Multivariable Transmitters
MVX800 OEM Pressure Transducer
MVX800 uses the SMV800 sensing platform to supply differential pressure plus absolute or gauge pressure to flow computers and RTUs.
MVX800 uses the SMV800 sensing platform to supply differential pressure plus absolute or gauge pressure to flow computers and RTUs. Measurements are transmitted in multiplexed-pulse form. The MXA845, MXG870 and MXG890 variants provide different pressure combinations, allowing OEMs to obtain two pressure measurements from one device when designing compensated-flow equipment.
Models: MXA845, MXG870, MXG890
Features & Benefits
- Output
- Multiplexed pulse
- Variants
- MXA845, MXG870 and MXG890
- Replaces two separate pressure transducers
Applications
- OEM flow computers and RTUs
Processing & Performance Metrics
- Accuracy
- Up to 0.0375% standard
Environmental Conditions
- Maximum Allowable Working Pressure (MAWP)
- MXA845: 3000 psi (210 bar); MXG870/MXG890: 4500 psi (310 bar)
- Rangeability
- DP: up to 400:1; SP (Absolute): up to 50:1; SP (Gauge): up to 75:1
- Stability
- Up to 0.1% of URL for ten years
Applications & Compatibility
- Measurement Capabilities
- Differential Pressure (DP) and Static Pressure (SP, Absolute or Gauge)
I/O Capabilities
- Technology Base
- Honeywell ST 800 SmartLine Transmitter Technology
- Response Time
- 90 ms millisecond
Standards & Certifications
- Approvals
- ISO15156 for Process Wetted/Non-Wetted Parts, EN10204 Type 3.1 Material Traceability, Certificate of Conformance, Calibration Test Report, Certificate of Origin, Over-Pressure Leak Test Certificate; MR0103; NACE MR0175
Technical Specifications
- Model
- DP | SP
- MXA845
- 0-1000 mbar | 0-104 bara
- MXG870
- 0-1000 mbar | 0-310 barg
- MXG890
- 0-5000 mbar | 0-310 barg
| Parameter | Published value / configuration |
|---|---|
| Accuracy | Up to 0.0375% standard |
| Maximum Allowable Working Pressure (MAWP) | MXA845: 3000 psi (210 bar); MXG870/MXG890: 4500 psi (310 bar) |
| Rangeability | DP: up to 400:1; SP (Absolute): up to 50:1; SP (Gauge): up to 75:1 |
| Stability | Up to 0.1% of URL for ten years |
| Measurement Capabilities | Differential Pressure (DP) and Static Pressure (SP, Absolute or Gauge) |
| Technology Base | Honeywell ST 800 SmartLine Transmitter Technology |
| Response Time | 90 ms millisecond |
| Approvals | ISO15156 for Process Wetted/Non-Wetted Parts, EN10204 Type 3.1 Material Traceability, Certificate of Conformance, Calibration Test Report, Certificate of Origin, Over-Pressure Leak Test Certificate; MR0103; NACE MR0175 |
| Model | DP | SP |
| MXA845 | 0-1000 mbar | 0-104 bara |
| MXG870 | 0-1000 mbar | 0-310 barg |
| MXG890 | 0-5000 mbar | 0-310 barg |
Values retain manufacturer model qualifications. Review Honeywell specifications ↗
Resources
Resources linked from the manufacturer’s page. Confirm the document revision and applicable model before installation or ordering.
Honeywell resource listing ↗Part Number
Published model / variant identifiers. A full ordering code requires the manufacturer configuration.
Published part numbers
2 parts
| Part Number | Description | Enquiry |
|---|---|---|
| MXA845 | MXA845 MV ABS 400"/1500PSIA | Request quotation |
| MXG890 | SMARTLINE MULTIVAR METER BODY MVX890 | Request quotation |
Manufacturer sources
Last source check: 2026-11-02
MVX 800 & 3000 OEM Pressure Transducer Image · Manufacturer ownership retained; republication licence not independently confirmed
ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.
Your next project. A clear starting point.
Tell us about your facility and what you need to achieve.