Flame Detectors
C7012 Ultraviolet Flame Detector
C7012 senses ultraviolet energy from fuels including natural gas, LPG and oil for Honeywell burner-control systems.
C7012 senses ultraviolet energy from fuels including natural gas, LPG and oil for Honeywell burner-control systems. Continuous-duty approval applies to E/F models with dynamic self-checking. Hazardous-location listings apply to C/F variants, and EN 298 approval depends on pairing the sensor with the specified amplifier or controller.
Features & Benefits
- Viewing Window Pressure Rating
- A/E/G: 20 psi (optional 50 psi window)|C/F: 100 psi rated window
- Ambient Operating Temperature
- A/C/G: 25 to 175 deg F (-4 to 79 deg C)|E/F: -20 to 175 deg F (-29 to 79 deg C)|Low‑temp versions to -40 deg F available
- Parallel Detector Capability
- Up to two detectors can be wired in parallel to prevent nuisance shutdowns
- Hazardous Location Approvals
- C7012C and C7012F: Class I Groups C and D; Class II Groups E, F, G (explosion‑proof)
- Storage Temperature Range
- -60 to 175°F (-51 to 79°C)
- Operating Voltage Range
- C7012A/E: Models for 100, 120, 208, 240 VAC 50/60 Hz|C7012C/F: 120 VAC only; C7012G: 220 V 50 Hz models
- Compatible Amplifiers
- R7247A/B/C, R7289A, R7747C, R7847A/B/C depending on model type (rectification/dynamic self‑check)
- Minimum Flame Signal
- Typically ≥2 µA (or ≥1.25 VDC depending on amplifier) per Table 1 spec
- Mounting Interface
- A/E/G: 3/4 or 1 in NPT mounting flange|C/F: 1 in NPT pipe union
- Detection Method
- Ultraviolet radiation sensing tube (field replaceable) with quartz viewing window
- Connection Type
- A/E: 1/2‑14 NPSM Internal Thread|C/F: 1/2‑14 NPT explosion‑proof (Conduit Entry)
- Housing Type
- A/E/G: NEMA‑4 Cast Aluminum (rain‑tight, dust‑tight, hose‑tight)|C/F: Explosion‑Proof Housing (UL listed)
- Approvals
- UL, CSA, Factory Mutual (FM), DIN, British Gas Corporation, SwissRe depending on model variant
- Leadwire
- A/C: 4 wires|All NEC Class 1, 8 ft long, color‑coded|E/F: 6 wires|G: 5 wires
Applications
- Industrial gas, LPG and oil flame supervision with compatible controls
Overview
- Models
- C7012A, C7012C, C7012E, C7012F, C7012G (includes self‑checking and explosion‑proof variants)
Pressure Specifications
- Viewing Window Pressure Rating
- A/E/G: 20 psi (optional 50 psi window); C/F: 100 psi rated window
Environmental Conditions
- Ambient Operating Temperature
- A/C/G: 25 to 175 deg F (-4 to 79 deg C); E/F: -20 to 175 deg F (-29 to 79 deg C); Low‑temp versions to -40 deg F available
Ignition, Flame & Supervision Specifications
- Parallel Detector Capability
- Up to two detectors can be wired in parallel to prevent nuisance shutdowns
- Minimum Flame Signal
- Typically ≥2 µA (or ≥1.25 VDC depending on amplifier) per Table 1 spec
Standards & Certifications
- Hazardous Location Approvals
- C7012C and C7012F: Class I Groups C and D; Class II Groups E, F, G (explosion‑proof)
- Approvals
- UL, CSA, Factory Mutual (FM), DIN, British Gas Corporation, SwissRe depending on model variant
Storage/Transport Temperatures
- Storage Temperature Range
- -60 to 175°F (-51 to 79°C)
Electrical Specifications
- Operating Voltage Range
- C7012A/E: Models for 100, 120, 208, 240 VAC 50/60 Hz; C7012C/F: 120 VAC only; C7012G: 220 V 50 Hz models
Applications & Compatibility
- Compatible Amplifiers
- R7247A/B/C, R7289A, R7747C, R7847A/B/C depending on model type (rectification/dynamic self‑check)
- Applications
- Burner/boiler flame supervision, flame safeguard systems, multi‑burner installations, flame discrimination in industrial furnaces
Installation & Mounting Specifications
- Mounting Interface
- A/E/G: 3/4 or 1 in NPT mounting flange; C/F: 1 in NPT pipe union
Measurement & Sensing Characteristics
- Detection Method
- Ultraviolet radiation sensing tube (field replaceable) with quartz viewing window
Connections & Interfaces
- Connection Type
- A/E: 1/2‑14 NPSM Internal Thread; C/F: 1/2‑14 NPT explosion‑proof (Conduit Entry)
Product Design & Configuration
- Housing Type
- A/E/G: NEMA‑4 Cast Aluminum (rain‑tight, dust‑tight, hose‑tight); C/F: Explosion‑Proof Housing (UL listed)
Mechanical Design & Hardware Details
- Leadwire
- A/C: 4 wires; All NEC Class 1, 8 ft long, color‑coded; E/F: 6 wires; G: 5 wires
| Parameter | Published value / configuration |
|---|---|
| Models | C7012A, C7012C, C7012E, C7012F, C7012G (includes self‑checking and explosion‑proof variants) |
| Viewing Window Pressure Rating | A/E/G: 20 psi (optional 50 psi window); C/F: 100 psi rated window |
| Ambient Operating Temperature | A/C/G: 25 to 175 deg F (-4 to 79 deg C); E/F: -20 to 175 deg F (-29 to 79 deg C); Low‑temp versions to -40 deg F available |
| Parallel Detector Capability | Up to two detectors can be wired in parallel to prevent nuisance shutdowns |
| Minimum Flame Signal | Typically ≥2 µA (or ≥1.25 VDC depending on amplifier) per Table 1 spec |
| Hazardous Location Approvals | C7012C and C7012F: Class I Groups C and D; Class II Groups E, F, G (explosion‑proof) |
| Approvals | UL, CSA, Factory Mutual (FM), DIN, British Gas Corporation, SwissRe depending on model variant |
| Storage Temperature Range | -60 to 175°F (-51 to 79°C) |
| Operating Voltage Range | C7012A/E: Models for 100, 120, 208, 240 VAC 50/60 Hz; C7012C/F: 120 VAC only; C7012G: 220 V 50 Hz models |
| Compatible Amplifiers | R7247A/B/C, R7289A, R7747C, R7847A/B/C depending on model type (rectification/dynamic self‑check) |
| Applications | Burner/boiler flame supervision, flame safeguard systems, multi‑burner installations, flame discrimination in industrial furnaces |
| Mounting Interface | A/E/G: 3/4 or 1 in NPT mounting flange; C/F: 1 in NPT pipe union |
| Detection Method | Ultraviolet radiation sensing tube (field replaceable) with quartz viewing window |
| Connection Type | A/E: 1/2‑14 NPSM Internal Thread; C/F: 1/2‑14 NPT explosion‑proof (Conduit Entry) |
| Housing Type | A/E/G: NEMA‑4 Cast Aluminum (rain‑tight, dust‑tight, hose‑tight); C/F: Explosion‑Proof Housing (UL listed) |
| Leadwire | A/C: 4 wires; All NEC Class 1, 8 ft long, color‑coded; E/F: 6 wires; G: 5 wires |
Values retain manufacturer model qualifications. Review Honeywell specifications ↗
Part Number
Published part numbers
7 parts
| Part Number | Description | Enquiry |
|---|---|---|
| 114465/U | WINDOW GASKET | Request quotation |
| 191002A/U | CHASSIS ASSY 100V | Request quotation |
| 191050/U | QUARTZ LENCSE C7076D | Request quotation |
| C7012A1186/U | UV DETECTOR 208VAC | Request quotation |
| C7012C1042/U | UV DETECTOR 120VAC - EX | Request quotation |
| C7012E1211/U | UV DETECTOR 100VAC SELF-CHECK | Request quotation |
| C7044A1006/U | UV SENSOR | Request quotation |
Manufacturer sources
Last source check: 2026-11-02
Ultraviolet Flame Detector · Manufacturer ownership retained; republication licence not independently confirmed
ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.