Smartlink/Smartfire
SMARTLINK® DS Intelligent Control Actuator Series
SMARTLINK DS provides continuous-duty positioning as a standalone actuator or directly coupled valve assembly.
SMARTLINK DS provides continuous-duty positioning as a standalone actuator or directly coupled valve assembly. Torque, power, display, brake and hazardous-location options configure the installation. Analog or Modbus communication reports position and health, while onboard diagnostics and temperature sensing monitor operation; precise positioning and life figures retain their published operating basis.
Features & Benefits
- Full Travel (no valve option)
- 100 deg maximum full travel span
- Hazardous Location Approvals
- FM: Non‑incendive Class I, Div 2, Groups A-D; Dust‑protected Class II/III, Div 1 and 2, Groups E-G; ATEX II 3 G Ex nA nC IIC T4 (-40 to +70 deg C), II 3 D Ex tc IIIC T135 deg C; IECEx Ex nA nC IIC T4/Ex tC IIIC T135 deg C; UKCA equivalent
- Operating Temperature Range
- -40 to +70 deg C (-40 to +158 deg F)
- Ambient Temperature Range
- -20 to 122 deg F (-29 to 50 deg C)
- Communication Protocols
- RS‑485 Modbus; default 19.2 kbps, even parity
- Air/Fuel Ratio Control
- ± 2% with turndown of 20:1
- Storage Temperature
- -40 to +80 deg C (-40 to +176 deg F)
- Position Resolution
- 0.1 deg or up to 1000 position points over full 100 deg span
- Brake Response Time
- ≤10 ms (on loss of power or torque exceedance)
- Enclosure Rating
- NEMA 4, 4X; IP67
- Life Expectancy
- 10,000,000 repositions over 10 deg span or 100,000,000 over full 100 deg span
- Feedback Output
- 4 to 20 mA isolated, self‑powered (275 Ω max including cable resistance)
- Torque Options
- 300 in-lb (33 Nm) or 900 in-lb (101 Nm)
- Supply Voltage
- 100 to 240 VAC ±10%, 50/60 Hz (0.2 A rms at 120 VAC)|24 VDC +5%/-20% (1.1 A max)
- Mounting Types
- Any orientation; multiple shaft and coupling options available
- Command Inputs
- 4 to 20 mA isolated (100 Ω burden)|RS‑485 Modbus
- Relay Outputs
- General use: 5 A at 120 VAC; 3 A at 250 VAC/24 VDC|Safety use: 1.5 A at 120 VAC/250 VAC/24 VDC
- Average Power
- AC: 19 W|DC: 17 W
- Power Supply
- 100 to 120 VAC at 2.5 A max, 50 to 60 Hz|200 to 240 VAC at 1.5 A max, 50 to 60 Hz
- Flow Control
- ± 1% of flow reading over a turndown of 20:1
- Display Type
- 2 LEDs (manual mode, alarm/lockout)|2x16 backlit LCD
- Valve Sizes
- Ball valves: 1/2 to 2 in|Butterfly valves: 1 to 18 in
- Travel Time
- 300 in-lb: 15 seconds; 900 in-lb: 45 seconds (100 deg span)
- Approvals
- FM; UL 353 and UL 1998; CSA C22.2; ATEX; IECEx; CE; UKCA; CCC
- Material
- Extruded and Cast Aluminum Housing; Powder‑coated
- Onboard health and temperature diagnostics support troubleshooting.
- Continuous-duty gearing does not require periodic lubrication.
Applications
- Combustion flow positioning
- General industrial process positioning
Detailed capabilities
Selecting the mechanical and electrical arrangement
DuraStep is offered as DSSA actuator-only, DSCA with mounting bracket, DSCV with butterfly valve or DSBV with ball valve, as well as selected burner-mounted packages. Two torque groups, AC/DC power, a local display, brake and hazardous-location options adapt the device. The standard general-purpose enclosure and the optional hazardous rating are different selections; installing the former does not establish the latter.
Position control, brake and diagnostics
Analog 4–20 mA and Modbus provide position demand, confirmation and health information. The optional shaft brake limits unwanted motion on loss of power or torque overload. Onboard checks assess alarms/lockout every 50 ms, while the source gives a slower approximate interval for external indication. Temperature sensors track internal conditions. Permanently lubricated planetary gears support fine positioning and the stated lifetime, which remains a manufacturer performance claim under the product's operating conditions.
Valve materials and commissioning routes
Direct-coupled butterfly/ball options provide several body materials, internal seals and connection formats for the specifically listed media. Separate linkages can adapt other equipment. Commissioning can use the local LCD, PC software or DCS programming, with dual conduit paths separating power and low-voltage wiring. The aluminum enclosure can mount in different orientations; actual chemical and oxygen compatibility follows the selected body and trim combination.
Features and benefits
- Onboard health and temperature diagnostics support troubleshooting.
- Continuous-duty gearing does not require periodic lubrication.
Published application context
- Combustion flow positioning
- General industrial process positioning
Actuation, Valve & Motion Control Specifications
- Full Travel (no valve option)
- 100 deg maximum full travel span
- Position Resolution
- 0.1 deg or up to 1000 position points over full 100 deg span
- Brake Response Time
- ≤10 ms (on loss of power or torque exceedance)
- Torque Options
- 300 in-lb (33 Nm) or 900 in-lb (101 Nm)
- Travel Time
- 300 in-lb: 15 seconds; 900 in-lb: 45 seconds (100 deg span)
Standards & Certifications
- Hazardous Location Approvals
- FM: Non‑incendive Class I, Div 2, Groups A-D; Dust‑protected Class II/III, Div 1 and 2, Groups E-G; ATEX II 3 G Ex nA nC IIC T4 (-40 to +70 deg C), II 3 D Ex tc IIIC T135 deg C; IECEx Ex nA nC IIC T4/Ex tC IIIC T135 deg C; UKCA equivalent
- Approvals
- FM; UL 353 and UL 1998; CSA C22.2; ATEX; IECEx; CE; UKCA; CCC
Operating/Process Temperature Ranges
- Operating Temperature Range
- -40 to +70 deg C (-40 to +158 deg F)
Environmental Conditions
- Ambient Temperature Range
- -20 to 122 deg F (-29 to 50 deg C)
- Enclosure Rating
- NEMA 4, 4X; IP67
Communication & Interfaces
- Communication Protocols
- RS‑485 Modbus; default 19.2 kbps, even parity
Air & Combustion Air Specifications
- Air/Fuel Ratio Control
- ± 2% with turndown of 20:1
Storage/Transport Temperatures
- Storage Temperature
- -40 to +80 deg C (-40 to +176 deg F)
Processing & Performance Metrics
- Life Expectancy
- 10,000,000 repositions over 10 deg span or 100,000,000 over full 100 deg span
Inputs, Outputs & Signal Interfaces
- Feedback Output
- 4 to 20 mA isolated, self‑powered (275 Ω max including cable resistance)
- Command Inputs
- 4 to 20 mA isolated (100 Ω burden); RS‑485 Modbus
- Relay Outputs
- General use: 5 A at 120 VAC; 3 A at 250 VAC/24 VDC; Safety use: 1.5 A at 120 VAC/250 VAC/24 VDC
Electrical Specifications
- Supply Voltage
- 100 to 240 VAC ±10%, 50/60 Hz (0.2 A rms at 120 VAC); 24 VDC +5%/-20% (1.1 A max)
- Average Power
- AC: 19 W; DC: 17 W
- Power Supply
- 100 to 120 VAC at 2.5 A max, 50 to 60 Hz; 200 to 240 VAC at 1.5 A max, 50 to 60 Hz
Installation & Mounting Specifications
- Mounting Types
- Any orientation; multiple shaft and coupling options available
Performance, Flow & Capacity
- Flow Control
- ± 1% of flow reading over a turndown of 20:1
Control, Software & User Interface Specifications
- Display Type
- 2 LEDs (manual mode, alarm/lockout); 2x16 backlit LCD
Applications & Compatibility
- Applications
- HVAC and air dampers; Industrial ovens, furnaces, and boilers; Oil and gas and chemical processing; Power generation; Pulp and paper, metals, and mining; Water/wastewater treatment
Dimensions & Size Specifications
- Valve Sizes
- Ball valves: 1/2 to 2 in; Butterfly valves: 1 to 18 in
Material Specifications
- Material
- Extruded and Cast Aluminum Housing; Powder‑coated
| Parameter | Published value / configuration |
|---|---|
| Full Travel (no valve option) | 100 deg maximum full travel span |
| Position Resolution | 0.1 deg or up to 1000 position points over full 100 deg span |
| Brake Response Time | ≤10 ms (on loss of power or torque exceedance) |
| Torque Options | 300 in-lb (33 Nm) or 900 in-lb (101 Nm) |
| Travel Time | 300 in-lb: 15 seconds; 900 in-lb: 45 seconds (100 deg span) |
| Hazardous Location Approvals | FM: Non‑incendive Class I, Div 2, Groups A-D; Dust‑protected Class II/III, Div 1 and 2, Groups E-G; ATEX II 3 G Ex nA nC IIC T4 (-40 to +70 deg C), II 3 D Ex tc IIIC T135 deg C; IECEx Ex nA nC IIC T4/Ex tC IIIC T135 deg C; UKCA equivalent |
| Approvals | FM; UL 353 and UL 1998; CSA C22.2; ATEX; IECEx; CE; UKCA; CCC |
| Operating Temperature Range | -40 to +70 deg C (-40 to +158 deg F) |
| Ambient Temperature Range | -20 to 122 deg F (-29 to 50 deg C) |
| Enclosure Rating | NEMA 4, 4X; IP67 |
| Communication Protocols | RS‑485 Modbus; default 19.2 kbps, even parity |
| Air/Fuel Ratio Control | ± 2% with turndown of 20:1 |
| Storage Temperature | -40 to +80 deg C (-40 to +176 deg F) |
| Life Expectancy | 10,000,000 repositions over 10 deg span or 100,000,000 over full 100 deg span |
| Feedback Output | 4 to 20 mA isolated, self‑powered (275 Ω max including cable resistance) |
| Command Inputs | 4 to 20 mA isolated (100 Ω burden); RS‑485 Modbus |
| Relay Outputs | General use: 5 A at 120 VAC; 3 A at 250 VAC/24 VDC; Safety use: 1.5 A at 120 VAC/250 VAC/24 VDC |
| Supply Voltage | 100 to 240 VAC ±10%, 50/60 Hz (0.2 A rms at 120 VAC); 24 VDC +5%/-20% (1.1 A max) |
| Average Power | AC: 19 W; DC: 17 W |
| Power Supply | 100 to 120 VAC at 2.5 A max, 50 to 60 Hz; 200 to 240 VAC at 1.5 A max, 50 to 60 Hz |
| Mounting Types | Any orientation; multiple shaft and coupling options available |
| Flow Control | ± 1% of flow reading over a turndown of 20:1 |
| Display Type | 2 LEDs (manual mode, alarm/lockout); 2x16 backlit LCD |
| Applications | HVAC and air dampers; Industrial ovens, furnaces, and boilers; Oil and gas and chemical processing; Power generation; Pulp and paper, metals, and mining; Water/wastewater treatment |
| Valve Sizes | Ball valves: 1/2 to 2 in; Butterfly valves: 1 to 18 in |
| Material | Extruded and Cast Aluminum Housing; Powder‑coated |
Values retain manufacturer model qualifications. Review Honeywell specifications ↗
Part Number
Published part numbers
10 parts
| Part Number | Description | Enquiry |
|---|---|---|
| 0050DSBV | .5" SMARTLINK DS BALL VALVE | Request quotation |
| 0050LDSCV | .5" DS Low Flow CV Valve | Request quotation |
| 0075DSBV | .75" SMARTLINK DS BALL VALVE | Request quotation |
| 0075LDSCV | .75" DS Low Flow CV Valve | Request quotation |
| 0075ULDSCV | .75" Undersize Port DS Low Flow CV Valve | Request quotation |
| 0100DSBV | 1" SMARTLINK DS BALL VALVE | Request quotation |
| 0100LDSCV | 1" DS Low Flow CV Valve | Request quotation |
| 0100SDSCV | 1" SMARTLINK DS BUTTERFLY VALVE | Request quotation |
| 0100ULDSCV | 1" Undersize Port DS Low Flow CV Valve | Request quotation |
| 0125DSBV | 1.25" SMARTLINK DS BALL VALVE | Request quotation |
Manufacturer sources
Last source check: 2026-11-02
SMARTLINK DS Intelligent Control Actuator Series · Manufacturer ownership retained; republication licence not independently confirmed
ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.
Your next project. A clear starting point.
Tell us about your facility and what you need to achieve.