Pilot Burners
Pilot Burner Q179A
Q179A combines an electric-spark pilot electrode, a flame-detection electrode and a third grounding/shielding electrode.
Q179A combines an electric-spark pilot electrode, a flame-detection electrode and a third grounding/shielding electrode. Burner tips and orifices address the listed natural, mixed, manufactured and LP gases. Electronic detection uses an R190 or similar device; the published approximate flame current applies specifically to the R190 relay arrangement.
Features & Benefits
- Inlet Gas Pressure Range
- 2 to 8 in. WC
- Flame Signal Voltage
- Min. 1.25 VDC (Honeywell 7800 Series)
- Electrical Connector
- Rajah connectors (male and female)
- Electrodes Included
- Ignition electrode + flame electrode (Q179A1183: ignition only)
- Temperature Rating
- Flame/ignition electrodes 1750 deg F; ground shield 1300 deg F; pilot tip 1500 deg F
- Flame Signal Range
- Min. 2.0 µA flame current
- Product Category
- Electrically ignited gas pilot burner
- Pilot Tip Styles
- I-port, 45 deg I-port, 45 deg RH Ell, 45 deg LH Ell, T-port, Y-port, Large I-port
- Mounting Options
- Side-mounting holes + end-mounting ears
- Inlet Connection
- 1/4 in compression coupling (factory installed)
- Gas Consumption
- Approximately 2 cu ft/hr
- Flame Detection
- Flame rectification via flame electrode (rod)
- Orifice Sizes
- Natural Gas 0.025 in; LP 0.013 in; T/Y-port 0.028 in
- Ignition Type
- Spark ignition electrode (requires 6,000 V grounded secondary transformer)
- Electrode Gap
- 1/16 to 3/32 in
- Product Type
- Q179A Gas Pilot Burner Assembly
- Burner Type
- Primary aerated burner with stainless steel fins
- Fuel Type
- Natural gas (LP requires separate orifice)
- Approvals
- UL Listed, CSA certified, FM Approved, AGA Certified
Applications
- Gas-pilot ignition and electronic flame detection
Pressure Specifications
- Inlet Gas Pressure Range
- 2 to 8 in. WC
Electrical Specifications
- Flame Signal Voltage
- Min. 1.25 VDC (Honeywell 7800 Series)
Connections & Interfaces
- Electrical Connector
- Rajah connectors (male and female)
- Inlet Connection
- 1/4 in compression coupling (factory installed)
Ignition, Flame & Supervision Specifications
- Electrodes Included
- Ignition electrode + flame electrode (Q179A1183: ignition only)
- Flame Signal Range
- Min. 2.0 µA flame current
- Flame Detection
- Flame rectification via flame electrode (rod)
- Ignition Type
- Spark ignition electrode (requires 6,000 V grounded secondary transformer)
- Electrode Gap
- 1/16 to 3/32 in
Temperature Control/Measurement
- Temperature Rating
- Flame/ignition electrodes 1750 deg F; ground shield 1300 deg F; pilot tip 1500 deg F
Overview
- Product Category
- Electrically ignited gas pilot burner
- Product Type
- Q179A Gas Pilot Burner Assembly
- Burner Type
- Primary aerated burner with stainless steel fins
Combustion, Fuel & Mixing Sub‑Systems
- Pilot Tip Styles
- I-port, 45 deg I-port, 45 deg RH Ell, 45 deg LH Ell, T-port, Y-port, Large I-port
Installation & Mounting Specifications
- Mounting Options
- Side-mounting holes + end-mounting ears
Combustion, Mixing & Fuel Dynamics
- Gas Consumption
- Approximately 2 cu ft/hr
Dimensions & Size Specifications
- Orifice Sizes
- Natural Gas 0.025 in; LP 0.013 in; T/Y-port 0.028 in
Applications & Compatibility
- Applications
- Gas pilot assembly using flame rectification to prove flame, Gas burners and gas‑pilot‑ignited oil burners
Fuel, Gas & Media Specifications
- Fuel Type
- Natural gas (LP requires separate orifice)
Standards & Certifications
- Approvals
- UL Listed, CSA certified, FM Approved, AGA Certified
| Parameter | Published value / configuration |
|---|---|
| Inlet Gas Pressure Range | 2 to 8 in. WC |
| Flame Signal Voltage | Min. 1.25 VDC (Honeywell 7800 Series) |
| Electrical Connector | Rajah connectors (male and female) |
| Inlet Connection | 1/4 in compression coupling (factory installed) |
| Electrodes Included | Ignition electrode + flame electrode (Q179A1183: ignition only) |
| Flame Signal Range | Min. 2.0 µA flame current |
| Flame Detection | Flame rectification via flame electrode (rod) |
| Ignition Type | Spark ignition electrode (requires 6,000 V grounded secondary transformer) |
| Electrode Gap | 1/16 to 3/32 in |
| Temperature Rating | Flame/ignition electrodes 1750 deg F; ground shield 1300 deg F; pilot tip 1500 deg F |
| Product Category | Electrically ignited gas pilot burner |
| Product Type | Q179A Gas Pilot Burner Assembly |
| Burner Type | Primary aerated burner with stainless steel fins |
| Pilot Tip Styles | I-port, 45 deg I-port, 45 deg RH Ell, 45 deg LH Ell, T-port, Y-port, Large I-port |
| Mounting Options | Side-mounting holes + end-mounting ears |
| Gas Consumption | Approximately 2 cu ft/hr |
| Orifice Sizes | Natural Gas 0.025 in; LP 0.013 in; T/Y-port 0.028 in |
| Applications | Gas pilot assembly using flame rectification to prove flame, Gas burners and gas‑pilot‑ignited oil burners |
| Fuel Type | Natural gas (LP requires separate orifice) |
| Approvals | UL Listed, CSA certified, FM Approved, AGA Certified |
Values retain manufacturer model qualifications. Review Honeywell specifications ↗
Part Number
Published part numbers
10 parts
| Part Number | Description | Enquiry |
|---|---|---|
| 37356/520/U | RAJAH CONNECTOR FOR IGN ELECTRODE-Q179A | Request quotation |
| Q179A1001/U | GAS PILOT | Request quotation |
| Q179A1035/U | GAS PILOT | Request quotation |
| Q179A1050/U | T PILOT TIP | Request quotation |
| Q179A1076/U | GAS PILOT | Request quotation |
| Q179A1092/U | 45 DEG T PILOT TIP | Request quotation |
| Q179A1118/U | GAS PILOT | Request quotation |
| Q179A1126/U | 1 PILOT TIP, FOR HIGH TEMPERATURE APPL | Request quotation |
| Q179A1183/U | PILOT BURNER ASSY | Request quotation |
| Q179B1182/U | SAME AS Q179B1042 EXCEPT ORIFICE HAS .0 | Request quotation |
Manufacturer sources
Last source check: 2026-11-02
Pilot Burner Q179A Image · Manufacturer ownership retained; republication licence not independently confirmed
ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.
Your next project. A clear starting point.