Pilot for Gas Pressure Regulators
HON 658-DP
HON 658-DP uses independently set lower and upper outlet-pressure stages around a differential-pressure control stage.
HON 658-DP uses independently set lower and upper outlet-pressure stages around a differential-pressure control stage. Control transfers automatically between these functions as conditions change. Its modular arrangement includes load limiting, gauges and an upstream fine filter, with optional outlet gauging and venting to suit the gas regulating station.
Models: HON 658-DP
Features & Benefits
- Stages
- Lower outlet limit, upper outlet limit and differential pressure
- Transition
- Automatic
- Controls differential pressure within independently set outlet limits
Applications
- Gas pressure and differential-pressure control
Detailed capabilities
HON 658-DP — operating design
HON 658-DP uses independently set lower and upper outlet-pressure stages around a differential-pressure control stage. Control transfers automatically between these functions as conditions change. Its modular arrangement includes load limiting, gauges and an upstream fine filter, with optional outlet gauging and venting to suit the gas regulating station.
Independent pressure limits and differential control
Two outlet stages are set independently to a low and a high boundary, with a differential stage operating between them. Automatic transfer links these functions with modular load limiting. The source lists 0.3–90 bar for each outlet stage, 0.05–1.2 bar for differential pressure and loading 0.5–15 bar above the outlet, keeping those quantities distinct.
Published configuration and technical facts
The manufacturer lists these values for HON 658-DP. Version, size and option qualifications remain attached to each fact.
- Maximum Admissible Pressure: 100 bar
- Differential Pressure Range: 0.05 to 1.2 bar
- Outlet Pressure Range: Wd: 0.3 to 90 bar
- Inlet Pressure Range: 100 bar
- Auxiliary Energy: 24 VDC, max. 1.5 A (for HON 110a modulator)
- Approvals: CE Mark with PED, DIN EN 334
- Load-Limiting Stage: 0.5 to 15 bar
- Output Signal: Pulse Signal 24 Vss, Short Circuit-Proof
- Input Signal: 0/4 to 20 mA or 0 to 10 V
Processing & Performance Metrics
- Maximum Admissible Pressure
- 100 bar
Technical Specifications
- Differential Pressure Range
- 0.05 to 1.2 bar
Environmental Conditions
- Outlet Pressure Range
- Wd: 0.3 to 90 bar
- Inlet Pressure Range
- 100 bar
- Auxiliary Energy
- 24 VDC, max. 1.5 A (for HON 110a modulator)
Standards & Certifications
- Explosion Protection
- All mechanical components of this device are without potential ignition sources and/or hot faces. They are not subject to ATEX 95 (94/9/EC). All electronic accessories, on the other hand, meet ATEX requirements.
- Approvals
- CE Mark with PED, DIN EN 334
Mechanical & Physical Properties
- Load-Limiting Stage
- 0.5 to 15 bar
Electrical Specifications
- Output Signal
- Pulse Signal 24 Vss, Short Circuit-Proof
- Input Signal
- 0/4 to 20 mA or 0 to 10 V
Applications & Compatibility
- Applications
- Pilot for gas pressure regulators. Suitable for non-aggressive gases, other gases on enquiry
| Parameter | Published value / configuration |
|---|---|
| Maximum Admissible Pressure | 100 bar |
| Differential Pressure Range | 0.05 to 1.2 bar |
| Outlet Pressure Range | Wd: 0.3 to 90 bar |
| Inlet Pressure Range | 100 bar |
| Auxiliary Energy | 24 VDC, max. 1.5 A (for HON 110a modulator) |
| Explosion Protection | All mechanical components of this device are without potential ignition sources and/or hot faces. They are not subject to ATEX 95 (94/9/EC). All electronic accessories, on the other hand, meet ATEX requirements. |
| Approvals | CE Mark with PED, DIN EN 334 |
| Load-Limiting Stage | 0.5 to 15 bar |
| Output Signal | Pulse Signal 24 Vss, Short Circuit-Proof |
| Input Signal | 0/4 to 20 mA or 0 to 10 V |
| Applications | Pilot for gas pressure regulators. Suitable for non-aggressive gases, other gases on enquiry |
Values retain manufacturer model qualifications. Review Honeywell specifications ↗
Resources
Resources linked from the manufacturer’s page. Confirm the document revision and applicable model before installation or ordering.
Honeywell resource listing ↗Part Number
Published model / variant identifiers. A full ordering code requires the manufacturer configuration.
Published part numbers
1 parts
| Part Number | Description | Enquiry |
|---|---|---|
| HON658 | Pilot HON 658 | Request quotation |
Manufacturer sources
Last source check: 2026-11-02
HON 658-DP Image · Manufacturer ownership retained; republication licence not independently confirmed
ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.
Your next project. A clear starting point.