Fire & Life Safety · Building Systems · Industrial Automation [email protected] +880 1347 561 256
Honeywell Process Measurement & Control

Flame Detectors

UV sensor

UVS sensors monitor gas flames during intermittent burner operation when connected to compatible flame detectors or automatic controls.

UVS sensors monitor gas flames during intermittent burner operation when connected to compatible flame detectors or automatic controls. EU certification is stated with Kromschröder controls. The reference links distinguish UVS 5 and UVS 10; the page does not extend their intermittent qualification to continuous duty.

Features & Benefits

Storage Temperature Range
-40 to +80 deg C (-40 to +176 deg F)
Ambient Temperature Range
-40 to +80 deg C (-40 to +176 deg F)
Cooling/Purge Air Option
UVS 5 (Not specified), UVS 10 (Yes, via cooling air adapter and nozzle options)
Operating Voltage Range
220/240 VAC (supplied by burner control unit)
Distance to Flame
UVS 5 (Max. 400 mm (16 in)), UVS 10 (300-400 mm (12-16 in); with lens: 600-1200 mm (23-47 in))
UV Tube Lifetime
Approximately 10,000 operating hours
Mounting Options
UVS 5 (Bracket attached to burner), UVS 10 (Adapter with quartz glass heat guard on 1/2 in viewing tube)
Enclosure Rating
UVS 5 (IP40/IP54 (NEMA 3)), UVS 10 (IP65)
Detection Method
Max sensitivity: 210 nm ±10 nm|UV tube R16388, spectral range: 185 to 280 nm
Cable Gland Size
M20 for 7 to 13 mm cable diameter
Signal Output
DC signal, min. 1 μA
Approvals
CE Certified, Eurasian Customs Union, REACH Regulation No. 1907/2006, China RoHS

Applications

  • Intermittent gas-burner UV monitoring

Specifications

Overview

Models
UVS 5, UVS 10

Storage/Transport Temperatures

Storage Temperature Range
-40 to +80 deg C (-40 to +176 deg F)

Environmental Conditions

Ambient Temperature Range
-40 to +80 deg C (-40 to +176 deg F)
Enclosure Rating
UVS 5 (IP40/IP54 (NEMA 3)), UVS 10 (IP65)

Air & Combustion Air Specifications

Cooling/Purge Air Option
UVS 5 (Not specified), UVS 10 (Yes, via cooling air adapter and nozzle options)

Electrical Specifications

Operating Voltage Range
220/240 VAC (supplied by burner control unit)

Ignition, Flame & Supervision Specifications

Distance to Flame
UVS 5 (Max. 400 mm (16 in)), UVS 10 (300-400 mm (12-16 in); with lens: 600-1200 mm (23-47 in))
UV Tube Lifetime
Approximately 10,000 operating hours

Installation & Mounting Specifications

Mounting Options
UVS 5 (Bracket attached to burner), UVS 10 (Adapter with quartz glass heat guard on 1/2 in viewing tube)

Measurement & Sensing Characteristics

Detection Method
Max sensitivity: 210 nm ±10 nm; UV tube R16388, spectral range: 185 to 280 nm

Dimensions & Size Specifications

Cable Gland Size
M20 for 7 to 13 mm cable diameter

Inputs, Outputs & Signal Interfaces

Signal Output
DC signal, min. 1 μA

Standards & Certifications

Approvals
CE Certified, Eurasian Customs Union, REACH Regulation No. 1907/2006, China RoHS
UV sensor — manufacturer page values
ParameterPublished value / configuration
ModelsUVS 5, UVS 10
Storage Temperature Range-40 to +80 deg C (-40 to +176 deg F)
Ambient Temperature Range-40 to +80 deg C (-40 to +176 deg F)
Enclosure RatingUVS 5 (IP40/IP54 (NEMA 3)), UVS 10 (IP65)
Cooling/Purge Air OptionUVS 5 (Not specified), UVS 10 (Yes, via cooling air adapter and nozzle options)
Operating Voltage Range220/240 VAC (supplied by burner control unit)
Distance to FlameUVS 5 (Max. 400 mm (16 in)), UVS 10 (300-400 mm (12-16 in); with lens: 600-1200 mm (23-47 in))
UV Tube LifetimeApproximately 10,000 operating hours
Mounting OptionsUVS 5 (Bracket attached to burner), UVS 10 (Adapter with quartz glass heat guard on 1/2 in viewing tube)
Detection MethodMax sensitivity: 210 nm ±10 nm; UV tube R16388, spectral range: 185 to 280 nm
Cable Gland SizeM20 for 7 to 13 mm cable diameter
Signal OutputDC signal, min. 1 μA
ApprovalsCE Certified, Eurasian Customs Union, REACH Regulation No. 1907/2006, China RoHS

Values retain manufacturer model qualifications. Review Honeywell specifications ↗

Part Number

Published part numbers

5 parts

Part NumberDescriptionEnquiry
KS74927869Assembly Set f.UVS BR 80 L535 R1/2Request quotation
KS74960611LINSE MIT DICHTUNG (UVS10)Request quotation
KS74960612QUARZGLASSCHEIBE MIT DICHTUNG (UVS10)Request quotation
KS74960615ADAPTER UVS1 MIT QUARZGLASRequest quotation
KS84333010UVS 5Request quotation
Manufacturer sources

https://process.honeywell.com/us/en/products/thermal-solutions/burner-management-systems/flame-detectors/uv-sensor

Last source check: 2026-11-02

UV detector · Manufacturer ownership retained; republication licence not independently confirmed

ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.

Your next project. A clear starting point.