Fire & Life Safety · Building Systems · Industrial Automation [email protected] +880 1347 561 256
Honeywell Process Measurement & Control

Level Transmitters

SmartLine RM Series - Non-Contact Radar Level Meter

RM-series non-contact meters use FMCW radar to measure distance and level and derive volume or mass.

RM-series non-contact meters use FMCW radar to measure distance and level and derive volume or mass. The RM70 is configured for liquids, while the RM60 addresses powders and granulates. Honeywell identifies agitated vessels and demanding process conditions as suitable uses, with published measuring distances up to 80 m depending on the selected configuration.

Models: RM750, RM540, RM77, RM740

Features & Benefits

Versions
RM70 for liquids
  • Supports measurements in agitated vessels

Applications

  • Liquid and granular-product level
  • LPG and LNG

Detailed capabilities

What Is It?

RM70 electronics address liquids while RM60 addresses powders or granulates, including the stated LPG/LNG and agitated-vessel duties. The page lists range to 80 m, flange temperature to 200°C and pressure to 40 barg. Its accuracy appears as '±3 mm/±0.04' in the source; the incomplete second unit is retained as a source ambiguity rather than silently corrected or converted.

Manufacturer reference ↗

How Does It Work?

FMCW frequency rises linearly through the measurement phase. The reflected signal returns after a distance-related delay, and its frequency difference from the current transmitted wave determines the surface distance. A second current output can report another calculated quantity such as volume. Interchangeable horn or drop antennas adapt the installation without changing the RM70/RM60 material-role distinction.

Manufacturer reference ↗

What Problems Does It Solve?

The source describes FMCW as stable in agitated conditions and useful across a wider application range than pulse-time-of-flight radar. Reduced sensitivity to changes in conductivity, density, pressure and temperature supports process measurement where earlier technologies were difficult. These statements belong to the configured RM meter and do not replace its pressure, flange-temperature or antenna selection requirements.

Manufacturer reference ↗

Specifications

Overview

Models
RM750, RM540, RM77, RM740

Measurement & Sensor Related (Measurement Capabilities)

Measurement Principle
FMCW (Frequency Modulated Continuous Wave) Radar
Repeatability
±1 mm

Processing & Performance Metrics

Minimum Tank Height
0.2 m, 1 m
Measured Parameters
Distance, Level, Volume, Mass, Flow Rate
Application Range
Liquids, Pastes, Slurries
Software
PACTware™ and DTM (Device Type Manager) for configuration
Accuracy
±2 mm (≤10 m)

Communication Interfaces

Interface Languages
English, French, German, Italian, Spanish, Portuguese, Chinese, Japanese, Russian, Czech, Polish, Turkish

Environmental Conditions

Ambient Temperature
-40 to +80 deg C (-40 to +176 deg F)

Material Specifications

Housing Material
Polyester-Coated Aluminum (Standard); Stainless Steel (Option)

Technical Specifications

Resolution
1 mm

Electrical Specifications

Frequency
W-band (78 to 82 GHz), K-band (24 to 26 GHz), X-band (8.5…10.6 GHz)

Standards & Certifications

Approvals
CE, ATEX, IECEx, cQPSus, NAMUR NE 21/43/53/107, EMC, RED, FCC, Industry Canada, NACE MR0175/0103/ISO 15156

Software & Interface

Display
Backlit LCD, 128×64 pixels, 4-button keypad, 12 languages
SmartLine RM Series - Non-Contact Radar Level Meter — manufacturer page values
ParameterPublished value / configuration
ModelsRM750, RM540, RM77, RM740
Measurement PrincipleFMCW (Frequency Modulated Continuous Wave) Radar
Repeatability±1 mm
Minimum Tank Height0.2 m, 1 m
Measured ParametersDistance, Level, Volume, Mass, Flow Rate
Application RangeLiquids, Pastes, Slurries
SoftwarePACTware™ and DTM (Device Type Manager) for configuration
Accuracy±2 mm (≤10 m)
Interface LanguagesEnglish, French, German, Italian, Spanish, Portuguese, Chinese, Japanese, Russian, Czech, Polish, Turkish
Ambient Temperature-40 to +80 deg C (-40 to +176 deg F)
Housing MaterialPolyester-Coated Aluminum (Standard); Stainless Steel (Option)
Resolution1 mm
FrequencyW-band (78 to 82 GHz), K-band (24 to 26 GHz), X-band (8.5…10.6 GHz)
ApprovalsCE, ATEX, IECEx, cQPSus, NAMUR NE 21/43/53/107, EMC, RED, FCC, Industry Canada, NACE MR0175/0103/ISO 15156
DisplayBacklit LCD, 128×64 pixels, 4-button keypad, 12 languages

Values retain manufacturer model qualifications. Review Honeywell specifications ↗

Resources

Filter documents by type
NameLast checkedType

Resources linked from the manufacturer’s page. Confirm the document revision and applicable model before installation or ordering.

Honeywell resource listing ↗

Part Number

Published model / variant identifiers. A full ordering code requires the manufacturer configuration.

Manufacturer sources

https://process.honeywell.com/us/en/products/field-instruments/level-transmitters/smartline-rm-series-non-contact-radar-level-meter

Last source check: 2026-11-02