Manual Valves & Filters
Thermal equipment trips TAS
TAS automatically closes a gas line when exposed to the published thermal trip condition.
TAS automatically closes a gas line when exposed to the published thermal trip condition. The steel device is described as high-temperature resistant and suitable for natural gas, town gas and LPG. Threaded or flanged versions cover the stated size range, with certification and German installation-rule references provided by the manufacturer.
Features & Benefits
- Sizes
- DN 15 to 200 (variant dependent)
- High‑Temperature Tightness (HTB)
- Minimum 60 minutes at 650 deg C
- Thermal Trigger Temperature
- 95 deg C ± 5 deg C
- Ambient Temperature Range
- -20 to +60 deg C
- Installation Orientation
- Any; minimum 20 mm wall clearance
- Maintenance Interval
- Replace valve after thermal trip
- Inlet Pressure Range
- Up to 5 bar (GT5), or 16 bar with HT screws and flange seals
- Thermal Resistance
- 650 deg C for at least 60 minutes
- Connection Type
- Inlet - Rp Internal Thread (ISO 7‑1), PN16 flanged (ISO7005), Outlet - Rp Internal Thread + R male thread (ISO 7‑1), PN16 flanged (ISO 7005)
- Leakage Rating
- ≤ 30 l/h at 4 bar test pressure
- Closing Time
- ≤60 seconds
- Functions
- Automatically shuts off gas flow in case of fire; thermally triggered safety shut‑off device per DIN 3586
- Approvals
- DVGW G 260, DIN EN 331, DIN 3586
- Material
- Steel, Galvanized
- Gas Type
- Natural Gas, Town Gas, LPG (gaseous)
- DN
- 10-200
- pu
- max. 5 bar
Applications
- Heat-triggered gas-line shutdown
Dimensions & Size Specifications
- Sizes
- DN 15 to 200 (variant dependent)
Maximum/Minimum Temperature Limits
- High‑Temperature Tightness (HTB)
- Minimum 60 minutes at 650 deg C
- Thermal Trigger Temperature
- 95 deg C ± 5 deg C
Environmental Conditions
- Ambient Temperature Range
- -20 to +60 deg C
Installation & Mounting Specifications
- Installation Orientation
- Any; minimum 20 mm wall clearance
Electrical Specifications
- Maintenance Interval
- Replace valve after thermal trip
Pressure Specifications
- Inlet Pressure Range
- Up to 5 bar (GT5), or 16 bar with HT screws and flange seals
Temperature & Thermal Specifications
- Thermal Resistance
- 650 deg C for at least 60 minutes
Connections & Interfaces
- Connection Type
- Inlet - Rp Internal Thread (ISO 7‑1), PN16 flanged (ISO7005), Outlet - Rp Internal Thread + R male thread (ISO 7‑1), PN16 flanged (ISO 7005)
Safety, Protection & Reliability
- Leakage Rating
- ≤ 30 l/h at 4 bar test pressure
Actuation, Valve & Motion Control Specifications
- Closing Time
- ≤60 seconds
Applications & Compatibility
- Applications
- Gas Pressure Control Systems, Gas Inlet Systems, Kitchens, Boilers, Instantaneous Water Heaters, Commercial And Industrial Gas Installations
Control, Logic & Functional Behavior
- Functions
- Automatically shuts off gas flow in case of fire; thermally triggered safety shut‑off device per DIN 3586
Standards & Certifications
- Approvals
- DVGW G 260, DIN EN 331, DIN 3586
Material Specifications
- Material
- Steel, Galvanized
Fuel, Gas & Media Specifications
- Gas Type
- Natural Gas, Town Gas, LPG (gaseous)
Technical Specifications
- DN
- 10-200
- pu
- max. 5 bar
| Parameter | Published value / configuration |
|---|---|
| Sizes | DN 15 to 200 (variant dependent) |
| High‑Temperature Tightness (HTB) | Minimum 60 minutes at 650 deg C |
| Thermal Trigger Temperature | 95 deg C ± 5 deg C |
| Ambient Temperature Range | -20 to +60 deg C |
| Installation Orientation | Any; minimum 20 mm wall clearance |
| Maintenance Interval | Replace valve after thermal trip |
| Inlet Pressure Range | Up to 5 bar (GT5), or 16 bar with HT screws and flange seals |
| Thermal Resistance | 650 deg C for at least 60 minutes |
| Connection Type | Inlet - Rp Internal Thread (ISO 7‑1), PN16 flanged (ISO7005), Outlet - Rp Internal Thread + R male thread (ISO 7‑1), PN16 flanged (ISO 7005) |
| Leakage Rating | ≤ 30 l/h at 4 bar test pressure |
| Closing Time | ≤60 seconds |
| Applications | Gas Pressure Control Systems, Gas Inlet Systems, Kitchens, Boilers, Instantaneous Water Heaters, Commercial And Industrial Gas Installations |
| Functions | Automatically shuts off gas flow in case of fire; thermally triggered safety shut‑off device per DIN 3586 |
| Approvals | DVGW G 260, DIN EN 331, DIN 3586 |
| Material | Steel, Galvanized |
| Gas Type | Natural Gas, Town Gas, LPG (gaseous) |
| DN | 10-200 |
| pu | max. 5 bar |
Values retain manufacturer model qualifications. Review Honeywell specifications ↗
Part Number
Published part numbers
10 parts
| Part Number | Description | Enquiry |
|---|---|---|
| KS03352221 | FLG,WL HT DN 25 | Request quotation |
| KS03352222 | FLG,WL HT DN 32 | Request quotation |
| KS03352223 | FLG,WL HT DN 40 | Request quotation |
| KS03352224 | FLG,WL HT DN 50 | Request quotation |
| KS03352225 | FLG,WL HT DN 65 | Request quotation |
| KS03352226 | FLG,WL HT DN 80 | Request quotation |
| KS03352227 | FLG,WL HT DN 100 | Request quotation |
| KS03352228 | FLG,WL HT DN 125 | Request quotation |
| KS03352229 | FLG,WL HT DN 150 | Request quotation |
| KS03352230 | FLG,WL HT DN 200 | Request quotation |
Manufacturer sources
Last source check: 2026-11-02
Thermal equipment trips · Manufacturer ownership retained; republication licence not independently confirmed
ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.
Your next project. A clear starting point.
Tell us about your facility and what you need to achieve.