Medium Pressure Regulators PN16 (ANSI 150)
HON 270 MK2
HON 270 MK2 is a direct-acting gas regulator designed to respond quickly to load changes.
HON 270 MK2 is a direct-acting gas regulator designed to respond quickly to load changes. Its diaphragm casing rotates relative to the body, and the regulator can be installed in any position. A removable cartridge simplifies servicing, while options add overpressure or combined underpressure and overpressure shut-off protection.
Models: HON 270 MK2
Features & Benefits
- Maximum inlet pressure
- 10.3 bar
- Outlet range
- 0.01–0.5 bar
- Orientation
- Any installation position
- Cartridge construction simplifies maintenance
Applications
- Gas distribution offtake stations
Detailed capabilities
HON 270 MK2 — operating design
HON 270 MK2 is a direct-acting gas regulator designed to respond quickly to load changes. Its diaphragm casing rotates relative to the body, and the regulator can be installed in any position. A removable cartridge simplifies servicing, while options add overpressure or combined underpressure and overpressure shut-off protection.
Cartridge servicing and protection variants
The diaphragm assembly rotates in forty-five-degree increments, and the cartridge can be removed to simplify service. Optional overpressure or combined underpressure/overpressure cut-off is available. P versions omit the internal relief valve and R versions include it; those labels must remain distinct when specifying a protection arrangement, along with the chosen screwed or flanged connection.
Published configuration and technical facts
The manufacturer lists these values for HON 270 MK2. Version, size and option qualifications remain attached to each fact.
- Maximum Incidental Outlet Pressure: 700 mbar g (280 in-wg) (Max. OPCO trip set pressure)
- Minimum Differential Pressure: Typically 35 mbar (14 in wg)
- Maximum Inlet Pressure Rating: Up to 10.3 bar g (150psig)
- Connection Type: 1.5 and 2 in Screwed (BS21 Rc and Rp), DN 50 Flanged (PN16, BS EN 1092-2:1997, ASA Class 150)
- Lock-up Pressure Zone Class: 5 to 10 mbar (2 to 4 in-wg)
- Temperature Range: -20 to +60 deg C
Processing & Performance Metrics
- Maximum Incidental Outlet Pressure
- 700 mbar g (280 in-wg) (Max. OPCO trip set pressure)
Technical Specifications
- Minimum Differential Pressure
- Typically 35 mbar (14 in wg)
- Maximum Inlet Pressure Rating
- Up to 10.3 bar g (150psig)
- Connection Type
- 1.5 and 2 in Screwed (BS21 Rc and Rp), DN 50 Flanged (PN16, BS EN 1092-2:1997, ASA Class 150)
Mechanical & Physical Properties
- Lock-up Pressure Zone Class
- 5 to 10 mbar (2 to 4 in-wg)
Environmental Conditions
- Outlet Pressure Range
- HON 270 MK2: 10 to 350 mbar g (4 to 140 in wg); HON 270H MK2: 320 to 500 mbar (128 to 200 in wg)
- Temperature Range
- -20 to +60 deg C
Standards & Certifications
- Explosion Protection
- All mechanical components of this device are without potential ignition sources and/or hot faces. They are not subject to ATEX 95 (94/9/EC). All electronic accessories, on the other hand, meet ATEX requirements.
Software & Interface
- Suitable Gases
- Natural and Manufactured Gases (Non-Aggressive), Nitrogen, Carbon Dioxide, Propane, Butane
Material Specifications
- Body Material
- Ductile Iron
Applications & Compatibility
- Applications
- Gas pressure reduction for domestic, business, and small industrial feeds to burners, heaters, boilers
| Parameter | Published value / configuration |
|---|---|
| Maximum Incidental Outlet Pressure | 700 mbar g (280 in-wg) (Max. OPCO trip set pressure) |
| Minimum Differential Pressure | Typically 35 mbar (14 in wg) |
| Maximum Inlet Pressure Rating | Up to 10.3 bar g (150psig) |
| Connection Type | 1.5 and 2 in Screwed (BS21 Rc and Rp), DN 50 Flanged (PN16, BS EN 1092-2:1997, ASA Class 150) |
| Lock-up Pressure Zone Class | 5 to 10 mbar (2 to 4 in-wg) |
| Outlet Pressure Range | HON 270 MK2: 10 to 350 mbar g (4 to 140 in wg); HON 270H MK2: 320 to 500 mbar (128 to 200 in wg) |
| Temperature Range | -20 to +60 deg C |
| Explosion Protection | All mechanical components of this device are without potential ignition sources and/or hot faces. They are not subject to ATEX 95 (94/9/EC). All electronic accessories, on the other hand, meet ATEX requirements. |
| Suitable Gases | Natural and Manufactured Gases (Non-Aggressive), Nitrogen, Carbon Dioxide, Propane, Butane |
| Body Material | Ductile Iron |
| Applications | Gas pressure reduction for domestic, business, and small industrial feeds to burners, heaters, boilers |
Values retain manufacturer model qualifications. Review Honeywell specifications ↗
Resources
Resources linked from the manufacturer’s page. Confirm the document revision and applicable model before installation or ordering.
Honeywell resource listing ↗Part Number
Published model / variant identifiers. A full ordering code requires the manufacturer configuration.
Published part numbers
8 parts
| Part Number | Description | Enquiry |
|---|---|---|
| BD270BP | SERIES 270P REGULATOR NO INTERNAL RELIEF | Request quotation |
| BD270BR | SERIES 270R REG WITH INTERNAL RELIEF | Request quotation |
| BD270HP | SERIES 270H-P REG NO INTERNAL RELIEF | Request quotation |
| BD270HR | SERIES 270H-R REG WITH INTERNAL RELIEF | Request quotation |
| HON270BP | SERIES 270P REGULATOR NO INTERNAL RELIEF | Request quotation |
| HON270BR | SERIES 270R REG WITH INTERNAL RELIEF | Request quotation |
| HON270HP | SERIES 270H-P REG NO INTERNAL RELIEF | Request quotation |
| HON270HR | SERIES 270H-R REG WITH INTERNAL RELIEF | Request quotation |
Manufacturer sources
Last source check: 2026-11-02
HON 270 MK2 Image · Manufacturer ownership retained; republication licence not independently confirmed
ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.
Your next project. A clear starting point.