Flame Detectors
C7027, C7035
C7027 and C7035 are compact analog UV sensors for commercial and industrial flame supervision.
C7027 and C7035 are compact analog UV sensors for commercial and industrial flame supervision. An encapsulated sensing tube protects the detection element, and installation uses a standard sight pipe. They are specified for intermittent operation, requiring a controlled burner recycle at least once in each 24-hour period.
Features & Benefits
- Ambient Operating Temperature
- -20 to +70 deg C (-4 to +160 deg F)
- Storage Temperature Range
- -50 to +80°C (-60 to +175°F)
- Serviceability
- Field-replaceable UV sensing tube
- Purge Air Connection
- 3/8 in NPT internal thread
- Pressure Ratings
- 690 kPa (100 psi) (Quartz Window)
- Parallel Detector Capability
- Up to 2 detectors can be connected in parallel
- Operating Voltage Range
- 115 VAC or 230 VAC (terminal selectable) (Shutter)
- Mounting Options
- 1 in NPT internal thread flange
- Flame Signal Range
- 0.8 to 8 VDC depending on controller, 4 to 14 µA (DBC2000)
- Enclosure Rating
- IP66, Explosion-proof (CENELEC II G Ex db IIC T6)
- Compatible Controllers
- SLATE, 7800-series, DBC2000, BC1000, Kromschröder FDU 510..3
- Cable Entries
- 1/2 in NPT internal thread
- Approvals
- IECEx Certified, ATEX Certified, KCs Certified, CE Approved, SIL 3 Capable
- A protected sensing tube and standard sight-pipe mounting simplify installation.
Applications
- Intermittent commercial and industrial flame supervision
Environmental Conditions
- Ambient Operating Temperature
- -20 to +70 deg C (-4 to +160 deg F)
- Enclosure Rating
- IP66, Explosion-proof (CENELEC II G Ex db IIC T6)
Storage/Transport Temperatures
- Storage Temperature Range
- -50 to +80°C (-60 to +175°F)
Operating Limits, Durability & Lifecycle
- Serviceability
- Field-replaceable UV sensing tube
Connections & Interfaces
- Purge Air Connection
- 3/8 in NPT internal thread
Pressure Specifications
- Pressure Ratings
- 690 kPa (100 psi) (Quartz Window)
Ignition, Flame & Supervision Specifications
- Parallel Detector Capability
- Up to 2 detectors can be connected in parallel
- Flame Signal Range
- 0.8 to 8 VDC depending on controller, 4 to 14 µA (DBC2000)
Electrical Specifications
- Operating Voltage Range
- 115 VAC or 230 VAC (terminal selectable) (Shutter)
Installation & Mounting Specifications
- Mounting Options
- 1 in NPT internal thread flange
Overview
- Models
- C7035C (non self-checking), C7061F1 (dynamic self-checking)
Applications & Compatibility
- Compatible Controllers
- SLATE, 7800-series, DBC2000, BC1000, Kromschröder FDU 510..3
- Applications
- Flame detection for gas, oil, or other fuel combustion
Mechanical Design, Layout & Construction Options
- Cable Entries
- 1/2 in NPT internal thread
Standards & Certifications
- Approvals
- IECEx Certified, ATEX Certified, KCs Certified, CE Approved, SIL 3 Capable
| Parameter | Published value / configuration |
|---|---|
| Ambient Operating Temperature | -20 to +70 deg C (-4 to +160 deg F) |
| Enclosure Rating | IP66, Explosion-proof (CENELEC II G Ex db IIC T6) |
| Storage Temperature Range | -50 to +80°C (-60 to +175°F) |
| Serviceability | Field-replaceable UV sensing tube |
| Purge Air Connection | 3/8 in NPT internal thread |
| Pressure Ratings | 690 kPa (100 psi) (Quartz Window) |
| Parallel Detector Capability | Up to 2 detectors can be connected in parallel |
| Flame Signal Range | 0.8 to 8 VDC depending on controller, 4 to 14 µA (DBC2000) |
| Operating Voltage Range | 115 VAC or 230 VAC (terminal selectable) (Shutter) |
| Mounting Options | 1 in NPT internal thread flange |
| Models | C7035C (non self-checking), C7061F1 (dynamic self-checking) |
| Compatible Controllers | SLATE, 7800-series, DBC2000, BC1000, Kromschröder FDU 510..3 |
| Applications | Flame detection for gas, oil, or other fuel combustion |
| Cable Entries | 1/2 in NPT internal thread |
| Approvals | IECEx Certified, ATEX Certified, KCs Certified, CE Approved, SIL 3 Capable |
Values retain manufacturer model qualifications. Review Honeywell specifications ↗
Part Number
Published part numbers
10 parts
| Part Number | Description | Enquiry |
|---|---|---|
| 120738/0021/X | PLATE | Request quotation |
| 129464N/X | UV POWER TUBE | Request quotation |
| 190790/X | SPRING TABS | Request quotation |
| 191019/X | C7012 BLADE | Request quotation |
| 191284/U | ALUMINUM SHEILD FOR C7035 | Request quotation |
| 50089925-001 | SOCKET | Request quotation |
| BS-MWC4-PN16-0150 | Butterfly Valve Series, Gear Box Operator, Wafer Type, Cast Iron Body, PN16, DN150 | Request quotation |
| C7027A1023/U | UV DETECTOR MINIPEEPER | Request quotation |
| C7027A1023U | U.V. FLAME DETECTOR - CN SPECIAL | Request quotation |
| C7027A1031/U | UV DETECTOR MINIPEEPER | Request quotation |
Manufacturer sources
Last source check: 2026-11-02
Ultraviolet Flame Detector · Manufacturer ownership retained; republication licence not independently confirmed
Ultraviolet Flame Detector · Manufacturer ownership retained; republication licence not independently confirmed
ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.
Your next project. A clear starting point.