S70X/S80X viewing heads pair with 700, P531 or P532 processors for single-fuel monitoring where extensive discrimination is unnecessary.
S70X/S80X viewing heads pair with 700, P531 or P532 processors for single-fuel monitoring where extensive discrimination is unnecessary. UV pulse sensing suits small, slow low-NOx flames. Model groups differ in barrel diameter and housing material; all use electronic self-checking, with cable arrangements distinguished by the PF suffix.
Features & Benefits
- Minimum/Maximum Viewing Distance
- Determined by sighting; typical count rates 12-22 recommended (Signal Processor displays 00-29).
- Electrical Isolation Requirement
- Must be isolated from burner front using Ultem nipples or couplers.
- Hazardous Location Approvals
- CSA Class I, Div 2, Groups A, B, C, D, T4A; IECEx Ex nA IIC T4/T5 Gc; NCC/Inmetro Ex ec IIC T4 Gc.
- Compatible Signal Processors
- Model 700ACSP, 700DCSP, 800, P531/P532.
- Ambient Temperature Range
- -40 to +185 deg F (-40 to +85 deg C) for standard models. (S70X/S80X)
- Purge Air Requirement
- 5 SCFM at ~1 in. above burner pressure to cool lens and clear viewing path. Air must be clean & dry.
- Optical Field of View
- IR Models: 1 deg angle of view (1.45 in at 6 ft)|UV Models: 5 deg angle of view (1 in per foot)
- Cable Connection Type
- Pre‑wired or field‑wired connectors: ASY782, ASY785, ASY785‑200, ASY786. Uses C330S cable (ITC/CIC rated).
- Vibration Resistance
- Avoid high-vibration areas; anti‑vibration mounts recommended.
- Maintenance Interval
- For UV models: UV tube lifetime 10,000-50,000 hrs depending on conditions; monthly sensitivity check recommended.
- Environmental Rating
- IP64 when connector ring is properly tightened and cable shielded.
- Proof Test Interval
- 1 to 5 years depending on safety system requirements.
- Mounting Connection
- 1/2 in NPT-F for sighting pipe|1/4 in NPT-F for purge air
- Pressure Ratings
- S70X: lens withstands 50 psi|S80X: lens withstands 90 psi (with correct compression ring)
- Housing Material
- S70X: Aluminum body, secured with over‑center latches|S80X: Stainless steel body, locked via twist‑lock mount
- LED Indicator
- Green LED: flame pulses/ID pulses. (Not present on PF versions.) (Connector Series)|Orange LED: processor self‑check pulse
- Detector Type
- Two families available: IR/Flicker-sensitive (S702, S702PF, S802) and UV-sensitive (S706, S706PF, S806).
- Power Supply
- Powered directly by signal processor (24 VDC supplied from 700/800 SP).
- Cable Rating
- C330S = 4‑conductor shielded with drain; ITC/CIC approved for hazardous locations.
- Sensor Type
- IR Models: Germanium photodiode, spectral response 950-1710 nm, peak at 1400 nm; high‑pass filter at 33 Hz|UV Models: UVTron sensor, spectral response 185-260 nm, peak at 210 nm
- Approvals
- SIL 3 Capable (S702/S802 and S706/S806 families).
- Electronic self-checking avoids a mechanical shutter.
Applications
- Single-fuel monitoring
- Low-NOx burner flame detection with UV models
Detailed capabilities
Choosing the S70X/S80X construction
S702/S706 variants use the larger aluminum barrel, while S802/S806 use the smaller stainless barrel. UV or IR choice follows the flame-monitoring duty, with the UV pulse tube described for small, slow low-NOx flames. Disconnect-cable LEDs assist setup; PF versions instead have a fitted cable. These are matched heads for the specified processors, not a common signal interface for any controller.
Features and benefits
- Electronic self-checking avoids a mechanical shutter.
Published application context
- Single-fuel monitoring
- Low-NOx burner flame detection with UV models
Measurement & Sensing Characteristics
- Minimum/Maximum Viewing Distance
- Determined by sighting; typical count rates 12-22 recommended (Signal Processor displays 00-29).
Ignition, Flame & Supervision Specifications
- Electrical Isolation Requirement
- Must be isolated from burner front using Ultem nipples or couplers.
Standards & Certifications
- Hazardous Location Approvals
- CSA Class I, Div 2, Groups A, B, C, D, T4A; IECEx Ex nA IIC T4/T5 Gc; NCC/Inmetro Ex ec IIC T4 Gc.
- Approvals
- SIL 3 Capable (S702/S802 and S706/S806 families).
Applications & Compatibility
- Compatible Signal Processors
- Model 700ACSP, 700DCSP, 800, P531/P532.
Environmental Conditions
- Ambient Temperature Range
- -40 to +185 deg F (-40 to +85 deg C) for standard models. (S70X/S80X)
- Environmental Rating
- IP64 when connector ring is properly tightened and cable shielded.
Air & Combustion Air Specifications
- Purge Air Requirement
- 5 SCFM at ~1 in. above burner pressure to cool lens and clear viewing path. Air must be clean & dry.
Measurement, Accuracy & Sensing
- Optical Field of View
- IR Models: 1 deg angle of view (1.45 in at 6 ft); UV Models: 5 deg angle of view (1 in per foot)
- Detector Type
- Two families available: IR/Flicker-sensitive (S702, S702PF, S802) and UV-sensitive (S706, S706PF, S806).
- Sensor Type
- IR Models: Germanium photodiode, spectral response 950-1710 nm, peak at 1400 nm; high‑pass filter at 33 Hz; UV Models: UVTron sensor, spectral response 185-260 nm, peak at 210 nm
Connections & Interfaces
- Cable Connection Type
- Pre‑wired or field‑wired connectors: ASY782, ASY785, ASY785‑200, ASY786. Uses C330S cable (ITC/CIC rated).
- Mounting Connection
- 1/2 in NPT-F for sighting pipe; 1/4 in NPT-F for purge air
Operating Limits, Durability & Lifecycle
- Vibration Resistance
- Avoid high-vibration areas; anti‑vibration mounts recommended.
Electrical Specifications
- Maintenance Interval
- For UV models: UV tube lifetime 10,000-50,000 hrs depending on conditions; monthly sensitivity check recommended.
- Proof Test Interval
- 1 to 5 years depending on safety system requirements.
- Power Supply
- Powered directly by signal processor (24 VDC supplied from 700/800 SP).
Pressure Specifications
- Pressure Ratings
- S70X: lens withstands 50 psi; S80X: lens withstands 90 psi (with correct compression ring)
Material Specifications
- Housing Material
- S70X: Aluminum body, secured with over‑center latches; S80X: Stainless steel body, locked via twist‑lock mount
Alarms, Status & Diagnostics
- LED Indicator
- Green LED: flame pulses/ID pulses. (Not present on PF versions.) (Connector Series); Orange LED: processor self‑check pulse
Mechanical Design & Hardware Details
- Cable Rating
- C330S = 4‑conductor shielded with drain; ITC/CIC approved for hazardous locations.
| Parameter | Published value / configuration |
|---|---|
| Minimum/Maximum Viewing Distance | Determined by sighting; typical count rates 12-22 recommended (Signal Processor displays 00-29). |
| Electrical Isolation Requirement | Must be isolated from burner front using Ultem nipples or couplers. |
| Hazardous Location Approvals | CSA Class I, Div 2, Groups A, B, C, D, T4A; IECEx Ex nA IIC T4/T5 Gc; NCC/Inmetro Ex ec IIC T4 Gc. |
| Approvals | SIL 3 Capable (S702/S802 and S706/S806 families). |
| Compatible Signal Processors | Model 700ACSP, 700DCSP, 800, P531/P532. |
| Ambient Temperature Range | -40 to +185 deg F (-40 to +85 deg C) for standard models. (S70X/S80X) |
| Environmental Rating | IP64 when connector ring is properly tightened and cable shielded. |
| Purge Air Requirement | 5 SCFM at ~1 in. above burner pressure to cool lens and clear viewing path. Air must be clean & dry. |
| Optical Field of View | IR Models: 1 deg angle of view (1.45 in at 6 ft); UV Models: 5 deg angle of view (1 in per foot) |
| Detector Type | Two families available: IR/Flicker-sensitive (S702, S702PF, S802) and UV-sensitive (S706, S706PF, S806). |
| Sensor Type | IR Models: Germanium photodiode, spectral response 950-1710 nm, peak at 1400 nm; high‑pass filter at 33 Hz; UV Models: UVTron sensor, spectral response 185-260 nm, peak at 210 nm |
| Cable Connection Type | Pre‑wired or field‑wired connectors: ASY782, ASY785, ASY785‑200, ASY786. Uses C330S cable (ITC/CIC rated). |
| Mounting Connection | 1/2 in NPT-F for sighting pipe; 1/4 in NPT-F for purge air |
| Vibration Resistance | Avoid high-vibration areas; anti‑vibration mounts recommended. |
| Maintenance Interval | For UV models: UV tube lifetime 10,000-50,000 hrs depending on conditions; monthly sensitivity check recommended. |
| Proof Test Interval | 1 to 5 years depending on safety system requirements. |
| Power Supply | Powered directly by signal processor (24 VDC supplied from 700/800 SP). |
| Pressure Ratings | S70X: lens withstands 50 psi; S80X: lens withstands 90 psi (with correct compression ring) |
| Housing Material | S70X: Aluminum body, secured with over‑center latches; S80X: Stainless steel body, locked via twist‑lock mount |
| LED Indicator | Green LED: flame pulses/ID pulses. (Not present on PF versions.) (Connector Series); Orange LED: processor self‑check pulse |
| Cable Rating | C330S = 4‑conductor shielded with drain; ITC/CIC approved for hazardous locations. |
Values retain manufacturer model qualifications. Review Honeywell specifications ↗
Part Number
Published part numbers
10 parts
| Part Number | Description | Enquiry |
|---|---|---|
| 700ACC | S70X COOLING CAN (REQ. VORTEX CLR) | Request quotation |
| 700DA | 1/2" DELRIN ADAPTER (S70X). FNPT | Request quotation |
| 700DA-1 | 1" DELRIN ADAPTER (S70X). FNPT | Request quotation |
| 700LTA | LIQUID TIGHT CABLE ADPTR 3/8" S700/S800 | Request quotation |
| 700UA | ULTEM HEAT INS. S700.1/2" VIEW-1/4" AIR | Request quotation |
| 800DA | 1/2" DELRIN ADAPTER S80X FNPT 1/2" | Request quotation |
| 800UA | 1/2" ULTEM ADAPTER S80X FNPT 1/2" | Request quotation |
| ASY782 | CABLE W.LED & 15FT CABLE FOR S700/S800 | Request quotation |
| ASY784 | S700/S800 CONNECTOR KIT W/O CABLE | Request quotation |
| ASY785 | 50FT 700/800 SERIES CABLE ASSEMBLY | Request quotation |
Manufacturer sources
Last source check: 2026-11-02
S70X/S80X Series Product Image · Manufacturer ownership retained; republication licence not independently confirmed
ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.
Your next project. A clear starting point.
Tell us about your facility and what you need to achieve.