Manual Valves & Filters

Manual valves with thermal equipment trip AKT..TAS

AKT..TAS combines manual gas isolation with automatic heat-triggered closure.

AKT..TAS combines manual gas isolation with automatic heat-triggered closure. The high-temperature-resistant arrangement has a published trip point of 95°C ±5 K. The source calls for WL-HT seals at the inlet and identifies the applicable German installation rules, with threaded/flanged sizes and pressure versions selected for the installation.

Features & Benefits

Ambient Temperature Range
-20 to +60 deg C
Thermal Trip Temperature
Trip activation at 95 deg C ± 5 deg C, 95 deg C ± 5 deg C
Installation Orientation
Any; minimum 20 mm wall clearance
Maintenance Interval
Replace valve after thermal trip
Inlet Pressure Range
Up to 5 bar (GT5), or 16 bar with HT screws and flange seals
Media Compatibility
Natural Gas, Town Gas, LPG (gaseous)
Thermal Resistance
650 deg C for at least 60 minutes
Product Variants
AKT..F..TAS - Flanged manual valve with integrated thermal equipment trip|AKT..R..TAS - Threaded manual valve with integrated thermal equipment trip
Connection Type
Inlet - Rp internal thread (ISO 7‑1) or PN16 flange (ISO 7005), Outlet - Rp internal thread/R male thread, PN16 flange (ISO 7005)
Leakage Rating
≤ 30 l/h at 4 bar test pressure
Seal Material
PTFE (Teflon) ball seals; Viton spindle seal
Nominal Sizes
DN 15 to 150 (variant dependent)
Closing Time
60 seconds
Valve Type
Manually operated ball valve with automatic thermal shut‑off
Functions
Manual main shut‑off valve for gas; automatically isolates gas pipelines in the event of a fire
Approvals
Compliant with TRGI (DVGW G 600) and German Firing System Directive, Gas Appliances Directive; DIN EN 331; DIN 3586, DVGW test marks for specific AKT..TAS variants
Material
Brass (threaded versions), Ductile iron/steel (flanged versions), TAS housing steel, galvanized
DN
10-150
pu
max. 4 or 5 bar
  • Thermal closure provides automatic gas isolation on overheating.

Applications

  • Manual gas isolation with thermal shutdown

Specifications

Environmental Conditions

Ambient Temperature Range
-20 to +60 deg C

Maximum/Minimum Temperature Limits

Thermal Trip Temperature
Trip activation at 95 deg C ± 5 deg C, 95 deg C ± 5 deg C

Installation & Mounting Specifications

Installation Orientation
Any; minimum 20 mm wall clearance

Electrical Specifications

Maintenance Interval
Replace valve after thermal trip

Pressure Specifications

Inlet Pressure Range
Up to 5 bar (GT5), or 16 bar with HT screws and flange seals

Applications & Compatibility

Media Compatibility
Natural Gas, Town Gas, LPG (gaseous)

Temperature & Thermal Specifications

Thermal Resistance
650 deg C for at least 60 minutes

Product Overview & Classification

Product Variants
AKT..F..TAS - Flanged manual valve with integrated thermal equipment trip; AKT..R..TAS - Threaded manual valve with integrated thermal equipment trip

Connections & Interfaces

Connection Type
Inlet - Rp internal thread (ISO 7‑1) or PN16 flange (ISO 7005), Outlet - Rp internal thread/R male thread, PN16 flange (ISO 7005)

Safety, Protection & Reliability

Leakage Rating
≤ 30 l/h at 4 bar test pressure

Material Specifications

Seal Material
PTFE (Teflon) ball seals; Viton spindle seal
Material
Brass (threaded versions), Ductile iron/steel (flanged versions), TAS housing steel, galvanized

Dimensions & Size Specifications

Nominal Sizes
DN 15 to 150 (variant dependent)

Actuation, Valve & Motion Control Specifications

Closing Time
60 seconds
Valve Type
Manually operated ball valve with automatic thermal shut‑off

Control, Logic & Functional Behavior

Functions
Manual main shut‑off valve for gas; automatically isolates gas pipelines in the event of a fire

Standards & Certifications

Approvals
Compliant with TRGI (DVGW G 600) and German Firing System Directive, Gas Appliances Directive; DIN EN 331; DIN 3586, DVGW test marks for specific AKT..TAS variants

Technical Specifications

DN
10-150
pu
max. 4 or 5 bar
Manual valves with thermal equipment trip AKT..TAS — manufacturer page values
ParameterPublished value / configuration
Ambient Temperature Range-20 to +60 deg C
Thermal Trip TemperatureTrip activation at 95 deg C ± 5 deg C, 95 deg C ± 5 deg C
Installation OrientationAny; minimum 20 mm wall clearance
Maintenance IntervalReplace valve after thermal trip
Inlet Pressure RangeUp to 5 bar (GT5), or 16 bar with HT screws and flange seals
Media CompatibilityNatural Gas, Town Gas, LPG (gaseous)
Thermal Resistance650 deg C for at least 60 minutes
Product VariantsAKT..F..TAS - Flanged manual valve with integrated thermal equipment trip; AKT..R..TAS - Threaded manual valve with integrated thermal equipment trip
Connection TypeInlet - Rp internal thread (ISO 7‑1) or PN16 flange (ISO 7005), Outlet - Rp internal thread/R male thread, PN16 flange (ISO 7005)
Leakage Rating≤ 30 l/h at 4 bar test pressure
Seal MaterialPTFE (Teflon) ball seals; Viton spindle seal
MaterialBrass (threaded versions), Ductile iron/steel (flanged versions), TAS housing steel, galvanized
Nominal SizesDN 15 to 150 (variant dependent)
Closing Time60 seconds
Valve TypeManually operated ball valve with automatic thermal shut‑off
FunctionsManual main shut‑off valve for gas; automatically isolates gas pipelines in the event of a fire
ApprovalsCompliant with TRGI (DVGW G 600) and German Firing System Directive, Gas Appliances Directive; DIN EN 331; DIN 3586, DVGW test marks for specific AKT..TAS variants
DN10-150
pumax. 4 or 5 bar

Values retain manufacturer model qualifications. Review Honeywell specifications ↗

Manufacturer sources

https://process.honeywell.com/us/en/products/thermal-solutions/fuel-and-air-delivery/manual-valves-and-filters/manual-valves-with-thermal-equipment-trip-akt-tas

Last source check: 2026-11-02

Manual valves with thermal equipment trip · Manufacturer ownership retained; republication licence not independently confirmed

ABID Automation LTD maintains this independent product reference. Honeywell owns its product names and trademarks. Current manufacturer documentation governs specification, availability and certification.

Your next project. A clear starting point.

Tell us about your facility and what you need to achieve.

CallSend enquiry