Fuel Delivery Accessories
Digital Pressure Control System DPS
Hauck DPS regulates dryer draft or furnace pressure by driving an exhaust damper from a differential-pressure signal.
Hauck DPS regulates dryer draft or furnace pressure by driving an exhaust damper from a differential-pressure signal. A PID controller, transmitter and actuator form the system, with manual controls and a damper-hold function before fan startup. It operates independently or with Hauck BCS equipment; field tubing is supplied separately as stated.
Features & Benefits
- Operating Temperature Range
- -20 to 180 deg F (-29 to 82 deg C)
- Pressure Tap Connection
- 1 in pipe coupling|1/4 in NPT sensing line
- Mounting Requirement
- Vibration‑free, shielded from flame
- Control Algorithms
- Full PID capability
- Transmitter Power
- Integral 30 VDC supply
- Panel Cutout Size
- 4‑1/2 in H x 6‑3/4 in W (114 x 171 mm)
- Controller Type
- Microprocessor‑based
- Sensing Method
- Differential Pressure Transmitter
- Control Method
- Time‑proportional control
- Tubing Length
- 4 ft (1.2 m) for heat dissipation (min)
- Output Relays
- 2 solid‑state relays
- Relay Rating
- 10 A per relay
- Power Supply
- 115 VAC (L1, L2, GND)
- Input Signal
- 4 to 20 mA (pressure transmitter)
- Display Type
- Dual LCD (upper and lower)
- Automatic draft control compensates for measured pressure deviation.
Applications
- Dryer draft control
- Furnace-pressure control
Detailed capabilities
Draft feedback and damper behavior
DPS converts differential-pressure measurement into timed actuator movements. Two solid-state relays drive the exhaust damper in the required direction according to deviation from setpoint, with full PID available. The controller includes transmitter power and manual switches and can hold the damper closed before fan startup. A complete package includes controller, transmitter, cables, actuator and manifold kit; specified stainless field tubing is supplied by others.
Features and benefits
- Automatic draft control compensates for measured pressure deviation.
Published application context
- Dryer draft control
- Furnace-pressure control
Operating/Process Temperature Ranges
- Operating Temperature Range
- -20 to 180 deg F (-29 to 82 deg C)
Connections & Interfaces
- Pressure Tap Connection
- 1 in pipe coupling; 1/4 in NPT sensing line
Installation & Mounting Specifications
- Mounting Requirement
- Vibration‑free, shielded from flame
Control, Logic & Functional Behavior
- Control Algorithms
- Full PID capability
- Controller Type
- Microprocessor‑based
- Control Method
- Time‑proportional control
Electrical Specifications
- Transmitter Power
- Integral 30 VDC supply
- Power Supply
- 115 VAC (L1, L2, GND)
Dimensions & Size Specifications
- Panel Cutout Size
- 4‑1/2 in H x 6‑3/4 in W (114 x 171 mm)
Control, Safety & Functional Behavior
- Sensing Method
- Differential Pressure Transmitter
Dimensions & Length Specifications
- Tubing Length
- 4 ft (1.2 m) for heat dissipation (min)
Inputs, Outputs & Signal Interfaces
- Output Relays
- 2 solid‑state relays
- Relay Rating
- 10 A per relay
- Input Signal
- 4 to 20 mA (pressure transmitter)
Control, Software & User Interface Specifications
- Display Type
- Dual LCD (upper and lower)
Applications & Compatibility
- Applications
- Dryer Draft Control, Furnace Pressure Control
| Parameter | Published value / configuration |
|---|---|
| Operating Temperature Range | -20 to 180 deg F (-29 to 82 deg C) |
| Pressure Tap Connection | 1 in pipe coupling; 1/4 in NPT sensing line |
| Mounting Requirement | Vibration‑free, shielded from flame |
| Control Algorithms | Full PID capability |
| Controller Type | Microprocessor‑based |
| Control Method | Time‑proportional control |
| Transmitter Power | Integral 30 VDC supply |
| Power Supply | 115 VAC (L1, L2, GND) |
| Panel Cutout Size | 4‑1/2 in H x 6‑3/4 in W (114 x 171 mm) |
| Sensing Method | Differential Pressure Transmitter |
| Tubing Length | 4 ft (1.2 m) for heat dissipation (min) |
| Output Relays | 2 solid‑state relays |
| Relay Rating | 10 A per relay |
| Input Signal | 4 to 20 mA (pressure transmitter) |
| Display Type | Dual LCD (upper and lower) |
| Applications | Dryer Draft Control, Furnace Pressure Control |
Values retain manufacturer model qualifications. Review Honeywell specifications ↗
Part Number
Published part numbers
6 parts
| Part Number | Description | Enquiry |
|---|---|---|
| DPSV | Differential Pressure System-VFD | Request quotation |
| HK401730 | INSTRUMENT ASSY,DPS300B,PNL MNT | Request quotation |
| HK401730-001 | INSTRUMENT ASSY,DPS300B 001 W/4 20MA CNT | Request quotation |
| HK55529 | ANG,DPS300 CHAS ATTACH | Request quotation |
| HK55531 | DRLG,DPS300 ENC | Request quotation |
| HK58658X001 | INSTRUMENT ASSY,DPS100 0 1WC | Request quotation |
Manufacturer sources
Last source check: 2026-11-02
Digital Pressure Control System · Manufacturer ownership retained; republication licence not independently confirmed
ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.
Your next project. A clear starting point.