Fire & Life Safety · Building Systems · Industrial Automation [email protected] +880 1347 561 256
Honeywell Process Measurement & Control

Industrial Flame Monitoring (IFM)

Signal Processors Model 600U

The 600U processor detects flame through rectified current at a flame rod, energizing its relay above the selected threshold.

The 600U processor detects flame through rectified current at a flame rod, energizing its relay above the selected threshold. Indicators distinguish fouling, grounding and faults, while a numeric display shows flame strength. With an ignition coil, the same rod can also provide the ignition function.

Features & Benefits

Ignition Transformer Relay
DPST contacts, rated 5 A at 125/250 VAC
Ambient Temperature Range
0 to 60 deg C (32 to 140 deg F)
Ignition Modes Supported
Flame rod only, flame rod with ignition coil, flame rod with ignition transformer
Ignition Command Input
12 to 50 VDC or 85 to 264 VAC
Ignition Coil Drive
4.4 μF capacitor discharged at line frequency via 4 A, 400 V SCR
Sensitivity Levels
4 selectable gain levels via jumper
Flame Relay Output
DPDT contacts, rated 5 A at 125/277 VAC and 30 VDC
Flame Rod Voltage
175 VAC
Flame Rod Current
< 0.5 mA (no flame)
Detection Method
Flame rod sensing via rectified current flow
Signal Display
6-digit LED bar graph (1-6) for flame strength
Mounting Types
35 mm DIN rail
  • Grounding and fouling indication help diagnose flame-rod problems.

Applications

  • Flame-rod detection

Specifications

Ignition, Flame & Supervision Specifications

Ignition Transformer Relay
DPST contacts, rated 5 A at 125/250 VAC
Ignition Command Input
12 to 50 VDC or 85 to 264 VAC
Flame Relay Output
DPDT contacts, rated 5 A at 125/277 VAC and 30 VDC

Environmental Conditions

Ambient Temperature Range
0 to 60 deg C (32 to 140 deg F)

Actuation, Valve & Motion Control Specifications

Ignition Modes Supported
Flame rod only, flame rod with ignition coil, flame rod with ignition transformer

Ignition & Flame‑Related Control

Ignition Coil Drive
4.4 μF capacitor discharged at line frequency via 4 A, 400 V SCR

Measurement, Accuracy & Sensing

Sensitivity Levels
4 selectable gain levels via jumper

Electrical Specifications

Flame Rod Voltage
175 VAC
Flame Rod Current
< 0.5 mA (no flame)

Measurement & Sensing Characteristics

Detection Method
Flame rod sensing via rectified current flow

Control, Software & User Interface Specifications

Signal Display
6-digit LED bar graph (1-6) for flame strength

Installation & Mounting Specifications

Mounting Types
35 mm DIN rail
Signal Processors Model 600U — manufacturer page values
ParameterPublished value / configuration
Ignition Transformer RelayDPST contacts, rated 5 A at 125/250 VAC
Ignition Command Input12 to 50 VDC or 85 to 264 VAC
Flame Relay OutputDPDT contacts, rated 5 A at 125/277 VAC and 30 VDC
Ambient Temperature Range0 to 60 deg C (32 to 140 deg F)
Ignition Modes SupportedFlame rod only, flame rod with ignition coil, flame rod with ignition transformer
Ignition Coil Drive4.4 μF capacitor discharged at line frequency via 4 A, 400 V SCR
Sensitivity Levels4 selectable gain levels via jumper
Flame Rod Voltage175 VAC
Flame Rod Current< 0.5 mA (no flame)
Detection MethodFlame rod sensing via rectified current flow
Signal Display6-digit LED bar graph (1-6) for flame strength
Mounting Types35 mm DIN rail

Values retain manufacturer model qualifications. Review Honeywell specifications ↗

Part Number

Published part numbers

1 parts

Part NumberDescriptionEnquiry
600U600 ULTRA FLAME ROD PROCESSOR/RELAYRequest quotation
Manufacturer sources

https://process.honeywell.com/us/en/products/thermal-solutions/burner-management-systems/industrial-flame-monitoring-ifm/signal-processors-model-600u

Last source check: 2026-11-02

600U Flame Rod Product Image · Manufacturer ownership retained; republication licence not independently confirmed

ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.