S70X/S80X viewing heads pair with 700, P531 or P532 processors for single-fuel monitoring where extensive discrimination is unnecessary.

S70X/S80X viewing heads pair with 700, P531 or P532 processors for single-fuel monitoring where extensive discrimination is unnecessary. UV pulse sensing suits small, slow low-NOx flames. Model groups differ in barrel diameter and housing material; all use electronic self-checking, with cable arrangements distinguished by the PF suffix.

Features & Benefits

Minimum/Maximum Viewing Distance
Determined by sighting; typical count rates 12-22 recommended (Signal Processor displays 00-29).
Electrical Isolation Requirement
Must be isolated from burner front using Ultem nipples or couplers.
Hazardous Location Approvals
CSA Class I, Div 2, Groups A, B, C, D, T4A; IECEx Ex nA IIC T4/T5 Gc; NCC/Inmetro Ex ec IIC T4 Gc.
Compatible Signal Processors
Model 700ACSP, 700DCSP, 800, P531/P532.
Ambient Temperature Range
-40 to +185 deg F (-40 to +85 deg C) for standard models. (S70X/S80X)
Purge Air Requirement
5 SCFM at ~1 in. above burner pressure to cool lens and clear viewing path. Air must be clean & dry.
Optical Field of View
IR Models: 1 deg angle of view (1.45 in at 6 ft)|UV Models: 5 deg angle of view (1 in per foot)
Cable Connection Type
Pre‑wired or field‑wired connectors: ASY782, ASY785, ASY785‑200, ASY786. Uses C330S cable (ITC/CIC rated).
Vibration Resistance
Avoid high-vibration areas; anti‑vibration mounts recommended.
Maintenance Interval
For UV models: UV tube lifetime 10,000-50,000 hrs depending on conditions; monthly sensitivity check recommended.
Environmental Rating
IP64 when connector ring is properly tightened and cable shielded.
Proof Test Interval
1 to 5 years depending on safety system requirements.
Mounting Connection
1/2 in NPT-F for sighting pipe|1/4 in NPT-F for purge air
Pressure Ratings
S70X: lens withstands 50 psi|S80X: lens withstands 90 psi (with correct compression ring)
Housing Material
S70X: Aluminum body, secured with over‑center latches|S80X: Stainless steel body, locked via twist‑lock mount
LED Indicator
Green LED: flame pulses/ID pulses. (Not present on PF versions.) (Connector Series)|Orange LED: processor self‑check pulse
Detector Type
Two families available: IR/Flicker-sensitive (S702, S702PF, S802) and UV-sensitive (S706, S706PF, S806).
Power Supply
Powered directly by signal processor (24 VDC supplied from 700/800 SP).
Cable Rating
C330S = 4‑conductor shielded with drain; ITC/CIC approved for hazardous locations.
Sensor Type
IR Models: Germanium photodiode, spectral response 950-1710 nm, peak at 1400 nm; high‑pass filter at 33 Hz|UV Models: UVTron sensor, spectral response 185-260 nm, peak at 210 nm
Approvals
SIL 3 Capable (S702/S802 and S706/S806 families).
  • Electronic self-checking avoids a mechanical shutter.

Applications

  • Single-fuel monitoring
  • Low-NOx burner flame detection with UV models

Detailed capabilities

Choosing the S70X/S80X construction

S702/S706 variants use the larger aluminum barrel, while S802/S806 use the smaller stainless barrel. UV or IR choice follows the flame-monitoring duty, with the UV pulse tube described for small, slow low-NOx flames. Disconnect-cable LEDs assist setup; PF versions instead have a fitted cable. These are matched heads for the specified processors, not a common signal interface for any controller.

Manufacturer reference ↗

Features and benefits

  • Electronic self-checking avoids a mechanical shutter.

Manufacturer reference ↗

Published application context

  • Single-fuel monitoring
  • Low-NOx burner flame detection with UV models

Manufacturer reference ↗

Specifications

Measurement & Sensing Characteristics

Minimum/Maximum Viewing Distance
Determined by sighting; typical count rates 12-22 recommended (Signal Processor displays 00-29).

Ignition, Flame & Supervision Specifications

Electrical Isolation Requirement
Must be isolated from burner front using Ultem nipples or couplers.

Standards & Certifications

Hazardous Location Approvals
CSA Class I, Div 2, Groups A, B, C, D, T4A; IECEx Ex nA IIC T4/T5 Gc; NCC/Inmetro Ex ec IIC T4 Gc.
Approvals
SIL 3 Capable (S702/S802 and S706/S806 families).

Applications & Compatibility

Compatible Signal Processors
Model 700ACSP, 700DCSP, 800, P531/P532.

Environmental Conditions

Ambient Temperature Range
-40 to +185 deg F (-40 to +85 deg C) for standard models. (S70X/S80X)
Environmental Rating
IP64 when connector ring is properly tightened and cable shielded.

Air & Combustion Air Specifications

Purge Air Requirement
5 SCFM at ~1 in. above burner pressure to cool lens and clear viewing path. Air must be clean & dry.

Measurement, Accuracy & Sensing

Optical Field of View
IR Models: 1 deg angle of view (1.45 in at 6 ft); UV Models: 5 deg angle of view (1 in per foot)
Detector Type
Two families available: IR/Flicker-sensitive (S702, S702PF, S802) and UV-sensitive (S706, S706PF, S806).
Sensor Type
IR Models: Germanium photodiode, spectral response 950-1710 nm, peak at 1400 nm; high‑pass filter at 33 Hz; UV Models: UVTron sensor, spectral response 185-260 nm, peak at 210 nm

Connections & Interfaces

Cable Connection Type
Pre‑wired or field‑wired connectors: ASY782, ASY785, ASY785‑200, ASY786. Uses C330S cable (ITC/CIC rated).
Mounting Connection
1/2 in NPT-F for sighting pipe; 1/4 in NPT-F for purge air

Operating Limits, Durability & Lifecycle

Vibration Resistance
Avoid high-vibration areas; anti‑vibration mounts recommended.

Electrical Specifications

Maintenance Interval
For UV models: UV tube lifetime 10,000-50,000 hrs depending on conditions; monthly sensitivity check recommended.
Proof Test Interval
1 to 5 years depending on safety system requirements.
Power Supply
Powered directly by signal processor (24 VDC supplied from 700/800 SP).

Pressure Specifications

Pressure Ratings
S70X: lens withstands 50 psi; S80X: lens withstands 90 psi (with correct compression ring)

Material Specifications

Housing Material
S70X: Aluminum body, secured with over‑center latches; S80X: Stainless steel body, locked via twist‑lock mount

Alarms, Status & Diagnostics

LED Indicator
Green LED: flame pulses/ID pulses. (Not present on PF versions.) (Connector Series); Orange LED: processor self‑check pulse

Mechanical Design & Hardware Details

Cable Rating
C330S = 4‑conductor shielded with drain; ITC/CIC approved for hazardous locations.
Viewing Heads S70X/S80X — manufacturer page values
ParameterPublished value / configuration
Minimum/Maximum Viewing DistanceDetermined by sighting; typical count rates 12-22 recommended (Signal Processor displays 00-29).
Electrical Isolation RequirementMust be isolated from burner front using Ultem nipples or couplers.
Hazardous Location ApprovalsCSA Class I, Div 2, Groups A, B, C, D, T4A; IECEx Ex nA IIC T4/T5 Gc; NCC/Inmetro Ex ec IIC T4 Gc.
ApprovalsSIL 3 Capable (S702/S802 and S706/S806 families).
Compatible Signal ProcessorsModel 700ACSP, 700DCSP, 800, P531/P532.
Ambient Temperature Range-40 to +185 deg F (-40 to +85 deg C) for standard models. (S70X/S80X)
Environmental RatingIP64 when connector ring is properly tightened and cable shielded.
Purge Air Requirement5 SCFM at ~1 in. above burner pressure to cool lens and clear viewing path. Air must be clean & dry.
Optical Field of ViewIR Models: 1 deg angle of view (1.45 in at 6 ft); UV Models: 5 deg angle of view (1 in per foot)
Detector TypeTwo families available: IR/Flicker-sensitive (S702, S702PF, S802) and UV-sensitive (S706, S706PF, S806).
Sensor TypeIR Models: Germanium photodiode, spectral response 950-1710 nm, peak at 1400 nm; high‑pass filter at 33 Hz; UV Models: UVTron sensor, spectral response 185-260 nm, peak at 210 nm
Cable Connection TypePre‑wired or field‑wired connectors: ASY782, ASY785, ASY785‑200, ASY786. Uses C330S cable (ITC/CIC rated).
Mounting Connection1/2 in NPT-F for sighting pipe; 1/4 in NPT-F for purge air
Vibration ResistanceAvoid high-vibration areas; anti‑vibration mounts recommended.
Maintenance IntervalFor UV models: UV tube lifetime 10,000-50,000 hrs depending on conditions; monthly sensitivity check recommended.
Proof Test Interval1 to 5 years depending on safety system requirements.
Power SupplyPowered directly by signal processor (24 VDC supplied from 700/800 SP).
Pressure RatingsS70X: lens withstands 50 psi; S80X: lens withstands 90 psi (with correct compression ring)
Housing MaterialS70X: Aluminum body, secured with over‑center latches; S80X: Stainless steel body, locked via twist‑lock mount
LED IndicatorGreen LED: flame pulses/ID pulses. (Not present on PF versions.) (Connector Series); Orange LED: processor self‑check pulse
Cable RatingC330S = 4‑conductor shielded with drain; ITC/CIC approved for hazardous locations.

Values retain manufacturer model qualifications. Review Honeywell specifications ↗

Part Number

Published part numbers

10 parts

Part NumberDescriptionEnquiry
700ACCS70X COOLING CAN (REQ. VORTEX CLR)Request quotation
700DA1/2" DELRIN ADAPTER (S70X). FNPTRequest quotation
700DA-11" DELRIN ADAPTER (S70X). FNPTRequest quotation
700LTALIQUID TIGHT CABLE ADPTR 3/8" S700/S800Request quotation
700UAULTEM HEAT INS. S700.1/2" VIEW-1/4" AIRRequest quotation
800DA1/2" DELRIN ADAPTER S80X FNPT 1/2"Request quotation
800UA1/2" ULTEM ADAPTER S80X FNPT 1/2"Request quotation
ASY782CABLE W.LED & 15FT CABLE FOR S700/S800Request quotation
ASY784S700/S800 CONNECTOR KIT W/O CABLERequest quotation
ASY78550FT 700/800 SERIES CABLE ASSEMBLYRequest quotation
Manufacturer sources

https://process.honeywell.com/us/en/products/thermal-solutions/burner-management-systems/industrial-flame-monitoring-ifm/viewing-heads-s70x-s80x

Last source check: 2026-11-02

S70X/S80X Series Product Image · Manufacturer ownership retained; republication licence not independently confirmed

ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.

Your next project. A clear starting point.

Tell us about your facility and what you need to achieve.

CallSend enquiry