Fire & Life Safety · Building Systems · Industrial Automation [email protected] +880 1347 561 256
Honeywell Process Measurement & Control

Sensors

DG Smart Pressure Sensor

DG Smart measures low-pressure combustion air or fuel gas in relative- or differential-pressure versions.

DG Smart measures low-pressure combustion air or fuel gas in relative- or differential-pressure versions. Local LCD/LED indication complements Modbus TCP and a failsafe NAMUR 4–20 mA output. The page states SIL 2 capability through that analog output under IEC 61508, rather than assigning the qualification to every communication path.

Features & Benefits

Ambient Temperature Range
-20 to +70 deg C (extended)|0 to 60 deg C (standard)
Communication Interfaces
Fast Ethernet (10/100 Mbit/s), Modbus TCP
Maximum Under Pressure
Differential: -0.2 kPa, -0.5 kPa, -1 kPa|Relative: -1 kPa, -3.5 kPa, -10 kPa
Electrical Connections
M12 connector (A-coded for power, D-coded for Ethernet)
Storage Temperature
-20 to +60 deg C
Installation Height
Max. 2000 m AMSL
Designed Lifetime
10 years
Housing Material
Upper: PBT plastic; Lower: AlSi 12
Enclosure Rating
IP65, NEMA Type 4 indoor
Applicable Media
Gas, air, flue gas, biogas (≤0.1% H₂S), hydrogen, and air (differential)
Measuring Range
Differential: 0-20 mbar, 0-50 mbar, 0-100 mbar|Relative: 0-100 mbar, 0-350 mbar, 0-1000 mbar
Gas Connections
Rp 1/4 or 1/4 in NPT
Output Signal
4 to 20 mA (NAMUR NE 43 or standard), Modbus TCP
Product Type
Digital gas pressure sensor/pressure transmitter with MIN/MAX monitoring
Power Supply
24 VDC ±20%, SELV/PELV
Overpressure
Differential: 2.2 kPa (20 mbar), 5.5 kPa (50 mbar), 11 kPa (100 mbar)|Relative: 12 kPa (100 mbar), 40 kPa (350 mbar), 110 kPa (1000 mbar)
Approvals
EN 1854, EN 13611, EN 60730‑1/‑2‑6, IEC 60730, IEC 61508, CE (GAR), UL Listed, FM Approved, REACH, China RoHS
  • Local indication and two signal paths make measurements accessible.

Applications

  • Low-pressure combustion-air and fuel-gas measurement

Detailed capabilities

Two pressure-sensing forms and two output paths

DG Smart is available for relative or differential pressure in low-pressure combustion air and fuel-gas systems. Its local LCD and LEDs permit inspection at the device. Modbus TCP provides digital communication alongside the NAMUR 4–20 mA output, allowing the instrument to communicate pressure while retaining the stated failsafe analog path.

Manufacturer reference ↗

Functional-safety qualification

The page describes SIL 2 capability under IEC 61508 specifically through the failsafe analog output. That statement does not assign the same safety role to every network signal or make the transmitter an independent burner-safety system. The manufacturer directs detailed selection to its technical information, with the pressure-sensing form and signal path established for the actual control architecture.

Manufacturer reference ↗

Features and benefits

  • Local indication and two signal paths make measurements accessible.

Manufacturer reference ↗

Published application context

  • Low-pressure combustion-air and fuel-gas measurement

Manufacturer reference ↗

Specifications

Environmental Conditions

Ambient Temperature Range
-20 to +70 deg C (extended); 0 to 60 deg C (standard)
Enclosure Rating
IP65, NEMA Type 4 indoor

Communication & Interfaces

Communication Interfaces
Fast Ethernet (10/100 Mbit/s), Modbus TCP

Pressure Specifications

Maximum Under Pressure
Differential: -0.2 kPa, -0.5 kPa, -1 kPa; Relative: -1 kPa, -3.5 kPa, -10 kPa
Overpressure
Differential: 2.2 kPa (20 mbar), 5.5 kPa (50 mbar), 11 kPa (100 mbar); Relative: 12 kPa (100 mbar), 40 kPa (350 mbar), 110 kPa (1000 mbar)

Connections & Interfaces

Electrical Connections
M12 connector (A-coded for power, D-coded for Ethernet)
Gas Connections
Rp 1/4 or 1/4 in NPT

Storage/Transport Temperatures

Storage Temperature
-20 to +60 deg C

Dimensions & Weight

Installation Height
Max. 2000 m AMSL

Operating Limits, Durability & Lifecycle

Designed Lifetime
10 years

Material Specifications

Housing Material
Upper: PBT plastic; Lower: AlSi 12

Fuel, Gas & Media Specifications

Applicable Media
Gas, air, flue gas, biogas (≤0.1% H₂S), hydrogen, and air (differential)

Processing & Performance Metrics

Measuring Range
Differential: 0-20 mbar, 0-50 mbar, 0-100 mbar; Relative: 0-100 mbar, 0-350 mbar, 0-1000 mbar

Inputs, Outputs & Signal Interfaces

Output Signal
4 to 20 mA (NAMUR NE 43 or standard), Modbus TCP

Overview

Product Type
Digital gas pressure sensor/pressure transmitter with MIN/MAX monitoring

Electrical Specifications

Power Supply
24 VDC ±20%, SELV/PELV

Standards & Certifications

Approvals
EN 1854, EN 13611, EN 60730‑1/‑2‑6, IEC 60730, IEC 61508, CE (GAR), UL Listed, FM Approved, REACH, China RoHS
DG Smart Pressure Sensor — manufacturer page values
ParameterPublished value / configuration
Ambient Temperature Range-20 to +70 deg C (extended); 0 to 60 deg C (standard)
Enclosure RatingIP65, NEMA Type 4 indoor
Communication InterfacesFast Ethernet (10/100 Mbit/s), Modbus TCP
Maximum Under PressureDifferential: -0.2 kPa, -0.5 kPa, -1 kPa; Relative: -1 kPa, -3.5 kPa, -10 kPa
OverpressureDifferential: 2.2 kPa (20 mbar), 5.5 kPa (50 mbar), 11 kPa (100 mbar); Relative: 12 kPa (100 mbar), 40 kPa (350 mbar), 110 kPa (1000 mbar)
Electrical ConnectionsM12 connector (A-coded for power, D-coded for Ethernet)
Gas ConnectionsRp 1/4 or 1/4 in NPT
Storage Temperature-20 to +60 deg C
Installation HeightMax. 2000 m AMSL
Designed Lifetime10 years
Housing MaterialUpper: PBT plastic; Lower: AlSi 12
Applicable MediaGas, air, flue gas, biogas (≤0.1% H₂S), hydrogen, and air (differential)
Measuring RangeDifferential: 0-20 mbar, 0-50 mbar, 0-100 mbar; Relative: 0-100 mbar, 0-350 mbar, 0-1000 mbar
Output Signal4 to 20 mA (NAMUR NE 43 or standard), Modbus TCP
Product TypeDigital gas pressure sensor/pressure transmitter with MIN/MAX monitoring
Power Supply24 VDC ±20%, SELV/PELV
ApprovalsEN 1854, EN 13611, EN 60730‑1/‑2‑6, IEC 60730, IEC 61508, CE (GAR), UL Listed, FM Approved, REACH, China RoHS

Values retain manufacturer model qualifications. Review Honeywell specifications ↗

Part Number

Published part numbers

10 parts

Part NumberDescriptionEnquiry
KS74926394Ethernet cable for use with DG SmartRequest quotation
KS7492639524V Connector M12 DG SmartRequest quotation
KS84450000DGS 100A-R8TX-MRequest quotation
KS84450001GAS PRESS. SENSOR DGS 350A-R8TX-MRequest quotation
KS84450002Gas Press. Sensor DGS 1000A-R8TX-MRequest quotation
KS84450100GAS PRESS. SENSOR DGS 100A-N8TX-MRequest quotation
KS84450101Gas Press. Sensor DGS 350A-N8TX-MRequest quotation
KS84450102Gas Press. Sensor DGS 1000A-N8TX-MRequest quotation
KS84450200Gas Press. Sensor DGS 100C-R8TX-MRequest quotation
KS84450201Gas Press. Sensor DGS 350C-R8TX-MRequest quotation
Manufacturer sources

https://process.honeywell.com/us/en/products/thermal-solutions/fuel-and-air-delivery/sensors/dg-smart-pressure-sensor

Last source check: 2026-11-02

DG Smart product image · Manufacturer ownership retained; republication licence not independently confirmed

DG Smart Gauge Pressure Sensor additional image · Manufacturer ownership retained; republication licence not independently confirmed

DG Smart Gauge Pressure Sensor additional image (2) · Manufacturer ownership retained; republication licence not independently confirmed

ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.

Your next project. A clear starting point.

Tell us about your facility and what you need to achieve.

CallSend enquiry