Smartlink/Smartfire
SMARTLINK® Meter
SMARTLINK METER derives mass flow from matched platinum temperature elements in a stainless probe.
SMARTLINK METER derives mass flow from matched platinum temperature elements in a stainless probe. Factory calibration and an inline flow-conditioning body support installation, while a local display, totalizer and analog I/O expose measurements. Linking two meters adds ratio observation, and redundant self-checking provides alarm and status outputs for supervisory integration.
Features & Benefits
- Sizes
- Natural Gas Models - 2, 3, 4, 6 in nominal sizes, Air Models - 8, 12, 16, 20, 24, 28 in nominal sizes
- Hazardous Location Approvals
- FM Approved: Class I and II Div 2; Class I Zone 2; ATEX/IECEx/UKCA
- Ambient Temperature Range
- -40 to +70 deg C (measurement)|LCD viewing -20 to +50 deg C
- Fluid Temperature Range
- -40 to +100 deg C
- Alarm and Event Logging
- On‑board alarm, limit indication, and event log
- Temperature Accuracy
- ±0.5 deg C
- Wetted Materials
- Probe: 316 SS; Flow body: Carbon Steel; Screens: 316 Stainless Steel
- Enclosure Rating
- IP66/NEMA 4X, 12, and 13
- Alarm Signaling
- NAMUR‑43 compatible 21.5 mA alarm output (configurable)
- Process Fluids
- Natural Gas, Air
- Analog Outputs
- Two isolated 4 to 20 mA outputs (Flow, Ratio or Temperature)
- Relay Outputs
- Three fail‑safe solid‑state relay drive outputs (Test, Alarm, Limit)
- Local Display
- 4‑line x 20‑character LCD with membrane keypad
- Flow Turndown
- 50:1
- Flow Accuracy
- <±2% additional installed error|±2% of reading over 5%-100% of flow range (20:1 turndown) [calibration stand]
- Analog Inputs
- One 4 to 20 mA input for external meter (ratio calculation)
- Product Type
- SMARTLINK® METER Digital Self‑checking Thermal Mass Flow Meter
- Power Supply
- 24 VDC standard|Optional 115/230 VAC (50/60 Hz)
- Approvals
- FM Class I, Div 2; Class I, Zone 2 IIC; Class II/III Div 1/2; ATEX II 3 G/D; UKCA; KCs (KTL); CCC; IP66
- Local configuration avoids a separate PC interface.
- Integrated flow conditioning reduces straight-pipe requirements.
Applications
- Air and natural-gas mass-flow measurement
- Air/fuel ratio monitoring with linked meters
Detailed capabilities
Thermal measurement principle
The probe contains two matched platinum RTDs. One senses the process temperature; electronics heat the other to maintain a fixed temperature difference above the fluid. The power needed to sustain that difference becomes the mass-flow measurement. The factory-calibrated inline body also conditions the velocity profile and positions the probe, reducing the installation uncertainties of an unconditioned insertion probe.
Local information and linked-meter functions
A display and membrane keypad provide local setup, instantaneous rate and accumulated flow without an external computer. Analog I/O can represent flow, fluid temperature or ratio-related information, and two electrically linked meters can display the air/fuel relationship. Redundant checks provide alarm, limit and test-status information. The meters are calibrated for the stated air or natural-gas service, with hazardous-location qualification associated with the published enclosure and approval configuration.
Features and benefits
- Local configuration avoids a separate PC interface.
- Integrated flow conditioning reduces straight-pipe requirements.
Published application context
- Air and natural-gas mass-flow measurement
- Air/fuel ratio monitoring with linked meters
Dimensions & Size Specifications
- Sizes
- Natural Gas Models - 2, 3, 4, 6 in nominal sizes, Air Models - 8, 12, 16, 20, 24, 28 in nominal sizes
Standards & Certifications
- Hazardous Location Approvals
- FM Approved: Class I and II Div 2; Class I Zone 2; ATEX/IECEx/UKCA
- Approvals
- FM Class I, Div 2; Class I, Zone 2 IIC; Class II/III Div 1/2; ATEX II 3 G/D; UKCA; KCs (KTL); CCC; IP66
Environmental Conditions
- Ambient Temperature Range
- -40 to +70 deg C (measurement); LCD viewing -20 to +50 deg C
- Enclosure Rating
- IP66/NEMA 4X, 12, and 13
Fluid/Media/Component Temperatures
- Fluid Temperature Range
- -40 to +100 deg C
Alarms, Diagnostics & Monitoring
- Alarm and Event Logging
- On‑board alarm, limit indication, and event log
Temperature Control/Measurement
- Temperature Accuracy
- ±0.5 deg C
Material Specifications
- Wetted Materials
- Probe: 316 SS; Flow body: Carbon Steel; Screens: 316 Stainless Steel
Alarms, Status & Diagnostics
- Alarm Signaling
- NAMUR‑43 compatible 21.5 mA alarm output (configurable)
Fuel, Gas & Media Specifications
- Process Fluids
- Natural Gas, Air
Inputs, Outputs & Signal Interfaces
- Analog Outputs
- Two isolated 4 to 20 mA outputs (Flow, Ratio or Temperature)
- Relay Outputs
- Three fail‑safe solid‑state relay drive outputs (Test, Alarm, Limit)
- Analog Inputs
- One 4 to 20 mA input for external meter (ratio calculation)
Control, Software & User Interface Specifications
- Local Display
- 4‑line x 20‑character LCD with membrane keypad
Processing & Performance Metrics
- Flow Turndown
- 50:1
Performance, Flow & Capacity
- Flow Accuracy
- <±2% additional installed error; ±2% of reading over 5%-100% of flow range (20:1 turndown) [calibration stand]
Overview
- Product Type
- SMARTLINK® METER Digital Self‑checking Thermal Mass Flow Meter
- Models
- Air: 0800 SLM (8 in), 1200 SLM (12 in), 1600 SLM (16 in), 2000 SLM (20 in), 2400 SLM (24 in), 2800 SLM (28 in); Natural Gas: 0200 SLM (2 in), 0300 SLM (3 in), 0400 SLM (4 in), 0600 SLM (6 in)
Electrical Specifications
- Power Supply
- 24 VDC standard; Optional 115/230 VAC (50/60 Hz)
Applications & Compatibility
- Applications
- Combustion air and gas flow measurement, air/fuel ratio monitoring, fuel usage tracking, emissions optimization
| Parameter | Published value / configuration |
|---|---|
| Sizes | Natural Gas Models - 2, 3, 4, 6 in nominal sizes, Air Models - 8, 12, 16, 20, 24, 28 in nominal sizes |
| Hazardous Location Approvals | FM Approved: Class I and II Div 2; Class I Zone 2; ATEX/IECEx/UKCA |
| Approvals | FM Class I, Div 2; Class I, Zone 2 IIC; Class II/III Div 1/2; ATEX II 3 G/D; UKCA; KCs (KTL); CCC; IP66 |
| Ambient Temperature Range | -40 to +70 deg C (measurement); LCD viewing -20 to +50 deg C |
| Enclosure Rating | IP66/NEMA 4X, 12, and 13 |
| Fluid Temperature Range | -40 to +100 deg C |
| Alarm and Event Logging | On‑board alarm, limit indication, and event log |
| Temperature Accuracy | ±0.5 deg C |
| Wetted Materials | Probe: 316 SS; Flow body: Carbon Steel; Screens: 316 Stainless Steel |
| Alarm Signaling | NAMUR‑43 compatible 21.5 mA alarm output (configurable) |
| Process Fluids | Natural Gas, Air |
| Analog Outputs | Two isolated 4 to 20 mA outputs (Flow, Ratio or Temperature) |
| Relay Outputs | Three fail‑safe solid‑state relay drive outputs (Test, Alarm, Limit) |
| Analog Inputs | One 4 to 20 mA input for external meter (ratio calculation) |
| Local Display | 4‑line x 20‑character LCD with membrane keypad |
| Flow Turndown | 50:1 |
| Flow Accuracy | <±2% additional installed error; ±2% of reading over 5%-100% of flow range (20:1 turndown) [calibration stand] |
| Product Type | SMARTLINK® METER Digital Self‑checking Thermal Mass Flow Meter |
| Models | Air: 0800 SLM (8 in), 1200 SLM (12 in), 1600 SLM (16 in), 2000 SLM (20 in), 2400 SLM (24 in), 2800 SLM (28 in); Natural Gas: 0200 SLM (2 in), 0300 SLM (3 in), 0400 SLM (4 in), 0600 SLM (6 in) |
| Power Supply | 24 VDC standard; Optional 115/230 VAC (50/60 Hz) |
| Applications | Combustion air and gas flow measurement, air/fuel ratio monitoring, fuel usage tracking, emissions optimization |
Values retain manufacturer model qualifications. Review Honeywell specifications ↗
Manufacturer sources
Last source check: 2026-11-02
SMARTLINK Meter · Manufacturer ownership retained; republication licence not independently confirmed
ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.