BCU 370 sequences ignition and supervises industrial forced-draught burners without a stated burner-capacity limit.

BCU 370 sequences ignition and supervises industrial forced-draught burners without a stated burner-capacity limit. It supports intermittent or continuous duty and either UV or ionization flame sensing. An external DL pressure switch checks combustion air during both pre-purge and operation; supply options are separately specified.

Features & Benefits

Ambient Temperature Range
-20 to +60 deg C (standard), -10 to +60 deg C (with ignition unit)
Maximum Operating Cycles
250000
Flame Signal Current
Ionization: 1-28 µA|UV: 1-35 µA
Valve Output Rating
Max 1 A each, total max 2.5 A
Software Interface
Optical interface with BCSoft PC software
Operating Altitude
< 2000 m AMSL
Fieldbus Interface
Optional PROFIBUS DP (B1), with three-point step control (B1-3)
Tightness Control
Optional (D3 variant), programmable test period
Start-up Attempts
1 to 4 (per parameter P07)
Fan Output Rating
Max 3 A, start-up current max 6.5 A < 1 s
Enclosure Rating
IP54 (IEC 529)
Mains Voltage
120 VAC (Q), 230 VAC (W), ±15%, 50/60 Hz
Ignition Type
Electronic ignition: I1 (single-pole), I2 (double-pole), I3 (double-pole with neutral)
Flame Control
UV Sensor or Flame Rod
Body Material
Impact‑resistant, heat‑resistant plastic
Display Type
2-digit 7-segment display
Output Load
Max 4 A
Approvals
EU DirectivesLow Voltage (2014/35/EU), EMC (2014/30/EU), GAR (2016/426), FMClass 7611, CSAClass 3335‑01/3335‑81, UL 372, AGA Approval No. 6880

Applications

  • Industrial forced-draught burner control

Specifications

Environmental Conditions

Ambient Temperature Range
-20 to +60 deg C (standard), -10 to +60 deg C (with ignition unit)
Enclosure Rating
IP54 (IEC 529)

Operating Limits & Resistance

Maximum Operating Cycles
250000

Electrical Specifications

Flame Signal Current
Ionization: 1-28 µA; UV: 1-35 µA
Mains Voltage
120 VAC (Q), 230 VAC (W), ±15%, 50/60 Hz

Actuation, Valve & Motion Control Specifications

Valve Output Rating
Max 1 A each, total max 2.5 A
Tightness Control
Optional (D3 variant), programmable test period

Control, Software & User Interface Specifications

Software Interface
Optical interface with BCSoft PC software
Display Type
2-digit 7-segment display

Operating Limits, Durability & Lifecycle

Operating Altitude
< 2000 m AMSL

Communication & Interfaces

Fieldbus Interface
Optional PROFIBUS DP (B1), with three-point step control (B1-3)

Control, Logic & System Behavior

Start-up Attempts
1 to 4 (per parameter P07)

Combustion Air, Blower & Emissions Specifications

Fan Output Rating
Max 3 A, start-up current max 6.5 A < 1 s

Ignition, Flame & Supervision Specifications

Ignition Type
Electronic ignition: I1 (single-pole), I2 (double-pole), I3 (double-pole with neutral)
Flame Control
UV Sensor or Flame Rod

Material Specifications

Body Material
Impact‑resistant, heat‑resistant plastic

Applications & Compatibility

Applications
Modulating, forced draught burners for gas (intermittent or continuous operation)

Inputs, Outputs & Signal Interfaces

Output Load
Max 4 A

Standards & Certifications

Approvals
EU DirectivesLow Voltage (2014/35/EU), EMC (2014/30/EU), GAR (2016/426), FMClass 7611, CSAClass 3335‑01/3335‑81, UL 372, AGA Approval No. 6880
Burner control unit BCU 370 — manufacturer page values
ParameterPublished value / configuration
Ambient Temperature Range-20 to +60 deg C (standard), -10 to +60 deg C (with ignition unit)
Enclosure RatingIP54 (IEC 529)
Maximum Operating Cycles250000
Flame Signal CurrentIonization: 1-28 µA; UV: 1-35 µA
Mains Voltage120 VAC (Q), 230 VAC (W), ±15%, 50/60 Hz
Valve Output RatingMax 1 A each, total max 2.5 A
Tightness ControlOptional (D3 variant), programmable test period
Software InterfaceOptical interface with BCSoft PC software
Display Type2-digit 7-segment display
Operating Altitude< 2000 m AMSL
Fieldbus InterfaceOptional PROFIBUS DP (B1), with three-point step control (B1-3)
Start-up Attempts1 to 4 (per parameter P07)
Fan Output RatingMax 3 A, start-up current max 6.5 A < 1 s
Ignition TypeElectronic ignition: I1 (single-pole), I2 (double-pole), I3 (double-pole with neutral)
Flame ControlUV Sensor or Flame Rod
Body MaterialImpact‑resistant, heat‑resistant plastic
ApplicationsModulating, forced draught burners for gas (intermittent or continuous operation)
Output LoadMax 4 A
ApprovalsEU DirectivesLow Voltage (2014/35/EU), EMC (2014/30/EU), GAR (2016/426), FMClass 7611, CSAClass 3335‑01/3335‑81, UL 372, AGA Approval No. 6880

Values retain manufacturer model qualifications. Review Honeywell specifications ↗

Part Number

Published part numbers

10 parts

Part NumberDescriptionEnquiry
613001QFLM SFGRD BCU370 230V w/CONFRequest quotation
KS88600001BCU370WI1FEU0D1Request quotation
KS88600002BCU370WI1FEU0D3Request quotation
KS88600003BCU370WI1FEU0D3Request quotation
KS88600004BCU370WI1FEU0D3Request quotation
KS88600005BCU370WI1FEU0D1Request quotation
KS88600006BCU370WI1FEU0D3Request quotation
KS88600007BCU370WI1FEU0D3Request quotation
KS88600008BCU370WI1FEU0D1Request quotation
KS88600009BCU370WI1FEU0D3Request quotation
Manufacturer sources

https://process.honeywell.com/us/en/products/thermal-solutions/burner-management-systems/burner-control-units/burner-control-unit-bcu-370

Last source check: 2026-11-02

Burner control unit · Manufacturer ownership retained; republication licence not independently confirmed

ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.

Your next project. A clear starting point.

Tell us about your facility and what you need to achieve.

CallSend enquiry