Commercial & Industrial Meters
ALPHA® 4 CI METER
ALPHA 4 CI combines four-quadrant revenue metering with load and instrumentation profiles for commercial and industrial sites.
ALPHA 4 CI combines four-quadrant revenue metering with load and instrumentation profiles for commercial and industrial sites. Power-quality monitoring is standard, including continuous tests against configured thresholds. The platform records voltage sag and swell events and supports edge processing, giving utilities local measurement and diagnostic information without adding separate option boards for the stated functions.
Models: ALPHA® 4 CI METER
Features & Benefits
- Revenue
- Four-quadrant measurement
- Monitoring
- Standard power-quality monitoring
- Records
- Voltage sag/swell and profiles
- Advanced measurement functions without additional hardware option boards
Applications
- Commercial and industrial electricity metering
Detailed capabilities
ALPHA® 4 CI METER — product role
ALPHA 4 CI combines four-quadrant revenue metering with load and instrumentation profiles for commercial and industrial sites. Power-quality monitoring is standard, including continuous tests against configured thresholds. The platform records voltage sag and swell events and supports edge processing, giving utilities local measurement and diagnostic information without adding separate option boards for the stated functions.
Continuous power-quality checks
A4CI runs twenty-three quality tests every two hundred milliseconds against configurable limits for quantities such as voltage, current and distortion. Tests work independently from energy measurement. Results can create LCD warnings, time-stamped logs or messages to a network interface; open-neutral indication is qualified to form2S service. Sag/swell and four-quadrant revenue functions are integrated without the stated extra option boards.
Interfaces, security and event history
An optical port is standard and additional communication boards are optional. Motion and magnetic-tamper detection accompany ANSI C12.22 communication protected by 128-bit encryption, including the optical port. Event and history logs each hold one thousand entries. A legally relevant parameter log is identified from metrology version3.0, with MeterCat providing configuration context.
Memory, self reads and instrumentation profiles
A4CI has sixteen megabytes of nonvolatile storage, up to forty self reads and 366 midnight register snapshots. Instrumentation profiling supports up to thirty-two channels and 86,400 one-minute intervals, or sixty days. More than sixty quantities are available, with independently chosen minimum, maximum, average or interval-end algorithms where supported. The head end can receive aggregated profile information.
Data & Storage
- Memory
- 16 MB non-volatile
- Midnight Snapshots
- 366
- Load Profiling
- 1-minute interval, up to 60 days
- Log Entries
- 1000 PQM + 1000 sag/swell entries
- Self Reads
- Up to 40
Communication
- Communication Rates
- Optical port: 28,800 bps, Remote port: 115,200 bps
Operating Conditions
- Temperature Range
- -40 to +85 deg C
- Power Consumption
- <1 W (meter), up to 10 W with radios
- Voltage Range
- 120 to 480 V (up to 528 VAC)
Electrical
- Starting Current
- Class 20: 10 mA; Class 200: 100 mA; Class 320: 160 mA
- Current Range
- 0 to class amperes
Metering
- Revenue Metering
- Four-quadrant metering
Measurement & Data
- Energy Registers
- kWh, kVARh, kVAh (Delivered, Received, Net, Sum)
- Demand Registers
- kW, kVAR, kVA
Electrical Characteristics
- Frequency Range
- 50/60 Hz ±2%
Security
- Data Encryption
- 128-bit (ANSI C12.22)
General Overview
- Applications
- Advanced grid applications, real-time insights
Time & Clock
- RTC Backup
- 8 hours during outage
Power Quality
- Monitoring
- Continuous 24/7 monitoring
Hardware
- Processor
- ARM dual-core, 100 MHz
Safety & Compliance
- Approvals
- ANSI C12.1, C12.10, C12.20, C12.21, C12.22
Environmental
- Humidity
- 0 to 100% non-condensing
Performance
- Accuracy
- Class 0.2% (ANSI C12.20)
| Parameter | Published value / configuration |
|---|---|
| Memory | 16 MB non-volatile |
| Midnight Snapshots | 366 |
| Load Profiling | 1-minute interval, up to 60 days |
| Log Entries | 1000 PQM + 1000 sag/swell entries |
| Self Reads | Up to 40 |
| Communication Rates | Optical port: 28,800 bps, Remote port: 115,200 bps |
| Temperature Range | -40 to +85 deg C |
| Power Consumption | <1 W (meter), up to 10 W with radios |
| Voltage Range | 120 to 480 V (up to 528 VAC) |
| Starting Current | Class 20: 10 mA; Class 200: 100 mA; Class 320: 160 mA |
| Current Range | 0 to class amperes |
| Revenue Metering | Four-quadrant metering |
| Energy Registers | kWh, kVARh, kVAh (Delivered, Received, Net, Sum) |
| Demand Registers | kW, kVAR, kVA |
| Frequency Range | 50/60 Hz ±2% |
| Data Encryption | 128-bit (ANSI C12.22) |
| Applications | Advanced grid applications, real-time insights |
| RTC Backup | 8 hours during outage |
| Monitoring | Continuous 24/7 monitoring |
| Processor | ARM dual-core, 100 MHz |
| Approvals | ANSI C12.1, C12.10, C12.20, C12.21, C12.22 |
| Humidity | 0 to 100% non-condensing |
| Accuracy | Class 0.2% (ANSI C12.20) |
Values retain manufacturer model qualifications. Review Honeywell specifications ↗
Resources
Resources linked from the manufacturer’s page. Confirm the document revision and applicable model before installation or ordering.
Honeywell resource listing ↗Part Number
Published model / variant identifiers. A full ordering code requires the manufacturer configuration.
Published part numbers
1 parts
| Part Number | Description | Enquiry |
|---|---|---|
| A4CI | HONEYWELL A4 C&I METER | Request quotation |
Manufacturer sources
Last source check: 2026-11-02
A4CI product image · Manufacturer ownership retained; republication licence not independently confirmed
ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.
Your next project. A clear starting point.
Tell us about your facility and what you need to achieve.