Industrial Flame Monitoring (IFM)
Signal Processors Model 600U
The 600U processor detects flame through rectified current at a flame rod, energizing its relay above the selected threshold.
The 600U processor detects flame through rectified current at a flame rod, energizing its relay above the selected threshold. Indicators distinguish fouling, grounding and faults, while a numeric display shows flame strength. With an ignition coil, the same rod can also provide the ignition function.
Features & Benefits
- Ignition Transformer Relay
- DPST contacts, rated 5 A at 125/250 VAC
- Ambient Temperature Range
- 0 to 60 deg C (32 to 140 deg F)
- Ignition Modes Supported
- Flame rod only, flame rod with ignition coil, flame rod with ignition transformer
- Ignition Command Input
- 12 to 50 VDC or 85 to 264 VAC
- Ignition Coil Drive
- 4.4 μF capacitor discharged at line frequency via 4 A, 400 V SCR
- Sensitivity Levels
- 4 selectable gain levels via jumper
- Flame Relay Output
- DPDT contacts, rated 5 A at 125/277 VAC and 30 VDC
- Flame Rod Voltage
- 175 VAC
- Flame Rod Current
- < 0.5 mA (no flame)
- Detection Method
- Flame rod sensing via rectified current flow
- Signal Display
- 6-digit LED bar graph (1-6) for flame strength
- Mounting Types
- 35 mm DIN rail
- Grounding and fouling indication help diagnose flame-rod problems.
Applications
- Flame-rod detection
Ignition, Flame & Supervision Specifications
- Ignition Transformer Relay
- DPST contacts, rated 5 A at 125/250 VAC
- Ignition Command Input
- 12 to 50 VDC or 85 to 264 VAC
- Flame Relay Output
- DPDT contacts, rated 5 A at 125/277 VAC and 30 VDC
Environmental Conditions
- Ambient Temperature Range
- 0 to 60 deg C (32 to 140 deg F)
Actuation, Valve & Motion Control Specifications
- Ignition Modes Supported
- Flame rod only, flame rod with ignition coil, flame rod with ignition transformer
Ignition & Flame‑Related Control
- Ignition Coil Drive
- 4.4 μF capacitor discharged at line frequency via 4 A, 400 V SCR
Measurement, Accuracy & Sensing
- Sensitivity Levels
- 4 selectable gain levels via jumper
Electrical Specifications
- Flame Rod Voltage
- 175 VAC
- Flame Rod Current
- < 0.5 mA (no flame)
Measurement & Sensing Characteristics
- Detection Method
- Flame rod sensing via rectified current flow
Control, Software & User Interface Specifications
- Signal Display
- 6-digit LED bar graph (1-6) for flame strength
Installation & Mounting Specifications
- Mounting Types
- 35 mm DIN rail
| Parameter | Published value / configuration |
|---|---|
| Ignition Transformer Relay | DPST contacts, rated 5 A at 125/250 VAC |
| Ignition Command Input | 12 to 50 VDC or 85 to 264 VAC |
| Flame Relay Output | DPDT contacts, rated 5 A at 125/277 VAC and 30 VDC |
| Ambient Temperature Range | 0 to 60 deg C (32 to 140 deg F) |
| Ignition Modes Supported | Flame rod only, flame rod with ignition coil, flame rod with ignition transformer |
| Ignition Coil Drive | 4.4 μF capacitor discharged at line frequency via 4 A, 400 V SCR |
| Sensitivity Levels | 4 selectable gain levels via jumper |
| Flame Rod Voltage | 175 VAC |
| Flame Rod Current | < 0.5 mA (no flame) |
| Detection Method | Flame rod sensing via rectified current flow |
| Signal Display | 6-digit LED bar graph (1-6) for flame strength |
| Mounting Types | 35 mm DIN rail |
Values retain manufacturer model qualifications. Review Honeywell specifications ↗
Part Number
Published part numbers
1 parts
| Part Number | Description | Enquiry |
|---|---|---|
| 600U | 600 ULTRA FLAME ROD PROCESSOR/RELAY | Request quotation |
Manufacturer sources
Last source check: 2026-11-02
600U Flame Rod Product Image · Manufacturer ownership retained; republication licence not independently confirmed
ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.
Your next project. A clear starting point.
Tell us about your facility and what you need to achieve.