Honeywell Process Measurement & Control

Industrial Flame Monitoring (IFM)

Flare Stack Monitoring System Watchdog III

Watchdog III monitors flare flames from ground-mounted equipment, including difficult outdoor conditions.

Watchdog III monitors flare flames from ground-mounted equipment, including difficult outdoor conditions. The package combines a P222 processor, S256BE viewing head and 50-foot cable. Remote mounting and service access avoid flare interruption; the published 1,000-foot sight range applies to the stated 40-foot target diameter.

Features & Benefits

Ambient Temperature Range
Processor: 0 to 60 deg C (32 to 140 deg F)|Viewing Head: -40 to 80 deg C (-40 to 176 deg F)
Relay Contact Ratings
5 A at 30 VDC or 250 VAC
Viewing Head Housing
NEMA 4X/IP66
Serial Communication
RS-422/RS-485, Modbus RTU, 4800-38400 baud
Remote Meter Output
Configurable 0 to 20 mA or 4 to 20 mA
Viewing Head Power
24 to 26 VDC, 150 mA (via 0.25 A self-resetting fuse)
Ingress Protection
IP66 (Viewing Head)
Flame Relay Output
Processor - R1: DPDT, Adjustable 0 to 60 s delay (pilot re‑ignition)|R2: SPDT, Adjustable 1 s to 3600 s (alarm delay)
System Components
S256BE Viewing Head, P222 Signal Processor, ASY55XBE Cable Assemblies
Viewing Distance
Up to 1000 ft (300 m) line of sight
Analog Outputs
0 to 19.8 mA or 4 to 19.8 mA (360 Ohm max)
Field of View
40 ft (12 m) target diameter at 1000 ft
Power Supply
85-264 VAC, 47-440 Hz or 22-26 VDC, 300 mA max (Processor)
Dimensions
Processor front: 4.25 x 7.19 in|Viewing head length: 20.25 in (514 mm)
Cable Type
4-conductor, #22 AWG, braided shield (Honeywell C330S recommended)
Approvals
CSA 213-M1987, CSA 142-M1987, WEEE Directive - 2012/19/EU - Waste Electrical and Electronic Equipment Directive
  • Ground-level access permits servicing without interrupting the flare.
  • No moving components limit mechanical maintenance.

Applications

  • Outdoor flare-stack flame monitoring

Detailed capabilities

Outdoor geometry and service arrangement

The Watchdog III package combines a remotely mounted P222 processor and ground-level S256BE head. Sun rejection permits different locations around the flare. The 1,000-foot viewing statement is qualified by a 40-foot target at that distance, not a minimum detectable pilot size at any range. Pushbuttons and LEDs support setup, and ground access allows service without shutting down the flare.

Manufacturer reference ↗

Features and benefits

  • Ground-level access permits servicing without interrupting the flare.
  • No moving components limit mechanical maintenance.

Manufacturer reference ↗

Published application context

  • Outdoor flare-stack flame monitoring

Manufacturer reference ↗

Specifications

Environmental Conditions

Ambient Temperature Range
Processor: 0 to 60 deg C (32 to 140 deg F); Viewing Head: -40 to 80 deg C (-40 to 176 deg F)

Actuation, Valve & Motion Control Specifications

Relay Contact Ratings
5 A at 30 VDC or 250 VAC
System Components
S256BE Viewing Head, P222 Signal Processor, ASY55XBE Cable Assemblies

Mechanical Design & Hardware Details

Viewing Head Housing
NEMA 4X/IP66
Cable Type
4-conductor, #22 AWG, braided shield (Honeywell C330S recommended)

Communication & Interfaces

Serial Communication
RS-422/RS-485, Modbus RTU, 4800-38400 baud

Inputs, Outputs & Interface Signals

Remote Meter Output
Configurable 0 to 20 mA or 4 to 20 mA

Electrical Specifications

Viewing Head Power
24 to 26 VDC, 150 mA (via 0.25 A self-resetting fuse)
Power Supply
85-264 VAC, 47-440 Hz or 22-26 VDC, 300 mA max (Processor)

Safety, Protection & Reliability

Ingress Protection
IP66 (Viewing Head)

Ignition, Flame & Supervision Specifications

Flame Relay Output
Processor - R1: DPDT, Adjustable 0 to 60 s delay (pilot re‑ignition); R2: SPDT, Adjustable 1 s to 3600 s (alarm delay)

Mechanical Design, Layout & Construction Options

Viewing Distance
Up to 1000 ft (300 m) line of sight

Inputs, Outputs & Signal Interfaces

Analog Outputs
0 to 19.8 mA or 4 to 19.8 mA (360 Ohm max)

Measurement & Sensing Characteristics

Field of View
40 ft (12 m) target diameter at 1000 ft

Dimensions & Weight

Dimensions
Processor front: 4.25 x 7.19 in; Viewing head length: 20.25 in (514 mm)

Standards & Certifications

Approvals
CSA 213-M1987, CSA 142-M1987, WEEE Directive - 2012/19/EU - Waste Electrical and Electronic Equipment Directive
Flare Stack Monitoring System Watchdog III — manufacturer page values
ParameterPublished value / configuration
Ambient Temperature RangeProcessor: 0 to 60 deg C (32 to 140 deg F); Viewing Head: -40 to 80 deg C (-40 to 176 deg F)
Relay Contact Ratings5 A at 30 VDC or 250 VAC
System ComponentsS256BE Viewing Head, P222 Signal Processor, ASY55XBE Cable Assemblies
Viewing Head HousingNEMA 4X/IP66
Cable Type4-conductor, #22 AWG, braided shield (Honeywell C330S recommended)
Serial CommunicationRS-422/RS-485, Modbus RTU, 4800-38400 baud
Remote Meter OutputConfigurable 0 to 20 mA or 4 to 20 mA
Viewing Head Power24 to 26 VDC, 150 mA (via 0.25 A self-resetting fuse)
Power Supply85-264 VAC, 47-440 Hz or 22-26 VDC, 300 mA max (Processor)
Ingress ProtectionIP66 (Viewing Head)
Flame Relay OutputProcessor - R1: DPDT, Adjustable 0 to 60 s delay (pilot re‑ignition); R2: SPDT, Adjustable 1 s to 3600 s (alarm delay)
Viewing DistanceUp to 1000 ft (300 m) line of sight
Analog Outputs0 to 19.8 mA or 4 to 19.8 mA (360 Ohm max)
Field of View40 ft (12 m) target diameter at 1000 ft
DimensionsProcessor front: 4.25 x 7.19 in; Viewing head length: 20.25 in (514 mm)
ApprovalsCSA 213-M1987, CSA 142-M1987, WEEE Directive - 2012/19/EU - Waste Electrical and Electronic Equipment Directive

Values retain manufacturer model qualifications. Review Honeywell specifications ↗

Part Number

Published part numbers

2 parts

Part NumberDescriptionEnquiry
P222WATCHDOG III SIGNAL PROCESSOR USE S256BERequest quotation
S256BEWATCHDOG III UV VIEWING HEAD USE P222Request quotation
Manufacturer sources

https://process.honeywell.com/us/en/products/thermal-solutions/burner-management-systems/industrial-flame-monitoring-ifm/flare-stack-monitoring-system-watchdog-iii

Last source check: 2026-11-02

Watchdog III Flare Stack Monitoring System Product Image · Manufacturer ownership retained; republication licence not independently confirmed

ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.

Your next project. A clear starting point.

Tell us about your facility and what you need to achieve.

CallSend enquiry