Fire & Life Safety · Building Systems · Industrial Automation [email protected] +880 1347 561 256
Honeywell Process Measurement & Control

Fuel Delivery Accessories

Non-return gas valves GRS, GRSF

GRS and GRSF prevent reverse flow or gas surge in gas, air or oxygen service.

GRS and GRSF prevent reverse flow or gas surge in gas, air or oxygen service. GRS is explicitly non-flame-arresting; GRSF adds a sintered-bronze element with the stated flame-arresting qualification for combustion air. Threaded/flanged choices and pressure versions must be matched to the medium and installation.

Features & Benefits

Design
Robust
Opening Pressure Range
Low
Pipe Connection Type
Rp Internal Thread (R), Flange to ISO 7005 (F)
Inlet Pressure Range
GRS: Up to 25 bar (DN 15-25), up to 20 bar (DN 40-50), up to 10 bar (DN 80)|GRSF: Up to 5 bar (DN 15-50)
Medium Temperature
GRS: -20 to +70 deg C (GRS 15-50/GRSF 15-50); -20 to +50 deg C with oxygen|GRSF: -20 to +70 deg C (GRSF 15-50); -20 to +50 deg C with oxygen
Flame Arresting
GRS: No (must be used with additional safety device for flashback protection)|GRSF: Yes (stops flashbacks and prevents gas return after flashback)
Nominal Sizes
GRS: DN 15, 20, 25, 40, 50, 80|GRSF: DN 15, 20, 25, 40, 50
Product Type
GRS: Non-return gas valve|GRSF: Non-return gas valve with flame arrester
Approvals
DIN-DVGW tested and registered; EU Pressure Equipment Directive compliant, Internal Thread to ISO 7-1, PN 16 flange to ISO 7005
Material
Brass
Gas Type
GRS: Town/district gas, hydrogen, natural gas, propane, purified biogas, nitrogen, inert gases, compressed air, oxygen|GRSF: Town/district gas, natural gas, propane, compressed air
Purpose
GRS: Prevents reverse gas flow, surges, and creeping|GRSF: Prevents reverse gas flow and flashbacks of combustion gas-air mixtures
DN
15 to 80
pu
max. 100 mbar or 5 bar

Applications

  • Reverse-flow prevention for gas, air or oxygen

Specifications

Overview

Design
Robust
Product Type
GRS: Non-return gas valve; GRSF: Non-return gas valve with flame arrester

Pressure Specifications

Opening Pressure Range
Low
Inlet Pressure Range
GRS: Up to 25 bar (DN 15-25), up to 20 bar (DN 40-50), up to 10 bar (DN 80); GRSF: Up to 5 bar (DN 15-50)

Connections & Interfaces

Pipe Connection Type
Rp Internal Thread (R), Flange to ISO 7005 (F)

Operating/Process Temperature Ranges

Medium Temperature
GRS: -20 to +70 deg C (GRS 15-50/GRSF 15-50); -20 to +50 deg C with oxygen; GRSF: -20 to +70 deg C (GRSF 15-50); -20 to +50 deg C with oxygen

Ignition, Flame & Supervision Specifications

Flame Arresting
GRS: No (must be used with additional safety device for flashback protection); GRSF: Yes (stops flashbacks and prevents gas return after flashback)

Dimensions & Size Specifications

Nominal Sizes
GRS: DN 15, 20, 25, 40, 50, 80; GRSF: DN 15, 20, 25, 40, 50

Standards & Certifications

Approvals
DIN-DVGW tested and registered; EU Pressure Equipment Directive compliant, Internal Thread to ISO 7-1, PN 16 flange to ISO 7005

Material Specifications

Material
Brass

Fuel, Gas & Media Specifications

Gas Type
GRS: Town/district gas, hydrogen, natural gas, propane, purified biogas, nitrogen, inert gases, compressed air, oxygen; GRSF: Town/district gas, natural gas, propane, compressed air

Applications & Compatibility

Purpose
GRS: Prevents reverse gas flow, surges, and creeping; GRSF: Prevents reverse gas flow and flashbacks of combustion gas-air mixtures

Technical Specifications

DN
15 to 80
pu
max. 100 mbar or 5 bar
Non-return gas valves GRS, GRSF — manufacturer page values
ParameterPublished value / configuration
DesignRobust
Product TypeGRS: Non-return gas valve; GRSF: Non-return gas valve with flame arrester
Opening Pressure RangeLow
Inlet Pressure RangeGRS: Up to 25 bar (DN 15-25), up to 20 bar (DN 40-50), up to 10 bar (DN 80); GRSF: Up to 5 bar (DN 15-50)
Pipe Connection TypeRp Internal Thread (R), Flange to ISO 7005 (F)
Medium TemperatureGRS: -20 to +70 deg C (GRS 15-50/GRSF 15-50); -20 to +50 deg C with oxygen; GRSF: -20 to +70 deg C (GRSF 15-50); -20 to +50 deg C with oxygen
Flame ArrestingGRS: No (must be used with additional safety device for flashback protection); GRSF: Yes (stops flashbacks and prevents gas return after flashback)
Nominal SizesGRS: DN 15, 20, 25, 40, 50, 80; GRSF: DN 15, 20, 25, 40, 50
ApprovalsDIN-DVGW tested and registered; EU Pressure Equipment Directive compliant, Internal Thread to ISO 7-1, PN 16 flange to ISO 7005
MaterialBrass
Gas TypeGRS: Town/district gas, hydrogen, natural gas, propane, purified biogas, nitrogen, inert gases, compressed air, oxygen; GRSF: Town/district gas, natural gas, propane, compressed air
PurposeGRS: Prevents reverse gas flow, surges, and creeping; GRSF: Prevents reverse gas flow and flashbacks of combustion gas-air mixtures
DN15 to 80
pumax. 100 mbar or 5 bar

Values retain manufacturer model qualifications. Review Honeywell specifications ↗

Part Number

Published part numbers

10 parts

Part NumberDescriptionEnquiry
03150667GRS 15RRequest quotation
KS03150631GRS 40R01 NON RET GAS VLVRequest quotation
KS03150642VLV,CHK,GRS 80F01Request quotation
KS03150667GRS 15RRequest quotation
KS03150668GRS 20RRequest quotation
KS03150669GRS 25RRequest quotation
KS03150670GRS 40RRequest quotation
KS03150671GRS 50RRequest quotation
KS03150672GRSF 15RRequest quotation
KS03150673GRSF 20RRequest quotation
Manufacturer sources

https://process.honeywell.com/us/en/products/thermal-solutions/fuel-and-air-delivery/accessories/fuel-delivery-accessories/non-return-gas-valves-grs-grsf

Last source check: 2026-11-02

Non-return gas valves · Manufacturer ownership retained; republication licence not independently confirmed

ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.

Your next project. A clear starting point.

Tell us about your facility and what you need to achieve.

CallSend enquiry