valVario Valves
VAS-VCS solenoid valves for gas
VAS/VCS gas safety valves provide automatic shutoff with deenergized closure, flow adjustment and a pilot lamp.
VAS/VCS gas safety valves provide automatic shutoff with deenergized closure, flow adjustment and a pilot lamp. Opening-speed choices and optional pressure switches, position indication or bypass/pilot valves support different burner trains. The manufacturer states class-A, SIL and PL capabilities with defined approvals; configuration-specific voltage, size and connection data still govern installation.
Features & Benefits
- Ambient Temperature Range
- -20 to +60 deg C
- Voltage Rating
- 230 VAC, 200 VAC, 120 VAC, 100 VAC, 24 VDC
- Valve Housing
- Aluminium Valve Housing, NBR Valve Seal
- Switching Frequency
- VAS../L: 2/min|VAS../N: 30/min|VCS 6-9: 1/min
- Storage Temperature
- -20 to +40 deg C
- Start Gas Adjustment
- 0 to 70% for slow-opening types
- Sizes
- VAS/VCS 1-3: DN 10-65|VAS/VCS 6-9: DN 65-125
- Safety Integrity Levels
- SIL 1-3, PL a-e
- Product Family
- VAS (single) and VCS (double) solenoid valves for gas
- POC Indicator Ratings
- AC: 12 to 250 V, 3A|DC: 12 to 30 V, 0.1A
- Operating Modes
- Closed when de-energized (fail-safe)
- Opening Time
- Quick <1 seconds (VAS../N)|Slow up to 10 seconds (VAS../L)
- Maintenance Interval
- Yearly, twice yearly for biogas, clean strainer if needed
- LED Indicator
- Blue LED when energized
- Installation Orientation
- Upright or horizontal, not upside-down
- Inlet Pressure Range
- 500 mbar (7 psig)
- Gas Compatibility
- Natural Gas, LPG, Biogas, Hydrogen, Clean Air
- Flow Adjustment Range
- 20 to 100%
- Enclosure Rating
- IP65, NEMA 2/4
- Electrical Connections
- M20 Cable Gland, Plug, Plug-With-Socket, Dual-Valve Connectors
- Duty Cycle
- 100%
- Designed Lifetime
- 50,000 to 500,000 cycles depending on size
- Connection Type
- Rp/NPT Internal Threads; ISO Flange; ANSI Flange for .T models
- Closing Time
- <1 seconds for all variants
- Approvals
- CE, UKCA, FM, UL, ANSI/CSA, AGA, Eurasian CU, RoHS, REACH, EN 161, EN 13611 Compliant
- Size
- 1 to 9
- DN
- 10 to 125
- Mains voltage
- 24 V DC, 120 V AC or 230 V AC
- Modular indication, pressure-switch and pilot options support configured trains.
Applications
- Automatic gas/air shutoff in combustion trains
Detailed capabilities
Valve-train options and closing behavior
VAS/VCS normally closes when deenergized. Quick or slower opening can be selected while rapid closing is retained. Options add position indication, a bypass/pilot valve or DG pressure supervision; these are fitted configurations rather than every valve's standard contents. The stated protection, approvals and SIL/PL capability must be interpreted with the selected size, supply, connections and safety-system design.
Features and benefits
- Modular indication, pressure-switch and pilot options support configured trains.
Published application context
- Automatic gas/air shutoff in combustion trains
Technical facts in the product overview
- Size: 1 to 9
- DN: 10 to 125
- Mains voltage: 24 V DC, 120 V AC or 230 V AC
Environmental Conditions
- Ambient Temperature Range
- -20 to +60 deg C
- Enclosure Rating
- IP65, NEMA 2/4
Electrical Specifications
- Voltage Rating
- 230 VAC, 200 VAC, 120 VAC, 100 VAC, 24 VDC
- Switching Frequency
- VAS../L: 2/min; VAS../N: 30/min; VCS 6-9: 1/min
- Maintenance Interval
- Yearly, twice yearly for biogas, clean strainer if needed
Actuation, Valve & Motion Control Specifications
- Valve Housing
- Aluminium Valve Housing, NBR Valve Seal
- Opening Time
- Quick <1 seconds (VAS../N); Slow up to 10 seconds (VAS../L)
- Closing Time
- <1 seconds for all variants
Storage/Transport Temperatures
- Storage Temperature
- -20 to +40 deg C
Combustion, Fuel & Mixing Sub‑Systems
- Start Gas Adjustment
- 0 to 70% for slow-opening types
Dimensions & Size Specifications
- Sizes
- VAS/VCS 1-3: DN 10-65; VAS/VCS 6-9: DN 65-125
Standards & Certifications
- Safety Integrity Levels
- SIL 1-3, PL a-e
- Approvals
- CE, UKCA, FM, UL, ANSI/CSA, AGA, Eurasian CU, RoHS, REACH, EN 161, EN 13611 Compliant
Product Overview & Classification
- Product Family
- VAS (single) and VCS (double) solenoid valves for gas
Control, Safety & Functional Behavior
- POC Indicator Ratings
- AC: 12 to 250 V, 3A; DC: 12 to 30 V, 0.1A
Control, Logic & System Behavior
- Operating Modes
- Closed when de-energized (fail-safe)
Alarms, Status & Diagnostics
- LED Indicator
- Blue LED when energized
Installation & Mounting Specifications
- Installation Orientation
- Upright or horizontal, not upside-down
Pressure Specifications
- Inlet Pressure Range
- 500 mbar (7 psig)
Applications & Compatibility
- Gas Compatibility
- Natural Gas, LPG, Biogas, Hydrogen, Clean Air
- Applications
- Commercial heat generation; Gas burners and gas appliances; Industrial furnaces, kilns, ovens, and heat treatment systems; Suitable for hydrogen applications
Processing & Performance Metrics
- Flow Adjustment Range
- 20 to 100%
- Duty Cycle
- 100%
Connections & Interfaces
- Electrical Connections
- M20 Cable Gland, Plug, Plug-With-Socket, Dual-Valve Connectors
- Connection Type
- Rp/NPT Internal Threads; ISO Flange; ANSI Flange for .T models
Operating Limits, Durability & Lifecycle
- Designed Lifetime
- 50,000 to 500,000 cycles depending on size
Technical Specifications
- Size
- 1 to 9
- DN
- 10 to 125
- Mains voltage
- 24 V DC, 120 V AC or 230 V AC
| Parameter | Published value / configuration |
|---|---|
| Ambient Temperature Range | -20 to +60 deg C |
| Enclosure Rating | IP65, NEMA 2/4 |
| Voltage Rating | 230 VAC, 200 VAC, 120 VAC, 100 VAC, 24 VDC |
| Switching Frequency | VAS../L: 2/min; VAS../N: 30/min; VCS 6-9: 1/min |
| Maintenance Interval | Yearly, twice yearly for biogas, clean strainer if needed |
| Valve Housing | Aluminium Valve Housing, NBR Valve Seal |
| Opening Time | Quick <1 seconds (VAS../N); Slow up to 10 seconds (VAS../L) |
| Closing Time | <1 seconds for all variants |
| Storage Temperature | -20 to +40 deg C |
| Start Gas Adjustment | 0 to 70% for slow-opening types |
| Sizes | VAS/VCS 1-3: DN 10-65; VAS/VCS 6-9: DN 65-125 |
| Safety Integrity Levels | SIL 1-3, PL a-e |
| Approvals | CE, UKCA, FM, UL, ANSI/CSA, AGA, Eurasian CU, RoHS, REACH, EN 161, EN 13611 Compliant |
| Product Family | VAS (single) and VCS (double) solenoid valves for gas |
| POC Indicator Ratings | AC: 12 to 250 V, 3A; DC: 12 to 30 V, 0.1A |
| Operating Modes | Closed when de-energized (fail-safe) |
| LED Indicator | Blue LED when energized |
| Installation Orientation | Upright or horizontal, not upside-down |
| Inlet Pressure Range | 500 mbar (7 psig) |
| Gas Compatibility | Natural Gas, LPG, Biogas, Hydrogen, Clean Air |
| Applications | Commercial heat generation; Gas burners and gas appliances; Industrial furnaces, kilns, ovens, and heat treatment systems; Suitable for hydrogen applications |
| Flow Adjustment Range | 20 to 100% |
| Duty Cycle | 100% |
| Electrical Connections | M20 Cable Gland, Plug, Plug-With-Socket, Dual-Valve Connectors |
| Connection Type | Rp/NPT Internal Threads; ISO Flange; ANSI Flange for .T models |
| Designed Lifetime | 50,000 to 500,000 cycles depending on size |
| Size | 1 to 9 |
| DN | 10 to 125 |
| Mains voltage | 24 V DC, 120 V AC or 230 V AC |
Values retain manufacturer model qualifications. Review Honeywell specifications ↗
Part Number
Published part numbers
10 parts
| Part Number | Description | Enquiry |
|---|---|---|
| 100103006 | VLV,SOLND,SZ 3,NPT,,VAS3T /NQGL,FAST OPN | Request quotation |
| 191002DF | CHASSIS ASSY 230V F-MODEL | Request quotation |
| 23433 | VCS1 (SOV) AND VOS1 (STO) SW | Request quotation |
| KS88000024 | VAS240R/NW | Request quotation |
| KS88000029 | VAS 240R/LW | Request quotation |
| KS88000067 | VLV, KS88003197 SOLND,SZ 2,NPT,,VAS2T /N | Request quotation |
| KS88000077 | VLV,SOLND,SZ 3,NPT,,VAS3T /NQ,FAST OPNG, | Request quotation |
| KS88000081 | VLV,SOLND,SZ 3,NPT,,VAS3T /LQ,SLOW OPNG, | Request quotation |
| KS88000100 | VLV ASSY,SOLND,RP 15,GAS VAS115R/NQSR FA | Request quotation |
| KS88000625 | VAS232R/LK | Request quotation |
Manufacturer sources
Last source check: 2026-11-02
Solenoid valves for gas · Manufacturer ownership retained; republication licence not independently confirmed
Secondary Image for VAS solenoid valves for gas · Manufacturer ownership retained; republication licence not independently confirmed
Secondary Image 3 for VAS solenoid valves for gas · Manufacturer ownership retained; republication licence not independently confirmed
Secondary Image for VAS 1-2-L solenoid valves for gas · Manufacturer ownership retained; republication licence not independently confirmed
ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.
Your next project. A clear starting point.
Tell us about your facility and what you need to achieve.