Pressure Switches & Gauges
Pressuretrol® Limit controllers L4079A, B, W, L604N
L4079 PressureTrol limits open circuits when pressure exceeds the setting and require manual reset.
L4079 PressureTrol limits open circuits when pressure exceeds the setting and require manual reset. A/B models cover the stated noncorrosive media, while W adds seals for oil service. Switch count varies by model, and the trip-free mechanism prevents the reset lever from defeating the pressure limit.
Features & Benefits
- Maximum Diaphragm Pressure
- Up to 350 psi (2410 kPa) depending on model
- Ambient Temperature Limits
- Max 150 deg F (66 deg C)
- Maintenance Interval
- Manual reset and annual function check recommended
- Media Compatibility
- L4079A, L4079B: Steam, Air, Non‑Combustible Gases, Non‑Corrosive Fluids|L4079W: Oil Burner Systems
- Differential Range
- 3 to 60 psi (20.7 to 413.7 kPa) depending on model
- Electrical Rating
- 120 VAC: 9.8 A (Full Load), 58.8 A (Locked Rotor)|240 VAC: 4.9 A (Full Load), 29.4 A (Locked Rotor)
- Control Functions
- Safety limit (manual reset)
- Adjustment Method
- External screw; scale in psi and kPa
- Primary Function
- Breaks electrical circuit on pressure rise
- Pressure Range
- 10 to 150 psi (70 to 1035 kPa)|2 to 15 psi (15 to 100 kPa)|20 to 300 psi (140 to 2070 kPa)|5 to 50 psi (35 to 350 kPa)
- Mounting Types
- 1/4-18 NPT pipe fitting|Boiler, wall, or remote mounting
- Configurations
- L4079A: Two ganged SPST switches (breaks two circuits)|L4079B: One SPST switch (breaks one circuit)|L4079W: One SPST switch with oil‑resistant seals
- Switch Action
- Opens circuit(s) on pressure rise
- Product Type
- High‑pressure limit control
- Switch Type
- MICRO SWITCH® snap‑acting
- Reset Type
- Manual reset (trip‑free)
- Approvals
- UL Listed (MP466), CSA Approved (LR95329), WEEE Directive 2012/19/EU compliant
- The trip-free reset prevents defeating the limit by holding the lever.
Applications
- High-pressure limiting
- Oil-burner limiting with L4079W
Detailed capabilities
Trip-free manual reset and model-specific media
L4079A opens two circuits together, B opens one and W adds seals for oil service. Snap switches can be seen through the cover. A rising-pressure event opens automatically, but restoring service requires manual reset; holding or jamming the lever cannot defeat the limit. The stated tolerance of moderate vibration and lack of leveling requirement do not change the model-specific fluid compatibility.
Features and benefits
- The trip-free reset prevents defeating the limit by holding the lever.
Published application context
- High-pressure limiting
- Oil-burner limiting with L4079W
Overview
- Models
- L4079A, L4079B, L4079W
- Product Type
- High‑pressure limit control
Pressure Specifications
- Maximum Diaphragm Pressure
- Up to 350 psi (2410 kPa) depending on model
- Pressure Range
- 10 to 150 psi (70 to 1035 kPa); 2 to 15 psi (15 to 100 kPa); 20 to 300 psi (140 to 2070 kPa); 5 to 50 psi (35 to 350 kPa)
Environmental Conditions
- Ambient Temperature Limits
- Max 150 deg F (66 deg C)
Electrical Specifications
- Maintenance Interval
- Manual reset and annual function check recommended
Applications & Compatibility
- Media Compatibility
- L4079A, L4079B: Steam, Air, Non‑Combustible Gases, Non‑Corrosive Fluids; L4079W: Oil Burner Systems
Measurement, Media & Physical Properties
- Differential Range
- 3 to 60 psi (20.7 to 413.7 kPa) depending on model
Electrical & Signal Specifications
- Electrical Rating
- 120 VAC: 9.8 A (Full Load), 58.8 A (Locked Rotor); 240 VAC: 4.9 A (Full Load), 29.4 A (Locked Rotor)
Control, Logic & Functional Behavior
- Control Functions
- Safety limit (manual reset)
Mechanical Design & Adjustment Characteristics
- Adjustment Method
- External screw; scale in psi and kPa
Product Overview & Classification
- Primary Function
- Breaks electrical circuit on pressure rise
Installation & Mounting Specifications
- Mounting Types
- 1/4-18 NPT pipe fitting; Boiler, wall, or remote mounting
Software, Configuration & Cyber
- Configurations
- L4079A: Two ganged SPST switches (breaks two circuits); L4079B: One SPST switch (breaks one circuit); L4079W: One SPST switch with oil‑resistant seals
Actuation, Control & Motion Characteristics
- Switch Action
- Opens circuit(s) on pressure rise
- Switch Type
- MICRO SWITCH® snap‑acting
Safety, Protection & Reliability
- Reset Type
- Manual reset (trip‑free)
Standards & Certifications
- Approvals
- UL Listed (MP466), CSA Approved (LR95329), WEEE Directive 2012/19/EU compliant
| Parameter | Published value / configuration |
|---|---|
| Models | L4079A, L4079B, L4079W |
| Product Type | High‑pressure limit control |
| Maximum Diaphragm Pressure | Up to 350 psi (2410 kPa) depending on model |
| Pressure Range | 10 to 150 psi (70 to 1035 kPa); 2 to 15 psi (15 to 100 kPa); 20 to 300 psi (140 to 2070 kPa); 5 to 50 psi (35 to 350 kPa) |
| Ambient Temperature Limits | Max 150 deg F (66 deg C) |
| Maintenance Interval | Manual reset and annual function check recommended |
| Media Compatibility | L4079A, L4079B: Steam, Air, Non‑Combustible Gases, Non‑Corrosive Fluids; L4079W: Oil Burner Systems |
| Differential Range | 3 to 60 psi (20.7 to 413.7 kPa) depending on model |
| Electrical Rating | 120 VAC: 9.8 A (Full Load), 58.8 A (Locked Rotor); 240 VAC: 4.9 A (Full Load), 29.4 A (Locked Rotor) |
| Control Functions | Safety limit (manual reset) |
| Adjustment Method | External screw; scale in psi and kPa |
| Primary Function | Breaks electrical circuit on pressure rise |
| Mounting Types | 1/4-18 NPT pipe fitting; Boiler, wall, or remote mounting |
| Configurations | L4079A: Two ganged SPST switches (breaks two circuits); L4079B: One SPST switch (breaks one circuit); L4079W: One SPST switch with oil‑resistant seals |
| Switch Action | Opens circuit(s) on pressure rise |
| Switch Type | MICRO SWITCH® snap‑acting |
| Reset Type | Manual reset (trip‑free) |
| Approvals | UL Listed (MP466), CSA Approved (LR95329), WEEE Directive 2012/19/EU compliant |
Values retain manufacturer model qualifications. Review Honeywell specifications ↗
Part Number
Published part numbers
10 parts
| Part Number | Description | Enquiry |
|---|---|---|
| L4079A1035/U | PRESSURETROL | Request quotation |
| L4079A1050/U | PRESSURETROL | Request quotation |
| L4079B1033/U | PRESSURETROL | Request quotation |
| L4079B1041/U | PRESSURETROL | Request quotation |
| L4079B1058/U | 5-50 PSI OPERATING RANGE. MAX DIAPHRAGM | Request quotation |
| L4079B1066/U | PRESSURETROL LIMIT CONTROLLER | Request quotation |
| L4079B1074/U | PRESSURETROL | Request quotation |
| L4079B1082/U | PRESSURETROL | Request quotation |
| L4079W1000/U | PRESSURETROL | Request quotation |
| L604N1009/U | RANGE 10-150 PSI,.7-10.6 KG/CM2,FIXED | Request quotation |
Manufacturer sources
Last source check: 2026-11-02
Pressuretrol® Limit controllers · Manufacturer ownership retained; republication licence not independently confirmed
ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.
Your next project. A clear starting point.