Pressure Switches & Gauges
Kromschroeder DG pressure switches for gas
DG and US-market DG..T monitor positive gas/air pressure or negative/differential air and flue-gas pressure.
DG and US-market DG..T monitor positive gas/air pressure or negative/differential air and flue-gas pressure. Both use dial adjustment, but pressure scales, contacts, connections and approvals differ by region. Optional locking/manual reset belongs to the stated arrangement; accessory links also identify specialized negative-pressure and oxygen/ammonia variants separately.
Features & Benefits
- Adjusting Range
- Approximately 0.5 up to 500 mbar (model‑dependent)
- Temperature Rating
- -15 to +60 deg C (others)|-20 to +80 deg C (DG, DG..U, DG..I)|-40 to +60 deg C (DG..T)
- Reset Options
- Manual reset for lock-off models
- Protection Class
- IP54/IP65 (DG), NEMA 4 (DG..T)
- Product Type
- Diaphragm pressure switch for gas and air
- Primary Function
- Monitoring and switching of gas and air pressures
- Media Compatibility
- Natural Gas, Town Gas, LPG (gaseous), Flue Gas, Biogas (≤ 0.1% H₂S), Air
- Mechanical Connection
- Rp 1/4 in, Rp 1/8 in (DG); 1/4 in NPT/1/8 in NPT (DG..T)
- Material
- PBT plastic (glass fiber reinforced), aluminum lower section
- Maintenance Interval
- At least once per year (twice per year for biogas)
- Installation Orientation
- Vertical, horizontal, or inverted (switching point must be verified)
- Hazardous Area Use
- Suitable for Zone 1 and 2 with isolating amplifier; Zone 2 without amplifier
- Electrical Connections
- Screw terminals, M16 cable gland, 1/2 in NPT conduit, 4-pin plug/socket
- Diaphragm Material
- NBR (standard), IIR (DG..S, DG..ST)
- Designed Lifetime
- Up to 10 years or specified switching cycles (model‑dependent)
- Approvals
- EN 1854, Gas Appliances Regulation (EU) 2016/426, CE (EN 1854), SIL 3 (EN 61508), PL e (ISO 13849), FM, UL, AGA Approved (except DG..S), Eurasian Customs Union
- Range
- 0.4 to 500 mbar (0.16 to 200 WC)
- Pneumatic Connections
- Internal Rp 1/8 2x, Rp 1/4 2x
- Electrical connection
- Screw terminals, M16x1.5 cable gland 4-Pin plug and socket
- Regional versions provide the appropriate contact and connection formats.
Applications
- Positive gas/air supervision
- Negative or differential air/flue-gas supervision
Detailed capabilities
DG and DG..T are regional variants
The DG version addresses the European market with its stated EU/AGA/EAC qualifications; DG..T addresses the US market with UL/FM qualifications. Both use a dial-set switching point and silicone-free construction. Their pressure scales, electrical contacts and pipe interfaces differ. The European contact values cannot be applied to the US version merely because the two share a family name.
Media and pressure direction matter
Positive-pressure service includes the listed gas, air and flue-gas media. Negative and differential service is described for air and flue gas. Specialized negative-pressure and oxygen/ammonia products appear as separate selection links, not as a blanket extension of every DG model. DG..T also has a stated locking/manual-reset option, with wiring chosen from the published gland, conduit or plug arrangements.
Features and benefits
- Regional versions provide the appropriate contact and connection formats.
Published application context
- Positive gas/air supervision
- Negative or differential air/flue-gas supervision
Technical facts in the product overview
- Range: 0.4 to 500 mbar (0.16 to 200 WC)
- Pneumatic Connections: Internal Rp 1/8 2x, Rp 1/4 2x
- Electrical connection: Screw terminals, M16x1.5 cable gland 4-Pin plug and socket
Processing & Performance Metrics
- Adjusting Range
- Approximately 0.5 up to 500 mbar (model‑dependent)
Temperature Control/Measurement
- Temperature Rating
- -15 to +60 deg C (others); -20 to +80 deg C (DG, DG..U, DG..I); -40 to +60 deg C (DG..T)
Safety, Protection & Reliability
- Reset Options
- Manual reset for lock-off models
- Protection Class
- IP54/IP65 (DG), NEMA 4 (DG..T)
Overview
- Product Type
- Diaphragm pressure switch for gas and air
Product Overview & Classification
- Primary Function
- Monitoring and switching of gas and air pressures
Applications & Compatibility
- Media Compatibility
- Natural Gas, Town Gas, LPG (gaseous), Flue Gas, Biogas (≤ 0.1% H₂S), Air
- Hazardous Area Use
- Suitable for Zone 1 and 2 with isolating amplifier; Zone 2 without amplifier
- Applications
- Low/High Gas Pressure Monitoring, Fan Monitoring, Filter Monitoring, Leak Tightness Checks, Differential Pressure Monitoring
Connections & Interfaces
- Mechanical Connection
- Rp 1/4 in, Rp 1/8 in (DG); 1/4 in NPT/1/8 in NPT (DG..T)
- Electrical Connections
- Screw terminals, M16 cable gland, 1/2 in NPT conduit, 4-pin plug/socket
Material Specifications
- Material
- PBT plastic (glass fiber reinforced), aluminum lower section
- Diaphragm Material
- NBR (standard), IIR (DG..S, DG..ST)
Electrical Specifications
- Maintenance Interval
- At least once per year (twice per year for biogas)
Installation & Mounting Specifications
- Installation Orientation
- Vertical, horizontal, or inverted (switching point must be verified)
Operating Limits, Durability & Lifecycle
- Designed Lifetime
- Up to 10 years or specified switching cycles (model‑dependent)
Standards & Certifications
- Approvals
- EN 1854, Gas Appliances Regulation (EU) 2016/426, CE (EN 1854), SIL 3 (EN 61508), PL e (ISO 13849), FM, UL, AGA Approved (except DG..S), Eurasian Customs Union
Technical Specifications
- Range
- 0.4 to 500 mbar (0.16 to 200 WC)
- Pneumatic Connections
- Internal Rp 1/8 2x, Rp 1/4 2x
- Electrical connection
- Screw terminals, M16x1.5 cable gland 4-Pin plug and socket
| Parameter | Published value / configuration |
|---|---|
| Adjusting Range | Approximately 0.5 up to 500 mbar (model‑dependent) |
| Temperature Rating | -15 to +60 deg C (others); -20 to +80 deg C (DG, DG..U, DG..I); -40 to +60 deg C (DG..T) |
| Reset Options | Manual reset for lock-off models |
| Protection Class | IP54/IP65 (DG), NEMA 4 (DG..T) |
| Product Type | Diaphragm pressure switch for gas and air |
| Primary Function | Monitoring and switching of gas and air pressures |
| Media Compatibility | Natural Gas, Town Gas, LPG (gaseous), Flue Gas, Biogas (≤ 0.1% H₂S), Air |
| Hazardous Area Use | Suitable for Zone 1 and 2 with isolating amplifier; Zone 2 without amplifier |
| Applications | Low/High Gas Pressure Monitoring, Fan Monitoring, Filter Monitoring, Leak Tightness Checks, Differential Pressure Monitoring |
| Mechanical Connection | Rp 1/4 in, Rp 1/8 in (DG); 1/4 in NPT/1/8 in NPT (DG..T) |
| Electrical Connections | Screw terminals, M16 cable gland, 1/2 in NPT conduit, 4-pin plug/socket |
| Material | PBT plastic (glass fiber reinforced), aluminum lower section |
| Diaphragm Material | NBR (standard), IIR (DG..S, DG..ST) |
| Maintenance Interval | At least once per year (twice per year for biogas) |
| Installation Orientation | Vertical, horizontal, or inverted (switching point must be verified) |
| Designed Lifetime | Up to 10 years or specified switching cycles (model‑dependent) |
| Approvals | EN 1854, Gas Appliances Regulation (EU) 2016/426, CE (EN 1854), SIL 3 (EN 61508), PL e (ISO 13849), FM, UL, AGA Approved (except DG..S), Eurasian Customs Union |
| Range | 0.4 to 500 mbar (0.16 to 200 WC) |
| Pneumatic Connections | Internal Rp 1/8 2x, Rp 1/4 2x |
| Electrical connection | Screw terminals, M16x1.5 cable gland 4-Pin plug and socket |
Values retain manufacturer model qualifications. Review Honeywell specifications ↗
Part Number
Published part numbers
10 parts
| Part Number | Description | Enquiry |
|---|---|---|
| 1187121 | KRM SCHRDR DG .4-4"WC AUT RST PRESS SW | Request quotation |
| 326080Q | DIFF.PR.SW DG6UG IP65 W/CONN | Request quotation |
| 326081Q | DIFF.PR.SW DG10UG IP65 W/CONN | Request quotation |
| 326082Q | DIFF.PR.SW DG50UG IP65 W/CONN | Request quotation |
| 326083Q | DIF.PR.SW DG150UG IP65 W/CONN | Request quotation |
| 326084Q | DIF.P.SW DG500UG-5Z IP65 W/CON | Request quotation |
| 326131Q | DIFF.PR.SW. DG 6U IP65 w/CONN | Request quotation |
| 326132Q | DIFF.PR.SW. DG 10U IP65 w/CONN | Request quotation |
| 326134Q | DIFF.PR.SW. DG 50U IP65 w/CONN | Request quotation |
| 326135Q | DIFF.PR.SW. DG 150U IP65 w/CNN | Request quotation |
Manufacturer sources
Last source check: 2026-11-02
Pressure switch · Manufacturer ownership retained; republication licence not independently confirmed
Front image used for DG 6 in mono 319 x 343 · Manufacturer ownership retained; republication licence not independently confirmed
Front image used for DG H N in mono 319 x 343 · Manufacturer ownership retained; republication licence not independently confirmed
Front image used for DG B in mono 319 x 343 · Manufacturer ownership retained; republication licence not independently confirmed
Front image used for DG 4 in mono 319 x 343 · Manufacturer ownership retained; republication licence not independently confirmed
Kromschroeder DG · Site owner attests manufacturer permission; licence not independently audited
ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.
Your next project. A clear starting point.
Tell us about your facility and what you need to achieve.