Pressure Switches & Gauges
PressureTrol® Pressure monitoring on/off controllers L404F, T, V
L404 PressureTrol provides automatic-reset pressure switching with adjustable differential.
L404 PressureTrol provides automatic-reset pressure switching with adjustable differential. L404F addresses the stated pressure-system media, while T and V serve oil burners with different high- and low-pressure actions. A clear cover exposes the settings, and the page publishes distinct system-pressure limits for the general and oil-burner groups.
Features & Benefits
- Maximum Diaphragm Pressure
- Up to 350 psi (2410 kPa)
- Ambient Temperature Limits
- Max 150 deg F (66 deg C)
- Operating Pressure Range
- 10 to 150 psi|2 to 15 psi|20 to 300 psi (model dependent)|5 to 50 psi
- Maximum System Pressure
- L404F: Up to 300 psi (2070 kPa)|L404T/L404V: Up to 150 psi (1035 kPa)
- Maintenance Interval
- Occasional scaleplate adjustment; annual checkout recommended
- Differential Range
- Adjustable; varies by model (e.g., 2 to 6 psi, 6 to 14 psi, 20 to 50 psi)
- Electrical Rating
- 120 VAC: 8.0 A (Full Load), 48.0 A (Locked Rotor)|240 VAC: 5.1 A (Full Load), 30.6 A (Locked Rotor)
- Control Functions
- Operating control with automatic reset
- Conduit Entries
- Knockouts for 1/2 in conduit
- Mounting Types
- 1/4-18 NPT pipe fitting or surface mount via case knockouts
- Switch Action
- Snap switch: breaks R-B, makes R-W on pressure rise
- Switch Type
- MicroSwitch® snap‑acting switch
- Reset Type
- Automatic reset
- Approvals
- UL Listed (MP466), CSA Approved (LR1620), WEEE Directive 2012/19/EU - Waste Electrical and Electronic Equipment Directive
- Material
- Rigid case with clear plastic cover
- Automatic reset and adjustable differential support pressure cycling.
Applications
- Pressure-system operating/limit control
- Oil-burner pressure supervision with T/V variants
Detailed capabilities
Different switch actions for process and oil duty
L404F provides operating control and automatic pressure limiting for the stated process media. L404T opens on excessive oil pressure, while L404V makes its circuit as oil pressure rises from a low-pressure condition. All reset automatically and have adjustable differential. The higher general-system pressure capability must not be assigned to the lower-pressure oil versions.
Features and benefits
- Automatic reset and adjustable differential support pressure cycling.
Published application context
- Pressure-system operating/limit control
- Oil-burner pressure supervision with T/V variants
Overview
- Models
- L404F, L404T, L404V
Pressure Specifications
- Maximum Diaphragm Pressure
- Up to 350 psi (2410 kPa)
- Operating Pressure Range
- 10 to 150 psi; 2 to 15 psi; 20 to 300 psi (model dependent); 5 to 50 psi
- Maximum System Pressure
- L404F: Up to 300 psi (2070 kPa); L404T/L404V: Up to 150 psi (1035 kPa)
Environmental Conditions
- Ambient Temperature Limits
- Max 150 deg F (66 deg C)
Electrical Specifications
- Maintenance Interval
- Occasional scaleplate adjustment; annual checkout recommended
Measurement, Media & Physical Properties
- Differential Range
- Adjustable; varies by model (e.g., 2 to 6 psi, 6 to 14 psi, 20 to 50 psi)
Electrical & Signal Specifications
- Electrical Rating
- 120 VAC: 8.0 A (Full Load), 48.0 A (Locked Rotor); 240 VAC: 5.1 A (Full Load), 30.6 A (Locked Rotor)
Control, Logic & Functional Behavior
- Control Functions
- Operating control with automatic reset
Mechanical Design, Layout & Construction Options
- Conduit Entries
- Knockouts for 1/2 in conduit
Installation & Mounting Specifications
- Mounting Types
- 1/4-18 NPT pipe fitting or surface mount via case knockouts
Actuation, Control & Motion Characteristics
- Switch Action
- Snap switch: breaks R-B, makes R-W on pressure rise
- Switch Type
- MicroSwitch® snap‑acting switch
Applications & Compatibility
- Applications
- L404F: Steam, air, non‑combustible gases, non‑corrosive fluids; L404T: High oil pressure limit (breaks circuit on pressure rise); L404V: Low oil pressure limit (makes circuit on pressure rise)
Safety, Protection & Reliability
- Reset Type
- Automatic reset
Standards & Certifications
- Approvals
- UL Listed (MP466), CSA Approved (LR1620), WEEE Directive 2012/19/EU - Waste Electrical and Electronic Equipment Directive
Material Specifications
- Material
- Rigid case with clear plastic cover
| Parameter | Published value / configuration |
|---|---|
| Models | L404F, L404T, L404V |
| Maximum Diaphragm Pressure | Up to 350 psi (2410 kPa) |
| Operating Pressure Range | 10 to 150 psi; 2 to 15 psi; 20 to 300 psi (model dependent); 5 to 50 psi |
| Maximum System Pressure | L404F: Up to 300 psi (2070 kPa); L404T/L404V: Up to 150 psi (1035 kPa) |
| Ambient Temperature Limits | Max 150 deg F (66 deg C) |
| Maintenance Interval | Occasional scaleplate adjustment; annual checkout recommended |
| Differential Range | Adjustable; varies by model (e.g., 2 to 6 psi, 6 to 14 psi, 20 to 50 psi) |
| Electrical Rating | 120 VAC: 8.0 A (Full Load), 48.0 A (Locked Rotor); 240 VAC: 5.1 A (Full Load), 30.6 A (Locked Rotor) |
| Control Functions | Operating control with automatic reset |
| Conduit Entries | Knockouts for 1/2 in conduit |
| Mounting Types | 1/4-18 NPT pipe fitting or surface mount via case knockouts |
| Switch Action | Snap switch: breaks R-B, makes R-W on pressure rise |
| Switch Type | MicroSwitch® snap‑acting switch |
| Applications | L404F: Steam, air, non‑combustible gases, non‑corrosive fluids; L404T: High oil pressure limit (breaks circuit on pressure rise); L404V: Low oil pressure limit (makes circuit on pressure rise) |
| Reset Type | Automatic reset |
| Approvals | UL Listed (MP466), CSA Approved (LR1620), WEEE Directive 2012/19/EU - Waste Electrical and Electronic Equipment Directive |
| Material | Rigid case with clear plastic cover |
Values retain manufacturer model qualifications. Review Honeywell specifications ↗
Part Number
Published part numbers
10 parts
| Part Number | Description | Enquiry |
|---|---|---|
| 4074BWJ/U | LIMIT STOP ASSEMBLY FOR L404/L604. INCL | Request quotation |
| EC16072 | SW,PRESS,AIR/GAS,LO,MAN RST,1 26 IN.WC,N | Request quotation |
| EC16118 | SW,PRESS,AIR/GAS,LO,MAN RST,0.5 5 PSI,NE | Request quotation |
| L404F1060/U | PRESSURETROL | Request quotation |
| L404F1078/U | PRESSURETROL | Request quotation |
| L404F1094/U | PRESSURE SWITCH | Request quotation |
| L404F1102/U | 10-150PSI PRESSURETOL | Request quotation |
| L404F1219/U | PRESSURETROL 2-15PSI | Request quotation |
| L404F1227/U | PRESSURETROL | Request quotation |
| L404F1235/U | PRESSURETROL 20-300PSI | Request quotation |
Manufacturer sources
Last source check: 2026-11-02
PressureTrol® Pressure monitoring on/off controllers · Manufacturer ownership retained; republication licence not independently confirmed
ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.
Your next project. A clear starting point.
Tell us about your facility and what you need to achieve.