Fire & Life Safety · Building Systems · Industrial Automation [email protected] +880 1347 561 256
Honeywell Process Measurement & Control

Flame Detectors

Ultraviolet Flame Detector C7961E,F

C7961E/F provides solid-state UV flame sensing and shares the enclosure arrangement of C7061A/F for mechanical replacement.

C7961E/F provides solid-state UV flame sensing and shares the enclosure arrangement of C7061A/F for mechanical replacement. The page also retains predecessor-specific amplifier and hazardous-area approval notes. Continuous-duty supervision and each listed approval therefore need to be matched to the exact detector, amplifier and control combination.

Features & Benefits

Storage Temperature Range
-60 to 175 deg F (-50 to 80 deg C)
Ambient Temperature Range
-40 to 175 deg F (-40 to 80 deg C)
Installation Orientation
Horizontal, vertical, or angled; conduit opening must be 45 deg below horizontal
Operating Voltage Range
120 VAC (-15%, +10%), 50/60 Hz
Compatible Amplifiers
R7851C Dynamic Self-Check Amplifier
Compatible Controls
RM7800 series, R7140, EC7810A modules
Shutter Frequency
3 Hz + additional test every 5 seconds by 7800 Series control
Pressure Ratings
C7961E: 20 psi|C7961F: 100 psi (Viewing Window)
Mounting Options
C7961E: 3/4 in or 1 in NPT flange|C7961F: 1 in NPT pipe union
Detection Method
Ultraviolet radiation with dynamic self-check via oscillating shutter
UV Tube Rating
-40 deg F (-40 deg C) rated
Signal Output
1.25 to 5.0 Vdc (steady flame signal)
Housing Type
C7961E: NEMA 4|C7961F: Explosion-proof (Class I and II hazardous locations)
Approvals
SIL 3 Capable, FM Approved, Swiss Re (Industrial Risk Insurers), WEEE Directive 2012/19/EU - proper disposal required, Hazardous Location Rating (C7961F) Class I, Groups C and D; Class II, Groups E, F, G

Applications

  • Industrial UV flame supervision with the specified control/amplifier combination

Detailed capabilities

Replacement path and hazardous-area qualifications

The C7961E/F enclosure matches the cited C7061A/F construction for mechanical replacement. The following compatibility text still names C7061 with R7861 or the SLATE amplifier and lists the predecessor's self-checking and F1/F2 hazardous-area conditions. Mechanical similarity is therefore not evidence that all approvals transfer unchanged. The exact replacement detector, amplifier, controller and area version need their own documented combination.

Manufacturer reference ↗

Published application context

  • Industrial UV flame supervision with the specified control/amplifier combination

Manufacturer reference ↗

Specifications

Storage/Transport Temperatures

Storage Temperature Range
-60 to 175 deg F (-50 to 80 deg C)

Environmental Conditions

Ambient Temperature Range
-40 to 175 deg F (-40 to 80 deg C)

Installation & Mounting Specifications

Installation Orientation
Horizontal, vertical, or angled; conduit opening must be 45 deg below horizontal
Mounting Options
C7961E: 3/4 in or 1 in NPT flange; C7961F: 1 in NPT pipe union

Electrical Specifications

Operating Voltage Range
120 VAC (-15%, +10%), 50/60 Hz
Shutter Frequency
3 Hz + additional test every 5 seconds by 7800 Series control

Applications & Compatibility

Compatible Amplifiers
R7851C Dynamic Self-Check Amplifier
Compatible Controls
RM7800 series, R7140, EC7810A modules

Pressure Specifications

Pressure Ratings
C7961E: 20 psi; C7961F: 100 psi (Viewing Window)

Measurement & Sensing Characteristics

Detection Method
Ultraviolet radiation with dynamic self-check via oscillating shutter

Ignition, Flame & Supervision Specifications

UV Tube Rating
-40 deg F (-40 deg C) rated

Inputs, Outputs & Signal Interfaces

Signal Output
1.25 to 5.0 Vdc (steady flame signal)

Product Design & Configuration

Housing Type
C7961E: NEMA 4; C7961F: Explosion-proof (Class I and II hazardous locations)

Standards & Certifications

Approvals
SIL 3 Capable, FM Approved, Swiss Re (Industrial Risk Insurers), WEEE Directive 2012/19/EU - proper disposal required, Hazardous Location Rating (C7961F) Class I, Groups C and D; Class II, Groups E, F, G
Ultraviolet Flame Detector C7961E,F — manufacturer page values
ParameterPublished value / configuration
Storage Temperature Range-60 to 175 deg F (-50 to 80 deg C)
Ambient Temperature Range-40 to 175 deg F (-40 to 80 deg C)
Installation OrientationHorizontal, vertical, or angled; conduit opening must be 45 deg below horizontal
Mounting OptionsC7961E: 3/4 in or 1 in NPT flange; C7961F: 1 in NPT pipe union
Operating Voltage Range120 VAC (-15%, +10%), 50/60 Hz
Shutter Frequency3 Hz + additional test every 5 seconds by 7800 Series control
Compatible AmplifiersR7851C Dynamic Self-Check Amplifier
Compatible ControlsRM7800 series, R7140, EC7810A modules
Pressure RatingsC7961E: 20 psi; C7961F: 100 psi (Viewing Window)
Detection MethodUltraviolet radiation with dynamic self-check via oscillating shutter
UV Tube Rating-40 deg F (-40 deg C) rated
Signal Output1.25 to 5.0 Vdc (steady flame signal)
Housing TypeC7961E: NEMA 4; C7961F: Explosion-proof (Class I and II hazardous locations)
ApprovalsSIL 3 Capable, FM Approved, Swiss Re (Industrial Risk Insurers), WEEE Directive 2012/19/EU - proper disposal required, Hazardous Location Rating (C7961F) Class I, Groups C and D; Class II, Groups E, F, G

Values retain manufacturer model qualifications. Review Honeywell specifications ↗

Part Number

Published part numbers

1 parts

Part NumberDescriptionEnquiry
32005268-001/XCABLE ASSEMBLYRequest quotation
Manufacturer sources

https://process.honeywell.com/us/en/products/thermal-solutions/burner-management-systems/flame-detectors/ultraviolet-flame-detector-c7961e-f

Last source check: 2026-11-02

Ultraviolet Flame Detector · Manufacturer ownership retained; republication licence not independently confirmed

Ultraviolet Flame Detector · Manufacturer ownership retained; republication licence not independently confirmed

ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.

Your next project. A clear starting point.

Tell us about your facility and what you need to achieve.

CallSend enquiry