑ignited)

Values retain manufacturer model qualifications. Review Honeywell specifications ↗

Part Number

Published part numbers

10 parts

Part NumberDescriptionEnquiry
1188567KROM BRNR CTL UNIT BCU 570+Request quotation
KS88660256BCU 570QC1F1U0K2-ERequest quotation
KS88660782BCU570WC1F2U0K1-ERequest quotation
KS88661053BCU570WC0F1U0K1-ERequest quotation
KS88661107BCU570WC1F1U0K2-ERequest quotation
KS88661182BCU570WC0F1U0K1-ERequest quotation
KS88661279BCU570WC0F1U0K1-ERequest quotation
KS88661291BCU570WC1F1U0K1-ERequest quotation
KS88661343BCU570WC1F1U0K1-ERequest quotation
KS88661345BCU570WC1F1U0K1-E 1Request quotation
Manufacturer sources

https://process.honeywell.com/us/en/products/thermal-solutions/burner-management-systems/burner-control-units/burner-control-unit-bcu-570

Last source check: 2026-11-02

Protective System Control · Manufacturer ownership retained; republication licence not independently confirmed

ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.

Your next project. A clear starting point.

Tell us about your facility and what you need to achieve.

CallSend enquiry