Fire & Life Safety · Building Systems · Industrial Automation [email protected] +880 1347 561 256
Honeywell Process Measurement & Control

Pilot Burners

Pilot Burner Q179A

Q179A combines an electric-spark pilot electrode, a flame-detection electrode and a third grounding/shielding electrode.

Q179A combines an electric-spark pilot electrode, a flame-detection electrode and a third grounding/shielding electrode. Burner tips and orifices address the listed natural, mixed, manufactured and LP gases. Electronic detection uses an R190 or similar device; the published approximate flame current applies specifically to the R190 relay arrangement.

Features & Benefits

Inlet Gas Pressure Range
2 to 8 in. WC
Flame Signal Voltage
Min. 1.25 VDC (Honeywell 7800 Series)
Electrical Connector
Rajah connectors (male and female)
Electrodes Included
Ignition electrode + flame electrode (Q179A1183: ignition only)
Temperature Rating
Flame/ignition electrodes 1750 deg F; ground shield 1300 deg F; pilot tip 1500 deg F
Flame Signal Range
Min. 2.0 µA flame current
Product Category
Electrically ignited gas pilot burner
Pilot Tip Styles
I-port, 45 deg I-port, 45 deg RH Ell, 45 deg LH Ell, T-port, Y-port, Large I-port
Mounting Options
Side-mounting holes + end-mounting ears
Inlet Connection
1/4 in compression coupling (factory installed)
Gas Consumption
Approximately 2 cu ft/hr
Flame Detection
Flame rectification via flame electrode (rod)
Orifice Sizes
Natural Gas 0.025 in; LP 0.013 in; T/Y-port 0.028 in
Ignition Type
Spark ignition electrode (requires 6,000 V grounded secondary transformer)
Electrode Gap
1/16 to 3/32 in
Product Type
Q179A Gas Pilot Burner Assembly
Burner Type
Primary aerated burner with stainless steel fins
Fuel Type
Natural gas (LP requires separate orifice)
Approvals
UL Listed, CSA certified, FM Approved, AGA Certified

Applications

  • Gas-pilot ignition and electronic flame detection

Specifications

Pressure Specifications

Inlet Gas Pressure Range
2 to 8 in. WC

Electrical Specifications

Flame Signal Voltage
Min. 1.25 VDC (Honeywell 7800 Series)

Connections & Interfaces

Electrical Connector
Rajah connectors (male and female)
Inlet Connection
1/4 in compression coupling (factory installed)

Ignition, Flame & Supervision Specifications

Electrodes Included
Ignition electrode + flame electrode (Q179A1183: ignition only)
Flame Signal Range
Min. 2.0 µA flame current
Flame Detection
Flame rectification via flame electrode (rod)
Ignition Type
Spark ignition electrode (requires 6,000 V grounded secondary transformer)
Electrode Gap
1/16 to 3/32 in

Temperature Control/Measurement

Temperature Rating
Flame/ignition electrodes 1750 deg F; ground shield 1300 deg F; pilot tip 1500 deg F

Overview

Product Category
Electrically ignited gas pilot burner
Product Type
Q179A Gas Pilot Burner Assembly
Burner Type
Primary aerated burner with stainless steel fins

Combustion, Fuel & Mixing Sub‑Systems

Pilot Tip Styles
I-port, 45 deg I-port, 45 deg RH Ell, 45 deg LH Ell, T-port, Y-port, Large I-port

Installation & Mounting Specifications

Mounting Options
Side-mounting holes + end-mounting ears

Combustion, Mixing & Fuel Dynamics

Gas Consumption
Approximately 2 cu ft/hr

Dimensions & Size Specifications

Orifice Sizes
Natural Gas 0.025 in; LP 0.013 in; T/Y-port 0.028 in

Applications & Compatibility

Applications
Gas pilot assembly using flame rectification to prove flame, Gas burners and gas‑pilot‑ignited oil burners

Fuel, Gas & Media Specifications

Fuel Type
Natural gas (LP requires separate orifice)

Standards & Certifications

Approvals
UL Listed, CSA certified, FM Approved, AGA Certified
Pilot Burner Q179A — manufacturer page values
ParameterPublished value / configuration
Inlet Gas Pressure Range2 to 8 in. WC
Flame Signal VoltageMin. 1.25 VDC (Honeywell 7800 Series)
Electrical ConnectorRajah connectors (male and female)
Inlet Connection1/4 in compression coupling (factory installed)
Electrodes IncludedIgnition electrode + flame electrode (Q179A1183: ignition only)
Flame Signal RangeMin. 2.0 µA flame current
Flame DetectionFlame rectification via flame electrode (rod)
Ignition TypeSpark ignition electrode (requires 6,000 V grounded secondary transformer)
Electrode Gap1/16 to 3/32 in
Temperature RatingFlame/ignition electrodes 1750 deg F; ground shield 1300 deg F; pilot tip 1500 deg F
Product CategoryElectrically ignited gas pilot burner
Product TypeQ179A Gas Pilot Burner Assembly
Burner TypePrimary aerated burner with stainless steel fins
Pilot Tip StylesI-port, 45 deg I-port, 45 deg RH Ell, 45 deg LH Ell, T-port, Y-port, Large I-port
Mounting OptionsSide-mounting holes + end-mounting ears
Gas ConsumptionApproximately 2 cu ft/hr
Orifice SizesNatural Gas 0.025 in; LP 0.013 in; T/Y-port 0.028 in
ApplicationsGas pilot assembly using flame rectification to prove flame, Gas burners and gas‑pilot‑ignited oil burners
Fuel TypeNatural gas (LP requires separate orifice)
ApprovalsUL Listed, CSA certified, FM Approved, AGA Certified

Values retain manufacturer model qualifications. Review Honeywell specifications ↗

Part Number

Published part numbers

10 parts

Part NumberDescriptionEnquiry
37356/520/URAJAH CONNECTOR FOR IGN ELECTRODE-Q179ARequest quotation
Q179A1001/UGAS PILOTRequest quotation
Q179A1035/UGAS PILOTRequest quotation
Q179A1050/UT PILOT TIPRequest quotation
Q179A1076/UGAS PILOTRequest quotation
Q179A1092/U45 DEG T PILOT TIPRequest quotation
Q179A1118/UGAS PILOTRequest quotation
Q179A1126/U1 PILOT TIP, FOR HIGH TEMPERATURE APPLRequest quotation
Q179A1183/UPILOT BURNER ASSYRequest quotation
Q179B1182/USAME AS Q179B1042 EXCEPT ORIFICE HAS .0Request quotation
Manufacturer sources

https://process.honeywell.com/us/en/products/thermal-solutions/burners-and-heat-exchangers/pilot-burners/pilot-burner-q179a

Last source check: 2026-11-02

Pilot Burner Q179A Image · Manufacturer ownership retained; republication licence not independently confirmed

ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.

Your next project. A clear starting point.

Tell us about your facility and what you need to achieve.

CallSend enquiry