Honeywell Process Measurement & Control

Flame Detectors

UVC, UVD

UVC and UVD provide ultraviolet gas-flame supervision, with continuous-duty configurations identified by the manufacturer.

UVC and UVD provide ultraviolet gas-flame supervision, with continuous-duty configurations identified by the manufacturer. UVD is described with BCU..U or PFU..U control units for intermittent or continuous service. The linked UVC 1 technical information should be used to establish the selected detector's complete installation requirements.

Features & Benefits

Ambient Temperature Range
-20 to +80 deg C (-4 to +176 deg F)
UV Tube Lifetime
10,000 operating hours
Terminal Wire Range
0.5 to 1.5 mm² (AWG 26 to AWG 16)
Switch-off Threshold
Adjustable from 20% to 80% (default: 20%) via BCSoft
Storage Temperature Range
-20 to +60 deg C (-4 to +140 deg F)
Signal Output
5 to 25 μA (active flame); < 1 μA (no flame)
Service Life
10 years after production
Sensor Type
UV tube R16388
Self-Check Mechanism
Integrated shutter test every minute
Safety Class/Pollution Degree
Class 1/Internal: 2, External: 4
Operating Voltage Range
100 to 230 VAC, -15/+10%, 50/60 Hz
Maximum Cooling Air Pressure
1.5 bar
Humidity Range
5 to 95% RH (non-condensing)
Enclosure Rating
IP65
Distance to Flame
300 to 400 mm
Detection Method
UV-C radiation (190 to 270 nm), max sensitivity at 210 nm ± 10 nm
Cable Length to Burner Control
2 to 100 m
Cable Gland Size
M20 (for 7-13 mm cable diameter)
Approvals
CE, GAR, LVD, EMC, UL, FM, AGA, Eurasian CU, China RoHS2, SIL3, PL e

Applications

  • Gas-burner UV supervision with specified BCU/PFU controls

Specifications

Environmental Conditions

Ambient Temperature Range
-20 to +80 deg C (-4 to +176 deg F)
Humidity Range
5 to 95% RH (non-condensing)
Enclosure Rating
IP65

Ignition, Flame & Supervision Specifications

UV Tube Lifetime
10,000 operating hours
Terminal Wire Range
0.5 to 1.5 mm² (AWG 26 to AWG 16)
Distance to Flame
300 to 400 mm

Control, Safety & Timing Characteristics

Switch-off Threshold
Adjustable from 20% to 80% (default: 20%) via BCSoft

Storage/Transport Temperatures

Storage Temperature Range
-20 to +60 deg C (-4 to +140 deg F)

Inputs, Outputs & Signal Interfaces

Signal Output
5 to 25 μA (active flame); < 1 μA (no flame)

Processing & Performance Metrics

Service Life
10 years after production

Measurement, Accuracy & Sensing

Sensor Type
UV tube R16388

Control, Logic & System Behavior

Self-Check Mechanism
Integrated shutter test every minute

Standards & Certifications

Safety Class/Pollution Degree
Class 1/Internal: 2, External: 4
Approvals
CE, GAR, LVD, EMC, UL, FM, AGA, Eurasian CU, China RoHS2, SIL3, PL e

Electrical Specifications

Operating Voltage Range
100 to 230 VAC, -15/+10%, 50/60 Hz

Pressure Specifications

Maximum Cooling Air Pressure
1.5 bar

Measurement & Sensing Characteristics

Detection Method
UV-C radiation (190 to 270 nm), max sensitivity at 210 nm ± 10 nm

Dimensions & Length Specifications

Cable Length to Burner Control
2 to 100 m

Dimensions & Size Specifications

Cable Gland Size
M20 (for 7-13 mm cable diameter)
UVC, UVD — manufacturer page values
ParameterPublished value / configuration
Ambient Temperature Range-20 to +80 deg C (-4 to +176 deg F)
Humidity Range5 to 95% RH (non-condensing)
Enclosure RatingIP65
UV Tube Lifetime10,000 operating hours
Terminal Wire Range0.5 to 1.5 mm² (AWG 26 to AWG 16)
Distance to Flame300 to 400 mm
Switch-off ThresholdAdjustable from 20% to 80% (default: 20%) via BCSoft
Storage Temperature Range-20 to +60 deg C (-4 to +140 deg F)
Signal Output5 to 25 μA (active flame); < 1 μA (no flame)
Service Life10 years after production
Sensor TypeUV tube R16388
Self-Check MechanismIntegrated shutter test every minute
Safety Class/Pollution DegreeClass 1/Internal: 2, External: 4
ApprovalsCE, GAR, LVD, EMC, UL, FM, AGA, Eurasian CU, China RoHS2, SIL3, PL e
Operating Voltage Range100 to 230 VAC, -15/+10%, 50/60 Hz
Maximum Cooling Air Pressure1.5 bar
Detection MethodUV-C radiation (190 to 270 nm), max sensitivity at 210 nm ± 10 nm
Cable Length to Burner Control2 to 100 m
Cable Gland SizeM20 (for 7-13 mm cable diameter)

Values retain manufacturer model qualifications. Review Honeywell specifications ↗

Part Number

Published part numbers

10 parts

Part NumberDescriptionEnquiry
002.0004.001MS20- 3/4in Relief ValveRequest quotation
009.0271.201ST1B80 - 3" Gas Pressure RegulatorRequest quotation
014.0204.001SpringRequest quotation
014.0508.001SpringRequest quotation
103003ADPT,SCNR,1/2 IN X 3/8 INRequest quotation
1175251SPL 5.875" SI W/.375" TIP ASY+Request quotation
13837IGN,SNSR,FLM,ION,291MM LG,0.5 IN. NPT,3.Request quotation
1811010MM SIRequest quotation
191048/0021BRACKETSRequest quotation
191053UV TUBERequest quotation
Manufacturer sources

https://process.honeywell.com/us/en/products/thermal-solutions/burner-management-systems/flame-detectors/uvc-uvd

Last source check: 2026-11-02

UV Detector · Manufacturer ownership retained; republication licence not independently confirmed

ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.

Your next project. A clear starting point.

Tell us about your facility and what you need to achieve.

CallSend enquiry