Pressure Switches & Gauges
Honeywell C6097 pressure switches for gas
C6097 supervises positive gas/air pressure and negative or differential air/flue-gas pressure.
C6097 supervises positive gas/air pressure and negative or differential air/flue-gas pressure. A dial sets the switching point, with regional connection and electrical options. Optional locking/manual reset is available, while the published medium distinctions prevent extending negative-pressure gas service beyond the manufacturer's stated application.
Features & Benefits
- Pressure Measurement Type
- Positive pressure, negative pressure, and differential pressure
- Installation Orientation
- Vertical, horizontal, or inverted (switching point must be verified)
- Electrical Connections
- Screw terminals, M16 cable gland (CE), 1/2 in NPT conduit (UL/FM)
- Mechanical Connection
- 1/4 in NPT/1/8 in NPT (UL/FM)|G 1/4 in, G 1/8 in (CE)
- Media Compatibility
- Natural Gas, Town Gas, LPG (gaseous), Flue Gas, Biogas (≤0.1% H₂S), Hydrogen, Air
- Temperature Rating
- CE: -20 to +80 deg C|UL/FM: -40 to +60 deg C
- Switching Function
- Change‑over contact (NO/NC/COM)
- Switching Capacity
- CE: 24 to 250 VAC, 0.05-5 A|UL/FM: 24 to 240 VAC, max 5 A
- Switching Behavior
- Switches on rising pressure (C6097B) or falling pressure (C6097A)
- Diaphragm Material
- NBR (silicone-free)
- Protection Class
- IP65
- Primary Function
- Monitoring and switching of gas and air pressures
- Pressure Range
- Extremely low to medium pressure ranges (model dependent)
- Product Type
- C6097A (switches on falling pressure), C6097B (switches on rising pressure)
- Approvals
- CE (EN 1854), UL Listed, FM Approved, LVD, EMC, RoHS, Gas Appliances Regulation (EU) 2016/426
- Material
- PBT Plastic (Glass Fiber reinforced), Aluminum Lower Section
- Electrical connection
- Screw terminals, M16x1.5 cable gland Screw terminals, 1/2 NPT cable conduit 4-Pin plug and socket
- Several connection and reset choices fit different installations.
Applications
- Positive gas/air supervision
- Negative or differential air/flue-gas supervision
Pressure Specifications
- Pressure Measurement Type
- Positive pressure, negative pressure, and differential pressure
- Pressure Range
- Extremely low to medium pressure ranges (model dependent)
Installation & Mounting Specifications
- Installation Orientation
- Vertical, horizontal, or inverted (switching point must be verified)
Connections & Interfaces
- Electrical Connections
- Screw terminals, M16 cable gland (CE), 1/2 in NPT conduit (UL/FM)
- Mechanical Connection
- 1/4 in NPT/1/8 in NPT (UL/FM); G 1/4 in, G 1/8 in (CE)
Applications & Compatibility
- Media Compatibility
- Natural Gas, Town Gas, LPG (gaseous), Flue Gas, Biogas (≤0.1% H₂S), Hydrogen, Air
- Applications
- Low/High Gas Pressure Protection, Fan Monitoring, Filter Monitoring, Differential Pressure Monitoring, Leak Tightness Checks
Temperature Control/Measurement
- Temperature Rating
- CE: -20 to +80 deg C; UL/FM: -40 to +60 deg C
Actuation, Control & Motion Characteristics
- Switching Function
- Change‑over contact (NO/NC/COM)
- Switching Behavior
- Switches on rising pressure (C6097B) or falling pressure (C6097A)
Performance Specifications
- Switching Capacity
- CE: 24 to 250 VAC, 0.05-5 A; UL/FM: 24 to 240 VAC, max 5 A
Material Specifications
- Diaphragm Material
- NBR (silicone-free)
- Material
- PBT Plastic (Glass Fiber reinforced), Aluminum Lower Section
Safety, Protection & Reliability
- Protection Class
- IP65
Product Overview & Classification
- Primary Function
- Monitoring and switching of gas and air pressures
Overview
- Product Type
- C6097A (switches on falling pressure), C6097B (switches on rising pressure)
Standards & Certifications
- Approvals
- CE (EN 1854), UL Listed, FM Approved, LVD, EMC, RoHS, Gas Appliances Regulation (EU) 2016/426
Technical Specifications
- Electrical connection
- Screw terminals, M16x1.5 cable gland Screw terminals, 1/2 NPT cable conduit 4-Pin plug and socket
| Parameter | Published value / configuration |
|---|---|
| Pressure Measurement Type | Positive pressure, negative pressure, and differential pressure |
| Pressure Range | Extremely low to medium pressure ranges (model dependent) |
| Installation Orientation | Vertical, horizontal, or inverted (switching point must be verified) |
| Electrical Connections | Screw terminals, M16 cable gland (CE), 1/2 in NPT conduit (UL/FM) |
| Mechanical Connection | 1/4 in NPT/1/8 in NPT (UL/FM); G 1/4 in, G 1/8 in (CE) |
| Media Compatibility | Natural Gas, Town Gas, LPG (gaseous), Flue Gas, Biogas (≤0.1% H₂S), Hydrogen, Air |
| Applications | Low/High Gas Pressure Protection, Fan Monitoring, Filter Monitoring, Differential Pressure Monitoring, Leak Tightness Checks |
| Temperature Rating | CE: -20 to +80 deg C; UL/FM: -40 to +60 deg C |
| Switching Function | Change‑over contact (NO/NC/COM) |
| Switching Behavior | Switches on rising pressure (C6097B) or falling pressure (C6097A) |
| Switching Capacity | CE: 24 to 250 VAC, 0.05-5 A; UL/FM: 24 to 240 VAC, max 5 A |
| Diaphragm Material | NBR (silicone-free) |
| Material | PBT Plastic (Glass Fiber reinforced), Aluminum Lower Section |
| Protection Class | IP65 |
| Primary Function | Monitoring and switching of gas and air pressures |
| Product Type | C6097A (switches on falling pressure), C6097B (switches on rising pressure) |
| Approvals | CE (EN 1854), UL Listed, FM Approved, LVD, EMC, RoHS, Gas Appliances Regulation (EU) 2016/426 |
| Electrical connection | Screw terminals, M16x1.5 cable gland Screw terminals, 1/2 NPT cable conduit 4-Pin plug and socket |
Values retain manufacturer model qualifications. Review Honeywell specifications ↗
Part Number
Published part numbers
10 parts
| Part Number | Description | Enquiry |
|---|---|---|
| 32003039-003/U | COVER FOR CE GAS PRESSURE SWITCH AUTO RE | Request quotation |
| 32003040-003/U | COVER FOR UL GAS PRESSURE SWITCH AUTO RE | Request quotation |
| 32003041-003/U | COVER FOR GAS PRESSURE SWITCH MANUAL RES | Request quotation |
| 32003042-003/U | FASTENING SET U-BRACKET FOR GAS PRESSURE | Request quotation |
| 32003043-003/U | CONNECTING SET FOR MIN/ MAX PRESS. | Request quotation |
| 32003044-003/U | PILOT LAMP, RED:110/120 V FOR GAS PRESSU | Request quotation |
| 32003045-003/U | PILOT LAMP, BLUE:110/120 V FOR GAS PRESS | Request quotation |
| 32003046-003/U | PILOT LAMP, RED:220/240 V FOR GAS PRESSU | Request quotation |
| 32003047-003/U | LED light set,blue:115/230 VAC FOR PRESS | Request quotation |
| 32003048-003/U | LED SET, RED/GREEN: 24 V DC FOR GAS PRE | Request quotation |
Manufacturer sources
Last source check: 2026-11-02
Pressure switches · Manufacturer ownership retained; republication licence not independently confirmed
Front image used for C6097-M16 Gland Secondary in mono 319 x 343 · Manufacturer ownership retained; republication licence not independently confirmed
C6097 NPT Conduit · Manufacturer ownership retained; republication licence not independently confirmed
ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.
Your next project. A clear starting point.
Tell us about your facility and what you need to achieve.