Flame Detectors
C7061A, F
C7061A/F provides electronic UV flame detection with dynamic self-checking for continuous industrial burner operation.
C7061A/F provides electronic UV flame detection with dynamic self-checking for continuous industrial burner operation. Approval depends on the complete detection/control combination. Hazardous-area coverage is model-specific: F1 carries the published ATEX qualification, while F2 has the stated North American class and group listings.
Features & Benefits
- Operating Temperature Range
- C7035C, C7061F1: -20 to +70 deg C (-4 to +160 deg F); C7061A|C7061F2: -40 to +175 deg F (-40 to +80 deg C)
- Storage Temperature Range
- -50 to +80°C (-60 to +175°F)
- Compatible Controllers
- SLATE, 7800-series, DBC2000, BC1000, Kromschröder FDU 510..3
- Compatible Amplifiers
- C7061A: R7861A (7800 SERIES) or R8001S1051 (SLATE)|C7061F (F1/F2): R7861 (7800 SERIES) or R8001S1051 (SLATE)
- Flame Signal Range
- C7061A: 1.25-5 VDC (7800 Series), up to 8 VDC (SLATE); C7061F (F1/F2): Same (1.25-5.0 VDC/up to 8 VDC for SLATE)
- Pressure Ratings
- C7035C, C7061F1: 690 kPa (100 psi) (Quartz Viewing Window)|C7061A, C7061F2: 138/690 kPa (20/100 psi) (Quartz Viewing Window), 20 psi (138 kPa) (Quartz Focusing Lens)
- Mounting Options
- C7035C: 1 in NPT Flange, includes 1 in MNPT x 3/4 in FNPT Adapter; C7061F (F1/F2): 1 in NPT explosion‑proof union
- Enclosure Rating
- C7035C, C7061F1: IP66, Explosion-proof (CENELEC II G Ex db IIC T6)|C7035C: NEMA 4|C7061F (F1/F2): IP66 + Explosion‑proof Ex db IIC T6
- Electrical Power
- C7061A: Powered via flame safeguard controller (tube + shutter)|C7061F (F1/F2): Powered via flame safeguard controller (tube + shutter); shutter voltage selectable 115/230 VAC (F1)
- UV Sensing Tube
- -40 deg C rated, field replaceable
- Cable Entries
- C7035C: 1/2‑14 NPSM conduit opening|C7061F (F1/F2): 1/2 in NPT conduit entry; EX‑approved gland required
- Approvals
- IECEx Certified, ATEX Certified, KCs Certified, CE Approved, SIL 3 Capable, UL Listed, FM Approved, WEEE Directive Compliance
Applications
- Continuous industrial flame supervision
Overview
- Models
- C7035C (non self-checking), C7061F (F1/F2) (dynamic self-checking)
Operating/Process Temperature Ranges
- Operating Temperature Range
- C7035C, C7061F1: -20 to +70 deg C (-4 to +160 deg F); C7061A; C7061F2: -40 to +175 deg F (-40 to +80 deg C)
Storage/Transport Temperatures
- Storage Temperature Range
- -50 to +80°C (-60 to +175°F)
Applications & Compatibility
- Compatible Controllers
- SLATE, 7800-series, DBC2000, BC1000, Kromschröder FDU 510..3
- Compatible Amplifiers
- C7061A: R7861A (7800 SERIES) or R8001S1051 (SLATE); C7061F (F1/F2): R7861 (7800 SERIES) or R8001S1051 (SLATE)
- Applications
- Detects UV radiation from gas/oil flames, used with R7861 self‑check amplifier
Ignition, Flame & Supervision Specifications
- Flame Signal Range
- C7061A: 1.25-5 VDC (7800 Series), up to 8 VDC (SLATE); C7061F (F1/F2): Same (1.25-5.0 VDC/up to 8 VDC for SLATE)
- UV Sensing Tube
- -40 deg C rated, field replaceable
Pressure Specifications
- Pressure Ratings
- C7035C, C7061F1: 690 kPa (100 psi) (Quartz Viewing Window); C7061A, C7061F2: 138/690 kPa (20/100 psi) (Quartz Viewing Window), 20 psi (138 kPa) (Quartz Focusing Lens)
Installation & Mounting Specifications
- Mounting Options
- C7035C: 1 in NPT Flange, includes 1 in MNPT x 3/4 in FNPT Adapter; C7061F (F1/F2): 1 in NPT explosion‑proof union
Environmental Conditions
- Enclosure Rating
- C7035C, C7061F1: IP66, Explosion-proof (CENELEC II G Ex db IIC T6); C7035C: NEMA 4; C7061F (F1/F2): IP66 + Explosion‑proof Ex db IIC T6
Electrical Specifications
- Electrical Power
- C7061A: Powered via flame safeguard controller (tube + shutter); C7061F (F1/F2): Powered via flame safeguard controller (tube + shutter); shutter voltage selectable 115/230 VAC (F1)
Mechanical Design, Layout & Construction Options
- Cable Entries
- C7035C: 1/2‑14 NPSM conduit opening; C7061F (F1/F2): 1/2 in NPT conduit entry; EX‑approved gland required
Standards & Certifications
- Approvals
- IECEx Certified, ATEX Certified, KCs Certified, CE Approved, SIL 3 Capable, UL Listed, FM Approved, WEEE Directive Compliance
| Parameter | Published value / configuration |
|---|---|
| Models | C7035C (non self-checking), C7061F (F1/F2) (dynamic self-checking) |
| Operating Temperature Range | C7035C, C7061F1: -20 to +70 deg C (-4 to +160 deg F); C7061A; C7061F2: -40 to +175 deg F (-40 to +80 deg C) |
| Storage Temperature Range | -50 to +80°C (-60 to +175°F) |
| Compatible Controllers | SLATE, 7800-series, DBC2000, BC1000, Kromschröder FDU 510..3 |
| Compatible Amplifiers | C7061A: R7861A (7800 SERIES) or R8001S1051 (SLATE); C7061F (F1/F2): R7861 (7800 SERIES) or R8001S1051 (SLATE) |
| Applications | Detects UV radiation from gas/oil flames, used with R7861 self‑check amplifier |
| Flame Signal Range | C7061A: 1.25-5 VDC (7800 Series), up to 8 VDC (SLATE); C7061F (F1/F2): Same (1.25-5.0 VDC/up to 8 VDC for SLATE) |
| UV Sensing Tube | -40 deg C rated, field replaceable |
| Pressure Ratings | C7035C, C7061F1: 690 kPa (100 psi) (Quartz Viewing Window); C7061A, C7061F2: 138/690 kPa (20/100 psi) (Quartz Viewing Window), 20 psi (138 kPa) (Quartz Focusing Lens) |
| Mounting Options | C7035C: 1 in NPT Flange, includes 1 in MNPT x 3/4 in FNPT Adapter; C7061F (F1/F2): 1 in NPT explosion‑proof union |
| Enclosure Rating | C7035C, C7061F1: IP66, Explosion-proof (CENELEC II G Ex db IIC T6); C7035C: NEMA 4; C7061F (F1/F2): IP66 + Explosion‑proof Ex db IIC T6 |
| Electrical Power | C7061A: Powered via flame safeguard controller (tube + shutter); C7061F (F1/F2): Powered via flame safeguard controller (tube + shutter); shutter voltage selectable 115/230 VAC (F1) |
| Cable Entries | C7035C: 1/2‑14 NPSM conduit opening; C7061F (F1/F2): 1/2 in NPT conduit entry; EX‑approved gland required |
| Approvals | IECEx Certified, ATEX Certified, KCs Certified, CE Approved, SIL 3 Capable, UL Listed, FM Approved, WEEE Directive Compliance |
Values retain manufacturer model qualifications. Review Honeywell specifications ↗
Part Number
Published part numbers
10 parts
| Part Number | Description | Enquiry |
|---|---|---|
| 50123613-001 | FIG5UVCART EP KIT | Request quotation |
| 50127283-001 | SPL .6075" 14MM SI | Request quotation |
| 50133140-001 | 20" QRTZ IGN ASY | Request quotation |
| 54376 | SI | Request quotation |
| 54437 | SI | Request quotation |
| 59162 | 1.875" MINI FR | Request quotation |
| 59164 | 2.625" MINI FR | Request quotation |
| 59165 | 2.75" MINI FR | Request quotation |
| 59166 | 6" MINI FR | Request quotation |
| 59174 | 4.125" MINI FR | Request quotation |
Manufacturer sources
Last source check: 2026-11-02
Ultraviolet Flame Detector · Manufacturer ownership retained; republication licence not independently confirmed
Ultraviolet Flame Detector · Manufacturer ownership retained; republication licence not independently confirmed
ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.
Your next project. A clear starting point.
Tell us about your facility and what you need to achieve.