DG and US-market DG..T monitor positive gas/air pressure or negative/differential air and flue-gas pressure.

DG and US-market DG..T monitor positive gas/air pressure or negative/differential air and flue-gas pressure. Both use dial adjustment, but pressure scales, contacts, connections and approvals differ by region. Optional locking/manual reset belongs to the stated arrangement; accessory links also identify specialized negative-pressure and oxygen/ammonia variants separately.

Features & Benefits

Adjusting Range
Approximately 0.5 up to 500 mbar (model‑dependent)
Temperature Rating
-15 to +60 deg C (others)|-20 to +80 deg C (DG, DG..U, DG..I)|-40 to +60 deg C (DG..T)
Reset Options
Manual reset for lock-off models
Protection Class
IP54/IP65 (DG), NEMA 4 (DG..T)
Product Type
Diaphragm pressure switch for gas and air
Primary Function
Monitoring and switching of gas and air pressures
Media Compatibility
Natural Gas, Town Gas, LPG (gaseous), Flue Gas, Biogas (≤ 0.1% H₂S), Air
Mechanical Connection
Rp 1/4 in, Rp 1/8 in (DG); 1/4 in NPT/1/8 in NPT (DG..T)
Material
PBT plastic (glass fiber reinforced), aluminum lower section
Maintenance Interval
At least once per year (twice per year for biogas)
Installation Orientation
Vertical, horizontal, or inverted (switching point must be verified)
Hazardous Area Use
Suitable for Zone 1 and 2 with isolating amplifier; Zone 2 without amplifier
Electrical Connections
Screw terminals, M16 cable gland, 1/2 in NPT conduit, 4-pin plug/socket
Diaphragm Material
NBR (standard), IIR (DG..S, DG..ST)
Designed Lifetime
Up to 10 years or specified switching cycles (model‑dependent)
Approvals
EN 1854, Gas Appliances Regulation (EU) 2016/426, CE (EN 1854), SIL 3 (EN 61508), PL e (ISO 13849), FM, UL, AGA Approved (except DG..S), Eurasian Customs Union
Range
0.4 to 500 mbar (0.16 to 200 WC)
Pneumatic Connections
Internal Rp 1/8 2x, Rp 1/4 2x
Electrical connection
Screw terminals, M16x1.5 cable gland 4-Pin plug and socket
  • Regional versions provide the appropriate contact and connection formats.

Applications

  • Positive gas/air supervision
  • Negative or differential air/flue-gas supervision

Detailed capabilities

DG and DG..T are regional variants

The DG version addresses the European market with its stated EU/AGA/EAC qualifications; DG..T addresses the US market with UL/FM qualifications. Both use a dial-set switching point and silicone-free construction. Their pressure scales, electrical contacts and pipe interfaces differ. The European contact values cannot be applied to the US version merely because the two share a family name.

Manufacturer reference ↗

Media and pressure direction matter

Positive-pressure service includes the listed gas, air and flue-gas media. Negative and differential service is described for air and flue gas. Specialized negative-pressure and oxygen/ammonia products appear as separate selection links, not as a blanket extension of every DG model. DG..T also has a stated locking/manual-reset option, with wiring chosen from the published gland, conduit or plug arrangements.

Manufacturer reference ↗

Features and benefits

  • Regional versions provide the appropriate contact and connection formats.

Manufacturer reference ↗

Published application context

  • Positive gas/air supervision
  • Negative or differential air/flue-gas supervision

Manufacturer reference ↗

Technical facts in the product overview

  • Range: 0.4 to 500 mbar (0.16 to 200 WC)
  • Pneumatic Connections: Internal Rp 1/8 2x, Rp 1/4 2x
  • Electrical connection: Screw terminals, M16x1.5 cable gland 4-Pin plug and socket

Manufacturer reference ↗

Specifications

Processing & Performance Metrics

Adjusting Range
Approximately 0.5 up to 500 mbar (model‑dependent)

Temperature Control/Measurement

Temperature Rating
-15 to +60 deg C (others); -20 to +80 deg C (DG, DG..U, DG..I); -40 to +60 deg C (DG..T)

Safety, Protection & Reliability

Reset Options
Manual reset for lock-off models
Protection Class
IP54/IP65 (DG), NEMA 4 (DG..T)

Overview

Product Type
Diaphragm pressure switch for gas and air

Product Overview & Classification

Primary Function
Monitoring and switching of gas and air pressures

Applications & Compatibility

Media Compatibility
Natural Gas, Town Gas, LPG (gaseous), Flue Gas, Biogas (≤ 0.1% H₂S), Air
Hazardous Area Use
Suitable for Zone 1 and 2 with isolating amplifier; Zone 2 without amplifier
Applications
Low/High Gas Pressure Monitoring, Fan Monitoring, Filter Monitoring, Leak Tightness Checks, Differential Pressure Monitoring

Connections & Interfaces

Mechanical Connection
Rp 1/4 in, Rp 1/8 in (DG); 1/4 in NPT/1/8 in NPT (DG..T)
Electrical Connections
Screw terminals, M16 cable gland, 1/2 in NPT conduit, 4-pin plug/socket

Material Specifications

Material
PBT plastic (glass fiber reinforced), aluminum lower section
Diaphragm Material
NBR (standard), IIR (DG..S, DG..ST)

Electrical Specifications

Maintenance Interval
At least once per year (twice per year for biogas)

Installation & Mounting Specifications

Installation Orientation
Vertical, horizontal, or inverted (switching point must be verified)

Operating Limits, Durability & Lifecycle

Designed Lifetime
Up to 10 years or specified switching cycles (model‑dependent)

Standards & Certifications

Approvals
EN 1854, Gas Appliances Regulation (EU) 2016/426, CE (EN 1854), SIL 3 (EN 61508), PL e (ISO 13849), FM, UL, AGA Approved (except DG..S), Eurasian Customs Union

Technical Specifications

Range
0.4 to 500 mbar (0.16 to 200 WC)
Pneumatic Connections
Internal Rp 1/8 2x, Rp 1/4 2x
Electrical connection
Screw terminals, M16x1.5 cable gland 4-Pin plug and socket
Kromschroeder DG pressure switches for gas — manufacturer page values
ParameterPublished value / configuration
Adjusting RangeApproximately 0.5 up to 500 mbar (model‑dependent)
Temperature Rating-15 to +60 deg C (others); -20 to +80 deg C (DG, DG..U, DG..I); -40 to +60 deg C (DG..T)
Reset OptionsManual reset for lock-off models
Protection ClassIP54/IP65 (DG), NEMA 4 (DG..T)
Product TypeDiaphragm pressure switch for gas and air
Primary FunctionMonitoring and switching of gas and air pressures
Media CompatibilityNatural Gas, Town Gas, LPG (gaseous), Flue Gas, Biogas (≤ 0.1% H₂S), Air
Hazardous Area UseSuitable for Zone 1 and 2 with isolating amplifier; Zone 2 without amplifier
ApplicationsLow/High Gas Pressure Monitoring, Fan Monitoring, Filter Monitoring, Leak Tightness Checks, Differential Pressure Monitoring
Mechanical ConnectionRp 1/4 in, Rp 1/8 in (DG); 1/4 in NPT/1/8 in NPT (DG..T)
Electrical ConnectionsScrew terminals, M16 cable gland, 1/2 in NPT conduit, 4-pin plug/socket
MaterialPBT plastic (glass fiber reinforced), aluminum lower section
Diaphragm MaterialNBR (standard), IIR (DG..S, DG..ST)
Maintenance IntervalAt least once per year (twice per year for biogas)
Installation OrientationVertical, horizontal, or inverted (switching point must be verified)
Designed LifetimeUp to 10 years or specified switching cycles (model‑dependent)
ApprovalsEN 1854, Gas Appliances Regulation (EU) 2016/426, CE (EN 1854), SIL 3 (EN 61508), PL e (ISO 13849), FM, UL, AGA Approved (except DG..S), Eurasian Customs Union
Range0.4 to 500 mbar (0.16 to 200 WC)
Pneumatic ConnectionsInternal Rp 1/8 2x, Rp 1/4 2x
Electrical connectionScrew terminals, M16x1.5 cable gland 4-Pin plug and socket

Values retain manufacturer model qualifications. Review Honeywell specifications ↗

Part Number

Published part numbers

10 parts

Part NumberDescriptionEnquiry
1187121KRM SCHRDR DG .4-4"WC AUT RST PRESS SWRequest quotation
326080QDIFF.PR.SW DG6UG IP65 W/CONNRequest quotation
326081QDIFF.PR.SW DG10UG IP65 W/CONNRequest quotation
326082QDIFF.PR.SW DG50UG IP65 W/CONNRequest quotation
326083QDIF.PR.SW DG150UG IP65 W/CONNRequest quotation
326084QDIF.P.SW DG500UG-5Z IP65 W/CONRequest quotation
326131QDIFF.PR.SW. DG 6U IP65 w/CONNRequest quotation
326132QDIFF.PR.SW. DG 10U IP65 w/CONNRequest quotation
326134QDIFF.PR.SW. DG 50U IP65 w/CONNRequest quotation
326135QDIFF.PR.SW. DG 150U IP65 w/CNNRequest quotation
Manufacturer sources

https://process.honeywell.com/us/en/products/thermal-solutions/fuel-and-air-delivery/pressure-switches-and-gauges/kromschroeder-dg-pressure-switches-for-gas

Last source check: 2026-11-02

Pressure switch · Manufacturer ownership retained; republication licence not independently confirmed

Front image used for DG 6 in mono 319 x 343 · Manufacturer ownership retained; republication licence not independently confirmed

Front image used for DG H N in mono 319 x 343 · Manufacturer ownership retained; republication licence not independently confirmed

Front image used for DG B in mono 319 x 343 · Manufacturer ownership retained; republication licence not independently confirmed

Front image used for DG 4 in mono 319 x 343 · Manufacturer ownership retained; republication licence not independently confirmed

Kromschroeder DG · Site owner attests manufacturer permission; licence not independently audited

ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.

Your next project. A clear starting point.

Tell us about your facility and what you need to achieve.

CallSend enquiry