C7012 senses ultraviolet energy from fuels including natural gas, LPG and oil for Honeywell burner-control systems. Continuous-duty approval applies to E/F models with dynamic self-checking. Hazardous-location listings apply to C/F variants, and EN 298 approval depends on pairing the sensor with the specified amplifier or controller.

Features & Benefits

Viewing Window Pressure Rating
A/E/G: 20 psi (optional 50 psi window)|C/F: 100 psi rated window
Ambient Operating Temperature
A/C/G: 25 to 175 deg F (-4 to 79 deg C)|E/F: -20 to 175 deg F (-29 to 79 deg C)|Low‑temp versions to -40 deg F available
Parallel Detector Capability
Up to two detectors can be wired in parallel to prevent nuisance shutdowns
Hazardous Location Approvals
C7012C and C7012F: Class I Groups C and D; Class II Groups E, F, G (explosion‑proof)
Storage Temperature Range
-60 to 175°F (-51 to 79°C)
Operating Voltage Range
C7012A/E: Models for 100, 120, 208, 240 VAC 50/60 Hz|C7012C/F: 120 VAC only; C7012G: 220 V 50 Hz models
Compatible Amplifiers
R7247A/B/C, R7289A, R7747C, R7847A/B/C depending on model type (rectification/dynamic self‑check)
Minimum Flame Signal
Typically ≥2 µA (or ≥1.25 VDC depending on amplifier) per Table 1 spec
Mounting Interface
A/E/G: 3/4 or 1 in NPT mounting flange|C/F: 1 in NPT pipe union
Detection Method
Ultraviolet radiation sensing tube (field replaceable) with quartz viewing window
Connection Type
A/E: 1/2‑14 NPSM Internal Thread|C/F: 1/2‑14 NPT explosion‑proof (Conduit Entry)
Housing Type
A/E/G: NEMA‑4 Cast Aluminum (rain‑tight, dust‑tight, hose‑tight)|C/F: Explosion‑Proof Housing (UL listed)
Approvals
UL, CSA, Factory Mutual (FM), DIN, British Gas Corporation, SwissRe depending on model variant
Leadwire
A/C: 4 wires|All NEC Class 1, 8 ft long, color‑coded|E/F: 6 wires|G: 5 wires

Applications

  • Industrial gas, LPG and oil flame supervision with compatible controls

Specifications

Overview

Models
C7012A, C7012C, C7012E, C7012F, C7012G (includes self‑checking and explosion‑proof variants)

Pressure Specifications

Viewing Window Pressure Rating
A/E/G: 20 psi (optional 50 psi window); C/F: 100 psi rated window

Environmental Conditions

Ambient Operating Temperature
A/C/G: 25 to 175 deg F (-4 to 79 deg C); E/F: -20 to 175 deg F (-29 to 79 deg C); Low‑temp versions to -40 deg F available

Ignition, Flame & Supervision Specifications

Parallel Detector Capability
Up to two detectors can be wired in parallel to prevent nuisance shutdowns
Minimum Flame Signal
Typically ≥2 µA (or ≥1.25 VDC depending on amplifier) per Table 1 spec

Standards & Certifications

Hazardous Location Approvals
C7012C and C7012F: Class I Groups C and D; Class II Groups E, F, G (explosion‑proof)
Approvals
UL, CSA, Factory Mutual (FM), DIN, British Gas Corporation, SwissRe depending on model variant

Storage/Transport Temperatures

Storage Temperature Range
-60 to 175°F (-51 to 79°C)

Electrical Specifications

Operating Voltage Range
C7012A/E: Models for 100, 120, 208, 240 VAC 50/60 Hz; C7012C/F: 120 VAC only; C7012G: 220 V 50 Hz models

Applications & Compatibility

Compatible Amplifiers
R7247A/B/C, R7289A, R7747C, R7847A/B/C depending on model type (rectification/dynamic self‑check)
Applications
Burner/boiler flame supervision, flame safeguard systems, multi‑burner installations, flame discrimination in industrial furnaces

Installation & Mounting Specifications

Mounting Interface
A/E/G: 3/4 or 1 in NPT mounting flange; C/F: 1 in NPT pipe union

Measurement & Sensing Characteristics

Detection Method
Ultraviolet radiation sensing tube (field replaceable) with quartz viewing window

Connections & Interfaces

Connection Type
A/E: 1/2‑14 NPSM Internal Thread; C/F: 1/2‑14 NPT explosion‑proof (Conduit Entry)

Product Design & Configuration

Housing Type
A/E/G: NEMA‑4 Cast Aluminum (rain‑tight, dust‑tight, hose‑tight); C/F: Explosion‑Proof Housing (UL listed)

Mechanical Design & Hardware Details

Leadwire
A/C: 4 wires; All NEC Class 1, 8 ft long, color‑coded; E/F: 6 wires; G: 5 wires
C7012 Ultraviolet Flame Detector — manufacturer page values
ParameterPublished value / configuration
ModelsC7012A, C7012C, C7012E, C7012F, C7012G (includes self‑checking and explosion‑proof variants)
Viewing Window Pressure RatingA/E/G: 20 psi (optional 50 psi window); C/F: 100 psi rated window
Ambient Operating TemperatureA/C/G: 25 to 175 deg F (-4 to 79 deg C); E/F: -20 to 175 deg F (-29 to 79 deg C); Low‑temp versions to -40 deg F available
Parallel Detector CapabilityUp to two detectors can be wired in parallel to prevent nuisance shutdowns
Minimum Flame SignalTypically ≥2 µA (or ≥1.25 VDC depending on amplifier) per Table 1 spec
Hazardous Location ApprovalsC7012C and C7012F: Class I Groups C and D; Class II Groups E, F, G (explosion‑proof)
ApprovalsUL, CSA, Factory Mutual (FM), DIN, British Gas Corporation, SwissRe depending on model variant
Storage Temperature Range-60 to 175°F (-51 to 79°C)
Operating Voltage RangeC7012A/E: Models for 100, 120, 208, 240 VAC 50/60 Hz; C7012C/F: 120 VAC only; C7012G: 220 V 50 Hz models
Compatible AmplifiersR7247A/B/C, R7289A, R7747C, R7847A/B/C depending on model type (rectification/dynamic self‑check)
ApplicationsBurner/boiler flame supervision, flame safeguard systems, multi‑burner installations, flame discrimination in industrial furnaces
Mounting InterfaceA/E/G: 3/4 or 1 in NPT mounting flange; C/F: 1 in NPT pipe union
Detection MethodUltraviolet radiation sensing tube (field replaceable) with quartz viewing window
Connection TypeA/E: 1/2‑14 NPSM Internal Thread; C/F: 1/2‑14 NPT explosion‑proof (Conduit Entry)
Housing TypeA/E/G: NEMA‑4 Cast Aluminum (rain‑tight, dust‑tight, hose‑tight); C/F: Explosion‑Proof Housing (UL listed)
LeadwireA/C: 4 wires; All NEC Class 1, 8 ft long, color‑coded; E/F: 6 wires; G: 5 wires

Values retain manufacturer model qualifications. Review Honeywell specifications ↗

Part Number

Published part numbers

7 parts

Part NumberDescriptionEnquiry
114465/UWINDOW GASKETRequest quotation
191002A/UCHASSIS ASSY 100VRequest quotation
191050/UQUARTZ LENCSE C7076DRequest quotation
C7012A1186/UUV DETECTOR 208VACRequest quotation
C7012C1042/UUV DETECTOR 120VAC - EXRequest quotation
C7012E1211/UUV DETECTOR 100VAC SELF-CHECKRequest quotation
C7044A1006/UUV SENSORRequest quotation
Manufacturer sources

https://process.honeywell.com/us/en/products/thermal-solutions/burner-management-systems/flame-detectors/c7012-ultraviolet-flame-detector

Last source check: 2026-11-02

Ultraviolet Flame Detector · Manufacturer ownership retained; republication licence not independently confirmed

ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.

Your next project. A clear starting point.

Tell us about your facility and what you need to achieve.

CallSend enquiry