Pilot Burners
Pilot burner ZAI
ZAI is a thermo pilot for atmospheric gas-burner ignition with the named IFS/IFD or PFS/PFD automatic controls.
ZAI is a thermo pilot for atmospheric gas-burner ignition with the named IFS/IFD or PFS/PFD automatic controls. The page specifies approximately 3 kW input using natural gas or propane. It describes the pilot/control pairing without providing a universal installation geometry or compatibility statement for unrelated burner-control families.
Features & Benefits
- Ambient Temperature Range
- -15 to +60 deg C
- Typical Pilot Sizing
- Recommended at 2 to 5 % of main burner capacity
- Product Category
- Ionization‑controlled pilot burner
- Mounting Options
- Two mounting holes on fastening lug
- Material
- Ignition head: galvanized steel; Retaining plate: galvanized steel
- Ionization Current
- ≥ 5 µA stable
- Intended Use
- Ionization-controlled pilot burner for safely igniting gas burners; 2-5% of main burner capacity
- Installation Orientation
- Any position ensuring reliable main burner ignition
- Inlet Pressure Limit
- NG ≤ 35 mbar; Coke/Town gas ≤ 30 mbar; LPG ≤ 60 mbar
- Ignition Type
- Direct spark ignition (5 kV ignition transformer)
- Gas Type
- Natural Gas, LPG, Coke Oven Gas, Town Gas
- Gas Nozzles
- 0.7 mm LPG nozzle (included)|1.8 mm nozzle for coke/town gas (Order No. 34472880)
- Gas Connections
- 8 mm tube; cone olive + cap screw for ZAI K
- Electrodes Included
- Spark electrode + flame rod
- Combustion Method
- Atmospheric pilot with excess air operation
- Capacity
- Approximately 1.8 to 3 kW
- Burner Design
- No flame tube; bare electrodes (optional protective tube available)
- Approvals
- EN 746‑2, RoHS, REACH, Eurasian Customs Union
Applications
- Atmospheric gas-burner ignition
Environmental Conditions
- Ambient Temperature Range
- -15 to +60 deg C
Combustion, Fuel & Mixing Sub‑Systems
- Typical Pilot Sizing
- Recommended at 2 to 5 % of main burner capacity
Overview
- Product Category
- Ionization‑controlled pilot burner
Installation & Mounting Specifications
- Mounting Options
- Two mounting holes on fastening lug
- Installation Orientation
- Any position ensuring reliable main burner ignition
Material Specifications
- Material
- Ignition head: galvanized steel; Retaining plate: galvanized steel
Electrical Specifications
- Ionization Current
- ≥ 5 µA stable
Applications & Compatibility
- Intended Use
- Ionization-controlled pilot burner for safely igniting gas burners; 2-5% of main burner capacity
- Applications
- Safe ignition of gas burners; can also operate as an independent burner
Pressure Specifications
- Inlet Pressure Limit
- NG ≤ 35 mbar; Coke/Town gas ≤ 30 mbar; LPG ≤ 60 mbar
Ignition, Flame & Supervision Specifications
- Ignition Type
- Direct spark ignition (5 kV ignition transformer)
- Electrodes Included
- Spark electrode + flame rod
Fuel, Gas & Media Specifications
- Gas Type
- Natural Gas, LPG, Coke Oven Gas, Town Gas
Combustion, Mixing & Fuel Dynamics
- Gas Nozzles
- 0.7 mm LPG nozzle (included); 1.8 mm nozzle for coke/town gas (Order No. 34472880)
Connections & Interfaces
- Gas Connections
- 8 mm tube; cone olive + cap screw for ZAI K
Combustion Design & Characteristics
- Combustion Method
- Atmospheric pilot with excess air operation
Performance Specifications
- Capacity
- Approximately 1.8 to 3 kW
Product Design & Configuration
- Burner Design
- No flame tube; bare electrodes (optional protective tube available)
Standards & Certifications
- Approvals
- EN 746‑2, RoHS, REACH, Eurasian Customs Union
| Parameter | Published value / configuration |
|---|---|
| Ambient Temperature Range | -15 to +60 deg C |
| Typical Pilot Sizing | Recommended at 2 to 5 % of main burner capacity |
| Product Category | Ionization‑controlled pilot burner |
| Mounting Options | Two mounting holes on fastening lug |
| Installation Orientation | Any position ensuring reliable main burner ignition |
| Material | Ignition head: galvanized steel; Retaining plate: galvanized steel |
| Ionization Current | ≥ 5 µA stable |
| Intended Use | Ionization-controlled pilot burner for safely igniting gas burners; 2-5% of main burner capacity |
| Applications | Safe ignition of gas burners; can also operate as an independent burner |
| Inlet Pressure Limit | NG ≤ 35 mbar; Coke/Town gas ≤ 30 mbar; LPG ≤ 60 mbar |
| Ignition Type | Direct spark ignition (5 kV ignition transformer) |
| Electrodes Included | Spark electrode + flame rod |
| Gas Type | Natural Gas, LPG, Coke Oven Gas, Town Gas |
| Gas Nozzles | 0.7 mm LPG nozzle (included); 1.8 mm nozzle for coke/town gas (Order No. 34472880) |
| Gas Connections | 8 mm tube; cone olive + cap screw for ZAI K |
| Combustion Method | Atmospheric pilot with excess air operation |
| Capacity | Approximately 1.8 to 3 kW |
| Burner Design | No flame tube; bare electrodes (optional protective tube available) |
| Approvals | EN 746‑2, RoHS, REACH, Eurasian Customs Union |
Values retain manufacturer model qualifications. Review Honeywell specifications ↗
Part Number
Published part numbers
2 parts
| Part Number | Description | Enquiry |
|---|---|---|
| KS84228010 | ZAI K Pilot Burner | Request quotation |
| KS84228020 | PILT BRNR,ZAI,NAT GAS/PROPANE | Request quotation |
Manufacturer sources
Last source check: 2026-11-02
Pilot Burner · Manufacturer ownership retained; republication licence not independently confirmed
ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.
Your next project. A clear starting point.
Tell us about your facility and what you need to achieve.