Level Transmitters
SmartLine RM Series - Non-Contact Radar Level Meter
RM-series non-contact meters use FMCW radar to measure distance and level and derive volume or mass.
RM-series non-contact meters use FMCW radar to measure distance and level and derive volume or mass. The RM70 is configured for liquids, while the RM60 addresses powders and granulates. Honeywell identifies agitated vessels and demanding process conditions as suitable uses, with published measuring distances up to 80 m depending on the selected configuration.
Models: RM750, RM540, RM77, RM740
Features & Benefits
- Versions
- RM70 for liquids
- Supports measurements in agitated vessels
Applications
- Liquid and granular-product level
- LPG and LNG
Detailed capabilities
What Is It?
RM70 electronics address liquids while RM60 addresses powders or granulates, including the stated LPG/LNG and agitated-vessel duties. The page lists range to 80 m, flange temperature to 200°C and pressure to 40 barg. Its accuracy appears as '±3 mm/±0.04' in the source; the incomplete second unit is retained as a source ambiguity rather than silently corrected or converted.
How Does It Work?
FMCW frequency rises linearly through the measurement phase. The reflected signal returns after a distance-related delay, and its frequency difference from the current transmitted wave determines the surface distance. A second current output can report another calculated quantity such as volume. Interchangeable horn or drop antennas adapt the installation without changing the RM70/RM60 material-role distinction.
What Problems Does It Solve?
The source describes FMCW as stable in agitated conditions and useful across a wider application range than pulse-time-of-flight radar. Reduced sensitivity to changes in conductivity, density, pressure and temperature supports process measurement where earlier technologies were difficult. These statements belong to the configured RM meter and do not replace its pressure, flange-temperature or antenna selection requirements.
Overview
- Models
- RM750, RM540, RM77, RM740
Measurement & Sensor Related (Measurement Capabilities)
- Measurement Principle
- FMCW (Frequency Modulated Continuous Wave) Radar
- Repeatability
- ±1 mm
Processing & Performance Metrics
- Minimum Tank Height
- 0.2 m, 1 m
- Measured Parameters
- Distance, Level, Volume, Mass, Flow Rate
- Application Range
- Liquids, Pastes, Slurries
- Software
- PACTware™ and DTM (Device Type Manager) for configuration
- Accuracy
- ±2 mm (≤10 m)
Communication Interfaces
- Interface Languages
- English, French, German, Italian, Spanish, Portuguese, Chinese, Japanese, Russian, Czech, Polish, Turkish
Environmental Conditions
- Ambient Temperature
- -40 to +80 deg C (-40 to +176 deg F)
Material Specifications
- Housing Material
- Polyester-Coated Aluminum (Standard); Stainless Steel (Option)
Technical Specifications
- Resolution
- 1 mm
Electrical Specifications
- Frequency
- W-band (78 to 82 GHz), K-band (24 to 26 GHz), X-band (8.5…10.6 GHz)
Standards & Certifications
- Approvals
- CE, ATEX, IECEx, cQPSus, NAMUR NE 21/43/53/107, EMC, RED, FCC, Industry Canada, NACE MR0175/0103/ISO 15156
Software & Interface
- Display
- Backlit LCD, 128×64 pixels, 4-button keypad, 12 languages
| Parameter | Published value / configuration |
|---|---|
| Models | RM750, RM540, RM77, RM740 |
| Measurement Principle | FMCW (Frequency Modulated Continuous Wave) Radar |
| Repeatability | ±1 mm |
| Minimum Tank Height | 0.2 m, 1 m |
| Measured Parameters | Distance, Level, Volume, Mass, Flow Rate |
| Application Range | Liquids, Pastes, Slurries |
| Software | PACTware™ and DTM (Device Type Manager) for configuration |
| Accuracy | ±2 mm (≤10 m) |
| Interface Languages | English, French, German, Italian, Spanish, Portuguese, Chinese, Japanese, Russian, Czech, Polish, Turkish |
| Ambient Temperature | -40 to +80 deg C (-40 to +176 deg F) |
| Housing Material | Polyester-Coated Aluminum (Standard); Stainless Steel (Option) |
| Resolution | 1 mm |
| Frequency | W-band (78 to 82 GHz), K-band (24 to 26 GHz), X-band (8.5…10.6 GHz) |
| Approvals | CE, ATEX, IECEx, cQPSus, NAMUR NE 21/43/53/107, EMC, RED, FCC, Industry Canada, NACE MR0175/0103/ISO 15156 |
| Display | Backlit LCD, 128×64 pixels, 4-button keypad, 12 languages |
Values retain manufacturer model qualifications. Review Honeywell specifications ↗
Resources
Resources linked from the manufacturer’s page. Confirm the document revision and applicable model before installation or ordering.
Honeywell resource listing ↗Part Number
Published model / variant identifiers. A full ordering code requires the manufacturer configuration.
Manufacturer sources
Last source check: 2026-11-02
SmartLine RM Series – Non-Contact Radar Level Meter Image · Manufacturer ownership retained; republication licence not independently confirmed
ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.
Your next project. A clear starting point.
Tell us about your facility and what you need to achieve.