Flame Detectors
Ultraviolet Flame Detector C7961E,F
C7961E/F provides solid-state UV flame sensing and shares the enclosure arrangement of C7061A/F for mechanical replacement.
C7961E/F provides solid-state UV flame sensing and shares the enclosure arrangement of C7061A/F for mechanical replacement. The page also retains predecessor-specific amplifier and hazardous-area approval notes. Continuous-duty supervision and each listed approval therefore need to be matched to the exact detector, amplifier and control combination.
Features & Benefits
- Storage Temperature Range
- -60 to 175 deg F (-50 to 80 deg C)
- Ambient Temperature Range
- -40 to 175 deg F (-40 to 80 deg C)
- Installation Orientation
- Horizontal, vertical, or angled; conduit opening must be 45 deg below horizontal
- Operating Voltage Range
- 120 VAC (-15%, +10%), 50/60 Hz
- Compatible Amplifiers
- R7851C Dynamic Self-Check Amplifier
- Compatible Controls
- RM7800 series, R7140, EC7810A modules
- Shutter Frequency
- 3 Hz + additional test every 5 seconds by 7800 Series control
- Pressure Ratings
- C7961E: 20 psi|C7961F: 100 psi (Viewing Window)
- Mounting Options
- C7961E: 3/4 in or 1 in NPT flange|C7961F: 1 in NPT pipe union
- Detection Method
- Ultraviolet radiation with dynamic self-check via oscillating shutter
- UV Tube Rating
- -40 deg F (-40 deg C) rated
- Signal Output
- 1.25 to 5.0 Vdc (steady flame signal)
- Housing Type
- C7961E: NEMA 4|C7961F: Explosion-proof (Class I and II hazardous locations)
- Approvals
- SIL 3 Capable, FM Approved, Swiss Re (Industrial Risk Insurers), WEEE Directive 2012/19/EU - proper disposal required, Hazardous Location Rating (C7961F) Class I, Groups C and D; Class II, Groups E, F, G
Applications
- Industrial UV flame supervision with the specified control/amplifier combination
Detailed capabilities
Replacement path and hazardous-area qualifications
The C7961E/F enclosure matches the cited C7061A/F construction for mechanical replacement. The following compatibility text still names C7061 with R7861 or the SLATE amplifier and lists the predecessor's self-checking and F1/F2 hazardous-area conditions. Mechanical similarity is therefore not evidence that all approvals transfer unchanged. The exact replacement detector, amplifier, controller and area version need their own documented combination.
Published application context
- Industrial UV flame supervision with the specified control/amplifier combination
Storage/Transport Temperatures
- Storage Temperature Range
- -60 to 175 deg F (-50 to 80 deg C)
Environmental Conditions
- Ambient Temperature Range
- -40 to 175 deg F (-40 to 80 deg C)
Installation & Mounting Specifications
- Installation Orientation
- Horizontal, vertical, or angled; conduit opening must be 45 deg below horizontal
- Mounting Options
- C7961E: 3/4 in or 1 in NPT flange; C7961F: 1 in NPT pipe union
Electrical Specifications
- Operating Voltage Range
- 120 VAC (-15%, +10%), 50/60 Hz
- Shutter Frequency
- 3 Hz + additional test every 5 seconds by 7800 Series control
Applications & Compatibility
- Compatible Amplifiers
- R7851C Dynamic Self-Check Amplifier
- Compatible Controls
- RM7800 series, R7140, EC7810A modules
Pressure Specifications
- Pressure Ratings
- C7961E: 20 psi; C7961F: 100 psi (Viewing Window)
Measurement & Sensing Characteristics
- Detection Method
- Ultraviolet radiation with dynamic self-check via oscillating shutter
Ignition, Flame & Supervision Specifications
- UV Tube Rating
- -40 deg F (-40 deg C) rated
Inputs, Outputs & Signal Interfaces
- Signal Output
- 1.25 to 5.0 Vdc (steady flame signal)
Product Design & Configuration
- Housing Type
- C7961E: NEMA 4; C7961F: Explosion-proof (Class I and II hazardous locations)
Standards & Certifications
- Approvals
- SIL 3 Capable, FM Approved, Swiss Re (Industrial Risk Insurers), WEEE Directive 2012/19/EU - proper disposal required, Hazardous Location Rating (C7961F) Class I, Groups C and D; Class II, Groups E, F, G
| Parameter | Published value / configuration |
|---|---|
| Storage Temperature Range | -60 to 175 deg F (-50 to 80 deg C) |
| Ambient Temperature Range | -40 to 175 deg F (-40 to 80 deg C) |
| Installation Orientation | Horizontal, vertical, or angled; conduit opening must be 45 deg below horizontal |
| Mounting Options | C7961E: 3/4 in or 1 in NPT flange; C7961F: 1 in NPT pipe union |
| Operating Voltage Range | 120 VAC (-15%, +10%), 50/60 Hz |
| Shutter Frequency | 3 Hz + additional test every 5 seconds by 7800 Series control |
| Compatible Amplifiers | R7851C Dynamic Self-Check Amplifier |
| Compatible Controls | RM7800 series, R7140, EC7810A modules |
| Pressure Ratings | C7961E: 20 psi; C7961F: 100 psi (Viewing Window) |
| Detection Method | Ultraviolet radiation with dynamic self-check via oscillating shutter |
| UV Tube Rating | -40 deg F (-40 deg C) rated |
| Signal Output | 1.25 to 5.0 Vdc (steady flame signal) |
| Housing Type | C7961E: NEMA 4; C7961F: Explosion-proof (Class I and II hazardous locations) |
| Approvals | SIL 3 Capable, FM Approved, Swiss Re (Industrial Risk Insurers), WEEE Directive 2012/19/EU - proper disposal required, Hazardous Location Rating (C7961F) Class I, Groups C and D; Class II, Groups E, F, G |
Values retain manufacturer model qualifications. Review Honeywell specifications ↗
Part Number
Published part numbers
1 parts
| Part Number | Description | Enquiry |
|---|---|---|
| 32005268-001/X | CABLE ASSEMBLY | Request quotation |
Manufacturer sources
Last source check: 2026-11-02
Ultraviolet Flame Detector · Manufacturer ownership retained; republication licence not independently confirmed
Ultraviolet Flame Detector · Manufacturer ownership retained; republication licence not independently confirmed
ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.
Your next project. A clear starting point.