C7027 and C7035 are compact analog UV sensors for commercial and industrial flame supervision. An encapsulated sensing tube protects the detection element, and installation uses a standard sight pipe. They are specified for intermittent operation, requiring a controlled burner recycle at least once in each 24-hour period.

Features & Benefits

Ambient Operating Temperature
-20 to +70 deg C (-4 to +160 deg F)
Storage Temperature Range
-50 to +80°C (-60 to +175°F)
Serviceability
Field-replaceable UV sensing tube
Purge Air Connection
3/8 in NPT internal thread
Pressure Ratings
690 kPa (100 psi) (Quartz Window)
Parallel Detector Capability
Up to 2 detectors can be connected in parallel
Operating Voltage Range
115 VAC or 230 VAC (terminal selectable) (Shutter)
Mounting Options
1 in NPT internal thread flange
Flame Signal Range
0.8 to 8 VDC depending on controller, 4 to 14 µA (DBC2000)
Enclosure Rating
IP66, Explosion-proof (CENELEC II G Ex db IIC T6)
Compatible Controllers
SLATE, 7800-series, DBC2000, BC1000, Kromschröder FDU 510..3
Cable Entries
1/2 in NPT internal thread
Approvals
IECEx Certified, ATEX Certified, KCs Certified, CE Approved, SIL 3 Capable
  • A protected sensing tube and standard sight-pipe mounting simplify installation.

Applications

  • Intermittent commercial and industrial flame supervision

Specifications

Environmental Conditions

Ambient Operating Temperature
-20 to +70 deg C (-4 to +160 deg F)
Enclosure Rating
IP66, Explosion-proof (CENELEC II G Ex db IIC T6)

Storage/Transport Temperatures

Storage Temperature Range
-50 to +80°C (-60 to +175°F)

Operating Limits, Durability & Lifecycle

Serviceability
Field-replaceable UV sensing tube

Connections & Interfaces

Purge Air Connection
3/8 in NPT internal thread

Pressure Specifications

Pressure Ratings
690 kPa (100 psi) (Quartz Window)

Ignition, Flame & Supervision Specifications

Parallel Detector Capability
Up to 2 detectors can be connected in parallel
Flame Signal Range
0.8 to 8 VDC depending on controller, 4 to 14 µA (DBC2000)

Electrical Specifications

Operating Voltage Range
115 VAC or 230 VAC (terminal selectable) (Shutter)

Installation & Mounting Specifications

Mounting Options
1 in NPT internal thread flange

Overview

Models
C7035C (non self-checking), C7061F1 (dynamic self-checking)

Applications & Compatibility

Compatible Controllers
SLATE, 7800-series, DBC2000, BC1000, Kromschröder FDU 510..3
Applications
Flame detection for gas, oil, or other fuel combustion

Mechanical Design, Layout & Construction Options

Cable Entries
1/2 in NPT internal thread

Standards & Certifications

Approvals
IECEx Certified, ATEX Certified, KCs Certified, CE Approved, SIL 3 Capable
C7027, C7035 — manufacturer page values
ParameterPublished value / configuration
Ambient Operating Temperature-20 to +70 deg C (-4 to +160 deg F)
Enclosure RatingIP66, Explosion-proof (CENELEC II G Ex db IIC T6)
Storage Temperature Range-50 to +80°C (-60 to +175°F)
ServiceabilityField-replaceable UV sensing tube
Purge Air Connection3/8 in NPT internal thread
Pressure Ratings690 kPa (100 psi) (Quartz Window)
Parallel Detector CapabilityUp to 2 detectors can be connected in parallel
Flame Signal Range0.8 to 8 VDC depending on controller, 4 to 14 µA (DBC2000)
Operating Voltage Range115 VAC or 230 VAC (terminal selectable) (Shutter)
Mounting Options1 in NPT internal thread flange
ModelsC7035C (non self-checking), C7061F1 (dynamic self-checking)
Compatible ControllersSLATE, 7800-series, DBC2000, BC1000, Kromschröder FDU 510..3
ApplicationsFlame detection for gas, oil, or other fuel combustion
Cable Entries1/2 in NPT internal thread
ApprovalsIECEx Certified, ATEX Certified, KCs Certified, CE Approved, SIL 3 Capable

Values retain manufacturer model qualifications. Review Honeywell specifications ↗

Part Number

Published part numbers

10 parts

Part NumberDescriptionEnquiry
120738/0021/XPLATERequest quotation
129464N/XUV POWER TUBERequest quotation
190790/XSPRING TABSRequest quotation
191019/XC7012 BLADERequest quotation
191284/UALUMINUM SHEILD FOR C7035Request quotation
50089925-001SOCKETRequest quotation
BS-MWC4-PN16-0150Butterfly Valve Series, Gear Box Operator, Wafer Type, Cast Iron Body, PN16, DN150Request quotation
C7027A1023/UUV DETECTOR MINIPEEPERRequest quotation
C7027A1023UU.V. FLAME DETECTOR - CN SPECIALRequest quotation
C7027A1031/UUV DETECTOR MINIPEEPERRequest quotation
Manufacturer sources

https://process.honeywell.com/us/en/products/thermal-solutions/burner-management-systems/flame-detectors/c7027-c7035

Last source check: 2026-11-02

Ultraviolet Flame Detector · Manufacturer ownership retained; republication licence not independently confirmed

Ultraviolet Flame Detector · Manufacturer ownership retained; republication licence not independently confirmed

ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.

Your next project. A clear starting point.

Tell us about your facility and what you need to achieve.

CallSend enquiry