Fire & Life Safety · Building Systems · Industrial Automation [email protected] +880 1347 561 256
Honeywell Process Measurement & Control

Industrial Flame Monitoring (IFM)

Signal Processors Model P522

P522 supervises two switched S55XBE viewing heads with separate sensor-gain adjustment and selectable infrared flicker settings.

P522 supervises two switched S55XBE viewing heads with separate sensor-gain adjustment and selectable infrared flicker settings. A digital display, LEDs and bar graph show operating status. Configuration can be local or through FlameTools, with two selectable files, an adjustable switching threshold and a scalable analog output.

Features & Benefits

Flame Failure Response Time (FFRT)
1, 2, or 3 seconds
Safe Failure Fraction (SFF)
>99%
Viewing Head Compatibility
S55XBE series
Analog Flame Signal Output
User-selectable 0 to 20 mA or 4 to 20 mA (360 Ohm max)
Ambient Temperature Range
0 to +50 deg C (32 to +122 deg F)
Self-Check Relay Output
1 Form C Contact (SPDT)
Communication Registers
23 Holding Registers (4X) and 5 Discrete Registers (0X) including flame count, gain, UV/IR settings, temperature, relay status, selections, firmware revision. (Modbus)
Battery Backup Voltage
+100 mA per additional viewing head|22 to 26 VDC, 300 mA
Serial Communication
RS-422, 4800 or 9600 baud, 4-wire/2 twisted pair
Channel Select Input
7.5-30 VDC, 3900 Ohm input resistance
System Architecture
1oo1 (one out of one)
Remote Meter Output
0 to 20 mA or 4 to 20 mA (switchable)
Proof Test Interval
1 to 5 years
Mounting Dimensions
7.2 in H x 4.25 in W x 6.4 in D (approximately)
Viewing Head Power
+26 VDC max, fused 0.25 A; +14.3 VDC pulsing (0.2 s ON, 0.8 s OFF)
IR Filter Settings
8 options: 16, 24, 33, 52, 75, 100, 155, 215 Hz
Flame Signal Input
7.5-30 VDC, 3900 Ohm input resistance
Flame Relay Output
2 Form C Contacts (DPDT)
UV Gain Range
0 to 99
IR Gain Range
0 to 699 (default: 450)
Relay Rating
Max 60 W, 125 VAC; Max 220 VDC/250 VAC; Max 2 A
Approvals
WEEE Directive 2012/19/EU - Electronic waste compliance, CSA Certified (Yes), SIL 3 (Safety Integrity Level), FM Approved
  • Independent gain and infrared settings improve application discrimination.

Applications

  • High-discrimination flame monitoring with switched S55XBE heads

Specifications

Overview

Models
P522AC, P522DC

Ignition, Flame & Supervision Specifications

Flame Failure Response Time (FFRT)
1, 2, or 3 seconds
Analog Flame Signal Output
User-selectable 0 to 20 mA or 4 to 20 mA (360 Ohm max)
IR Filter Settings
8 options: 16, 24, 33, 52, 75, 100, 155, 215 Hz
Flame Signal Input
7.5-30 VDC, 3900 Ohm input resistance
Flame Relay Output
2 Form C Contacts (DPDT)
UV Gain Range
0 to 99
IR Gain Range
0 to 699 (default: 450)

Safety, Protection & Reliability

Safe Failure Fraction (SFF)
>99%

Applications & Compatibility

Viewing Head Compatibility
S55XBE series

Environmental Conditions

Ambient Temperature Range
0 to +50 deg C (32 to +122 deg F)

Control, Logic & System Behavior

Self-Check Relay Output
1 Form C Contact (SPDT)

Communication & Interfaces

Communication Registers
23 Holding Registers (4X) and 5 Discrete Registers (0X) including flame count, gain, UV/IR settings, temperature, relay status, selections, firmware revision. (Modbus)
Serial Communication
RS-422, 4800 or 9600 baud, 4-wire/2 twisted pair

Electrical Specifications

Battery Backup Voltage
+100 mA per additional viewing head; 22 to 26 VDC, 300 mA
Proof Test Interval
1 to 5 years
Viewing Head Power
+26 VDC max, fused 0.25 A; +14.3 VDC pulsing (0.2 s ON, 0.8 s OFF)

Inputs, Outputs & Signal Interfaces

Channel Select Input
7.5-30 VDC, 3900 Ohm input resistance
Relay Rating
Max 60 W, 125 VAC; Max 220 VDC/250 VAC; Max 2 A

Actuation, Valve & Motion Control Specifications

System Architecture
1oo1 (one out of one)

Inputs, Outputs & Interface Signals

Remote Meter Output
0 to 20 mA or 4 to 20 mA (switchable)

Dimensions & Weight

Mounting Dimensions
7.2 in H x 4.25 in W x 6.4 in D (approximately)

Standards & Certifications

Approvals
WEEE Directive 2012/19/EU - Electronic waste compliance, CSA Certified (Yes), SIL 3 (Safety Integrity Level), FM Approved
Signal Processors Model P522 — manufacturer page values
ParameterPublished value / configuration
ModelsP522AC, P522DC
Flame Failure Response Time (FFRT)1, 2, or 3 seconds
Analog Flame Signal OutputUser-selectable 0 to 20 mA or 4 to 20 mA (360 Ohm max)
IR Filter Settings8 options: 16, 24, 33, 52, 75, 100, 155, 215 Hz
Flame Signal Input7.5-30 VDC, 3900 Ohm input resistance
Flame Relay Output2 Form C Contacts (DPDT)
UV Gain Range0 to 99
IR Gain Range0 to 699 (default: 450)
Safe Failure Fraction (SFF)>99%
Viewing Head CompatibilityS55XBE series
Ambient Temperature Range0 to +50 deg C (32 to +122 deg F)
Self-Check Relay Output1 Form C Contact (SPDT)
Communication Registers23 Holding Registers (4X) and 5 Discrete Registers (0X) including flame count, gain, UV/IR settings, temperature, relay status, selections, firmware revision. (Modbus)
Serial CommunicationRS-422, 4800 or 9600 baud, 4-wire/2 twisted pair
Battery Backup Voltage+100 mA per additional viewing head; 22 to 26 VDC, 300 mA
Proof Test Interval1 to 5 years
Viewing Head Power+26 VDC max, fused 0.25 A; +14.3 VDC pulsing (0.2 s ON, 0.8 s OFF)
Channel Select Input7.5-30 VDC, 3900 Ohm input resistance
Relay RatingMax 60 W, 125 VAC; Max 220 VDC/250 VAC; Max 2 A
System Architecture1oo1 (one out of one)
Remote Meter Output0 to 20 mA or 4 to 20 mA (switchable)
Mounting Dimensions7.2 in H x 4.25 in W x 6.4 in D (approximately)
ApprovalsWEEE Directive 2012/19/EU - Electronic waste compliance, CSA Certified (Yes), SIL 3 (Safety Integrity Level), FM Approved

Values retain manufacturer model qualifications. Review Honeywell specifications ↗

Part Number

Published part numbers

2 parts

Part NumberDescriptionEnquiry
P522ACAC SERIES 500 PROCESSOR UNIT (2CHNL)Request quotation
P522DCDC SERIES 500 PROCESSOR UNIT (2CHNL)Request quotation
Manufacturer sources

https://process.honeywell.com/us/en/products/thermal-solutions/burner-management-systems/industrial-flame-monitoring-ifm/signal-processors-model-p522

Last source check: 2026-11-02

Model P522 Product Image · Manufacturer ownership retained; republication licence not independently confirmed

ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.

Your next project. A clear starting point.

Tell us about your facility and what you need to achieve.

CallSend enquiry