Fire & Life Safety · Building Systems · Industrial Automation [email protected] +880 1347 561 256
Honeywell Process Measurement & Control

Self-Recuperative and Radiant Tube Burners

Tube Firing Burner

TFB tube-firing burners use an adjustable spiraling flame to improve transfer and temperature distribution along radiant or immersion tubes.

TFB tube-firing burners use an adjustable spiraling flame to improve transfer and temperature distribution along radiant or immersion tubes. The page covers 300,000–2,000,000 Btu/hr, low excess-air operation and broad ignition range. Eclipse Bayonet-Ultra recuperators can be added for heat recovery in a compatible tube arrangement.

Features & Benefits

Air Pressure Switch
Required for safety; detects insufficient air pressure
Safety Standards
NFPA 86 Compliant
Recuperator Type
Exhaust leg recuperator
Maximum Furnace Temperature
Up to 1850 deg F (application dependent)
Maximum Combustion Air Temperature
Up to 1000 deg F
Main Gas Shut-Off Valve Train
Must comply with NFPA; minimum: two shut-off valves
Ignition Type
Direct Spark Ignition
Heating Type
Indirect heating
Fuel Type
Natural Gas, Propane, Butane
Fuel Gross Heating Values
Natural Gas: 1,002 BTU/ft³, Propane: 2,572 BTU/ft³, Butane: 3,225 BTU/ft³
Flame Monitoring
Flame rod (TFB030 and TFB075), UV scanner (all models)
Efficiency
As low as 39% depending on furnace temperature (without Recuperator)|Up to 71% depending on furnace temperature (with Recuperator)
Control Method
Modulating control, High/Low control
Combustion Principle
Direct tube firing with controlled air/fuel mixing
Burner Type
Nozzle-mixing burner for tube firing applications
  • The spiraling flame increases tube transfer and temperature uniformity.

Applications

  • Radiant- and immersion-tube firing

Detailed capabilities

A long adjustable spiral inside the tube

TFB's nozzle creates an adjustable-length spiral that sweeps the tube surface, reducing the insulating gas-film layer. The intended result is more even tube temperature and improved transfer, supporting consistent process heating and tube life. Low excess-air firing, low inlet-pressure requirements and a broad ignition range are described. Bayonet-Ultra recovery can be paired with a suitable tube system rather than assumed present on every burner.

Manufacturer reference ↗

Features and benefits

  • The spiraling flame increases tube transfer and temperature uniformity.

Manufacturer reference ↗

Published application context

  • Radiant- and immersion-tube firing

Manufacturer reference ↗

Specifications

Air & Combustion Air Specifications

Air Pressure Switch
Required for safety; detects insufficient air pressure

Standards & Certifications

Safety Standards
NFPA 86 Compliant

Combustion, Fuel & Mixing Sub‑Systems

Recuperator Type
Exhaust leg recuperator

Overview

Models
TFB030, TFB075, TFB200
Burner Type
Nozzle-mixing burner for tube firing applications

Maximum/Minimum Temperature Limits

Maximum Furnace Temperature
Up to 1850 deg F (application dependent)

Combustion/Furnace/Chamber Temperatures

Maximum Combustion Air Temperature
Up to 1000 deg F

Actuation, Valve & Motion Control Specifications

Main Gas Shut-Off Valve Train
Must comply with NFPA; minimum: two shut-off valves

Ignition, Flame & Supervision Specifications

Ignition Type
Direct Spark Ignition
Flame Monitoring
Flame rod (TFB030 and TFB075), UV scanner (all models)

Thermal, Flow & Process Characteristics

Heating Type
Indirect heating

Fuel, Gas & Media Specifications

Fuel Type
Natural Gas, Propane, Butane

Combustion, Mixing & Fuel Dynamics

Fuel Gross Heating Values
Natural Gas: 1,002 BTU/ft³, Propane: 2,572 BTU/ft³, Butane: 3,225 BTU/ft³
Combustion Principle
Direct tube firing with controlled air/fuel mixing

Processing & Performance Metrics

Efficiency
As low as 39% depending on furnace temperature (without Recuperator); Up to 71% depending on furnace temperature (with Recuperator)

Control, Logic & Functional Behavior

Control Method
Modulating control, High/Low control

Applications & Compatibility

Applications
Radiant tube heating, immersion tube heating
Tube Firing Burner — manufacturer page values
ParameterPublished value / configuration
Air Pressure SwitchRequired for safety; detects insufficient air pressure
Safety StandardsNFPA 86 Compliant
Recuperator TypeExhaust leg recuperator
ModelsTFB030, TFB075, TFB200
Burner TypeNozzle-mixing burner for tube firing applications
Maximum Furnace TemperatureUp to 1850 deg F (application dependent)
Maximum Combustion Air TemperatureUp to 1000 deg F
Main Gas Shut-Off Valve TrainMust comply with NFPA; minimum: two shut-off valves
Ignition TypeDirect Spark Ignition
Flame MonitoringFlame rod (TFB030 and TFB075), UV scanner (all models)
Heating TypeIndirect heating
Fuel TypeNatural Gas, Propane, Butane
Fuel Gross Heating ValuesNatural Gas: 1,002 BTU/ft³, Propane: 2,572 BTU/ft³, Butane: 3,225 BTU/ft³
Combustion PrincipleDirect tube firing with controlled air/fuel mixing
EfficiencyAs low as 39% depending on furnace temperature (without Recuperator); Up to 71% depending on furnace temperature (with Recuperator)
Control MethodModulating control, High/Low control
ApplicationsRadiant tube heating, immersion tube heating

Values retain manufacturer model qualifications. Review Honeywell specifications ↗

Part Number

Published part numbers

10 parts

Part NumberDescriptionEnquiry
10001260-1EXT,SI,SPRK,SELF GNDG,1300MM LG,125MM ISRequest quotation
10034234PPST,0.5 IN.,NPT,STL SHL,ELECTROLYTICALLRequest quotation
10053512-1KIT,LIT,TB FRNG BRNR,TFB030,ENGRequest quotation
10053512-2KIT,LIT,TB FRNG BRNR,TFB075,ENGRequest quotation
10053512-3KIT,LIT,TB FRNG BRNR,TFB200,ENGRequest quotation
101017271CVR,REAR,TFB030,TFB075,BLK,HTRequest quotation
101017345CVR,REAR,TFB200,BLK,HTRequest quotation
1030RBK1030,1238 TOF REPLACEMENT BLOWER KITRequest quotation
13229GSKT,BKPLT,4.00 IN.,X 3.44 IN.,SQ,TFB 63Request quotation
13230GSKT,FLG,SQ,6.00 X 4.75 IN.,TFB63Request quotation
Manufacturer sources

https://process.honeywell.com/us/en/products/thermal-solutions/burners-and-heat-exchangers/self-recuperative-and-radiant-tube-burners/tube-firing-burner

Last source check: 2026-11-02

Tube Firing Burner Product Image · Manufacturer ownership retained; republication licence not independently confirmed

Tube Firing Burner Product Diagram 1 · Manufacturer ownership retained; republication licence not independently confirmed

Tube Firing Burner Product Diagram · Manufacturer ownership retained; republication licence not independently confirmed

ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.

Your next project. A clear starting point.

Tell us about your facility and what you need to achieve.

CallSend enquiry