C300 executes Experion process-control strategies using deterministic CEE software.
C300 executes Experion process-control strategies using deterministic CEE software. The controller supports continuous and batch duties, smart-device integration and custom algorithm blocks, with embedded cybersecurity features. Published protocol options cover several industrial network types, allowing the configured controller to serve varied field and supervisory connections while maintaining a common control-execution environment.
Models: C300, PCNT05
Features & Benefits
- Execution
- Deterministic Control Execution Environment
- Functions
- Continuous, batch and custom algorithms
- Supports scalable process-control integration
Applications
- Experion continuous and batch automation
Detailed capabilities
Product and configuration
C300 executes Experion process-control strategies using deterministic CEE software. The controller supports continuous and batch duties, smart-device integration and custom algorithm blocks, with embedded cybersecurity features. Published protocol options cover several industrial network types, allowing the configured controller to serve varied field and supervisory connections while maintaining a common control-execution environment.
- Execution: Deterministic Control Execution Environment
- Functions: Continuous, batch and custom algorithms
Operation and integration
C300 runs deterministic CEE strategies for continuous and batch operations, advanced control and custom algorithms. It integrates smart devices through supported industrial protocols. C300v5, identified as PCNT05, supports conventional one-to-one redundancy and Control HIVE deployment.
Application and selection
The architecture supports modular project execution, diagnostics and reduced maintenance through controller and I/O flexibility. Embedded cybersecurity and standardized communication help manage complex control installations; protocol availability and HIVE architecture must follow the selected controller release.
Others
- Device Indexing
- Odd-Even Pairing (e.g., 1 and 2)
- User Memory
- 32,768 MU (Memory Units)
- Time Sources
- NTP; PTPv2
- Temperature Rating
- –40 to +70°C
- Tagged Blocks
- Up to 4095
- Synchronization Time
- ~240 sec
- Switchover Time
- ~500 ms
- Supported Protocols
- CDA peer-to-peer second (time unit); EtherNet/IP via EIM second (time unit); Foundation Fieldbus via FIM4/FIM8 second (time unit); Modbus/TCP via PCDI second (time unit); Profibus via PGM second (time unit); Profinet via EIM second (time unit); VLAN-based IO HIVE second (time unit)
- Security Lock
- Configurable via Device Index Switches
- Security
- Embedded Firewall; ISA Secure CSA L2 Certified
- SNTP Update Period
- 1 min
- Redundancy Cable
- Ethernet STP
- Redundancy
- Supports 1:1 redundancy with dedicated IOTA and redundancy cable
- PTP Update Period
- 30 sec
- Mounting Type
- On Input Output Termination Assembly (IOTA)
- Models
- C300 (PCNT05)
- Memory Backup
- CC-SCMB05 Module for Power-Loss Recovery
- I/O HIVE Capacity
- 1500 IO HIVE Parameter References; Up to 15 CN100 Connections
- Form Factor
- Series C
- Execution Units (XUs)
- 9000 XUs
- Execution Period
- 20 ms not supported for PCNT05; 50 ms (Standard)
- Execution Environment
- Honeywell’s Control Execution Environment (CEE)
| Parameter | Published value / configuration |
|---|---|
| Device Indexing | Odd-Even Pairing (e.g., 1 and 2) |
| User Memory | 32,768 MU (Memory Units) |
| Time Sources | NTP; PTPv2 |
| Temperature Rating | –40 to +70°C |
| Tagged Blocks | Up to 4095 |
| Synchronization Time | ~240 sec |
| Switchover Time | ~500 ms |
| Supported Protocols | CDA peer-to-peer second (time unit); EtherNet/IP via EIM second (time unit); Foundation Fieldbus via FIM4/FIM8 second (time unit); Modbus/TCP via PCDI second (time unit); Profibus via PGM second (time unit); Profinet via EIM second (time unit); VLAN-based IO HIVE second (time unit) |
| Security Lock | Configurable via Device Index Switches |
| Security | Embedded Firewall; ISA Secure CSA L2 Certified |
| SNTP Update Period | 1 min |
| Redundancy Cable | Ethernet STP |
| Redundancy | Supports 1:1 redundancy with dedicated IOTA and redundancy cable |
| PTP Update Period | 30 sec |
| Mounting Type | On Input Output Termination Assembly (IOTA) |
| Models | C300 (PCNT05) |
| Memory Backup | CC-SCMB05 Module for Power-Loss Recovery |
| I/O HIVE Capacity | 1500 IO HIVE Parameter References; Up to 15 CN100 Connections |
| Form Factor | Series C |
| Execution Units (XUs) | 9000 XUs |
| Execution Period | 20 ms not supported for PCNT05; 50 ms (Standard) |
| Execution Environment | Honeywell’s Control Execution Environment (CEE) |
Values retain manufacturer model qualifications. Review Honeywell specifications ↗
Resources
Resources linked from the manufacturer’s page. Confirm the document revision and applicable model before installation or ordering.
Honeywell resource listing ↗Part Number
Published model / variant identifiers. A full ordering code requires the manufacturer configuration.
Published part numbers
10 parts
| Part Number | Description | Enquiry |
|---|---|---|
| 51109516-101 | FAN POWER CABLE (10 FEET) | Request quotation |
| 51109516-501 | FAN POWER CABLE (15 FEET) | Request quotation |
| 51121311-100 | SERIES C DUAL CAB INTERNAL KIT | Request quotation |
| 51121575-100 | FUSE, CLASS CC, TYPE T, 600V, 10A | Request quotation |
| 51154859-100 | MEANWELL POWER SUPPLY MODULE | Request quotation |
| 51155581-100 | BATTERY BACKUP MOUNTING KIT | Request quotation |
| 51190582-150 | FUSE, QUICK ACTING, 5x20mm, 0.5A/250V | Request quotation |
| 51190582-175 | FUSE 750MA | Request quotation |
| 51190582-180 | Fuse, Type F, 250V, 800mA | Request quotation |
| 51190582-310 | FUSE, QUICK ACTING, 5x20mm, 10A 125V | Request quotation |
Manufacturer sources
Last source check: 2026-11-02
C300 Controller product and category image · Manufacturer ownership retained; republication licence not independently confirmed
ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.
Your next project. A clear starting point.