Honeywell Process Measurement & Control

Flame Detectors

Ultraviolet Flame Detector C7915

Although headed as an ultraviolet product, this page describes C7915 as an infrared sensor using a lead-sulfide photocell.

Although headed as an ultraviolet product, this page describes C7915 as an infrared sensor using a lead-sulfide photocell. It monitors pilot and main flames in dual-fuel or combination service and mounts on a 3/4-inch sight pipe. Published bushing and cell identifiers differ between C7015 and C7915.

Features & Benefits

Ambient Temperature Range
-40 to 125 deg F (-40 to 52 deg C)
Field of View Control
Orifice plate (0.125 in. hexagonal), sight pipe length/diameter
Compatible Amplifiers
R7852A, R7852B (AMPLI-CHECK™)
Compatible Controls
RM7800 series, RM7823, RM7838, RM7840, RM7885, RM7890, RM7895, RM7896, RM7897, RM7898, R7140[1]
Mounting Options
3/4-14 NPSM internal threads; mounts on standard 3/4 in sight pipe
Detection Range
Infrared radiation between 0.75 and 1.0 microns
Signal Output
1.25 to 5.0 VDC (with R7852 amplifier)|1.4 to 5.5 µA (nominal)
Cable Rating
194 deg F (90 deg C), max cable length: 50 ft (15.2 m)
Sensor Type
Lead sulfide photocell (field-replaceable)
Flame Type
Natural Gas, oil, coal, dual-fuel
Cable Type
30, 48, or 96 in coaxial cable in flexible metal conduit
Approvals
SIL 3 Capable, FM Approved, Swiss Re (Industrial Risk Insurers), WEEE Directive 2012/19/EU - proper disposal required

Applications

  • Pilot and main-flame detection in combination or dual-fuel systems

Specifications

Environmental Conditions

Ambient Temperature Range
-40 to 125 deg F (-40 to 52 deg C)

Measurement, Accuracy & Sensing

Field of View Control
Orifice plate (0.125 in. hexagonal), sight pipe length/diameter
Sensor Type
Lead sulfide photocell (field-replaceable)

Applications & Compatibility

Compatible Amplifiers
R7852A, R7852B (AMPLI-CHECK™)
Compatible Controls
RM7800 series, RM7823, RM7838, RM7840, RM7885, RM7890, RM7895, RM7896, RM7897, RM7898, R7140[1]

Installation & Mounting Specifications

Mounting Options
3/4-14 NPSM internal threads; mounts on standard 3/4 in sight pipe

Processing & Performance Metrics

Detection Range
Infrared radiation between 0.75 and 1.0 microns

Inputs, Outputs & Signal Interfaces

Signal Output
1.25 to 5.0 VDC (with R7852 amplifier); 1.4 to 5.5 µA (nominal)

Mechanical Design & Hardware Details

Cable Rating
194 deg F (90 deg C), max cable length: 50 ft (15.2 m)
Cable Type
30, 48, or 96 in coaxial cable in flexible metal conduit

Ignition, Flame & Supervision Specifications

Flame Type
Natural Gas, oil, coal, dual-fuel

Standards & Certifications

Approvals
SIL 3 Capable, FM Approved, Swiss Re (Industrial Risk Insurers), WEEE Directive 2012/19/EU - proper disposal required
Ultraviolet Flame Detector C7915 — manufacturer page values
ParameterPublished value / configuration
Ambient Temperature Range-40 to 125 deg F (-40 to 52 deg C)
Field of View ControlOrifice plate (0.125 in. hexagonal), sight pipe length/diameter
Sensor TypeLead sulfide photocell (field-replaceable)
Compatible AmplifiersR7852A, R7852B (AMPLI-CHECK™)
Compatible ControlsRM7800 series, RM7823, RM7838, RM7840, RM7885, RM7890, RM7895, RM7896, RM7897, RM7898, R7140[1]
Mounting Options3/4-14 NPSM internal threads; mounts on standard 3/4 in sight pipe
Detection RangeInfrared radiation between 0.75 and 1.0 microns
Signal Output1.25 to 5.0 VDC (with R7852 amplifier); 1.4 to 5.5 µA (nominal)
Cable Rating194 deg F (90 deg C), max cable length: 50 ft (15.2 m)
Cable Type30, 48, or 96 in coaxial cable in flexible metal conduit
Flame TypeNatural Gas, oil, coal, dual-fuel
ApprovalsSIL 3 Capable, FM Approved, Swiss Re (Industrial Risk Insurers), WEEE Directive 2012/19/EU - proper disposal required

Values retain manufacturer model qualifications. Review Honeywell specifications ↗

Part Number

Published part numbers

4 parts

Part NumberDescriptionEnquiry
C7915A1010/UIR FLAME SENSORRequest quotation
C7915A1028/UIR FLAME SENSORRequest quotation
C7915A1036/UIR FLAME SENSORRequest quotation
C7915A1044/UIR DETECTORRequest quotation
Manufacturer sources

https://process.honeywell.com/us/en/products/thermal-solutions/burner-management-systems/flame-detectors/ultraviolet-flame-detector-c7915

Last source check: 2026-11-02

Ultraviolet Flame Detector · Manufacturer ownership retained; republication licence not independently confirmed